| Plan Review Notes For Permit 14050264 |
| Permit Number |
14050264 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-06-06 07:50:46 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) SPECIFY THE REQUIRED TRUSS DESIGN LOADS ON THE | | | PLANS. FBC R802.1.6.1 | | | | | | 2) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR THE | | | THREE ROOF ZONES ON THE PLANS. FBC R301.2.1.1 AND | | | FIGURE R301.2(7) | | | | | | 3) SPECIFY THE ROOF SHEATHING NAILING REQUIREMENTS ON | | | THE PLANS. FBC R803.2.3.1 | | | | | | 4) SHOW COMPLIANCE WITH FBC R806 FOR REQUIRED ROOF | | | VENTILATION. | | | | | | 5) SHOW COMPLIANCE WITH FBC R807.1 FOR ATTIC ACCESS TO | | | THE ADDITION. | | | | | | 6) THE PRODUCT APPROVALS REQUIRED BY DCA RULE 9N-3 ARE | | | REQUIRED TO BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. CITY AMENDMENTS 107.3.4.1 | | | | | | 7) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE | | | STRUCTURAL WINDOW MULLIONS, THE AWNING WINDOW ( | | | BATHROOM ) AND THE METAL ROOF. DCA RULE 9N-3 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|