2014-06-06 07:50:462010 FBC
  
 DENIED BY BUILDING
  
 1) SPECIFY THE REQUIRED TRUSS DESIGN LOADS ON THE
 PLANS. FBC R802.1.6.1
  
 2) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR THE
 THREE ROOF ZONES ON THE PLANS. FBC R301.2.1.1 AND
 FIGURE R301.2(7)
  
 3) SPECIFY THE ROOF SHEATHING NAILING REQUIREMENTS ON
 THE PLANS. FBC R803.2.3.1
  
 4) SHOW COMPLIANCE WITH FBC R806 FOR REQUIRED ROOF
 VENTILATION.
  
 5) SHOW COMPLIANCE WITH FBC R807.1 FOR ATTIC ACCESS TO
 THE ADDITION.
  
 6) THE PRODUCT APPROVALS REQUIRED BY DCA RULE 9N-3 ARE
 REQUIRED TO BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. CITY AMENDMENTS 107.3.4.1
  
 7) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 STRUCTURAL WINDOW MULLIONS, THE AWNING WINDOW (
 BATHROOM ) AND THE METAL ROOF. DCA RULE 9N-3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]