2014-07-16 11:00:23DATE: 7/14/2014
 PROJECT: SHOUTE KARAOKE
 PERMIT#: 14050254
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) INDICATE CIRCUITRY WITH MEANS OF DISCONNECT ON THE
 FLOOR PLAN AND ON A PANELS SCHEDULE FOR EF-1, AND THE
 MOTORIZED DAMPERS FOR MECHANICAL SYSTEMS.
 A DISCONNECTING MEANS FOR THE MOTOR SHALL BE LOCATED IN
 SIGHT FROM THE MOTOR LOCATION AND THE DRIVEN MACHINERY
 LOCATION. 430.102(B)(1), .FBC 107.2.1.3, NEC 440.11
  
 2) PROVIIDE MANUFACTURERS'S DATA SHEET FOR ELEVATOR
 LIFT TO INDICATE CODE COMPLIANCE WITH NEC110.3, 110.58,
 430.102(B)(1), 620, FBC 107.2.1.3,
  
 3) PROVIDE MANUFACTURERS'S DATA SHEET FOR LED RIBBON
 LIGHTING AND ASSOCIATED REMOTE TRANSFORMERS. NEC110.3,
 110.58, 411
  
 4) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 5) FIRE ALARM SYSTEM NOTES SHALL INDICATE COMPLIANCE
 WITH NFPA 72 WITH REGARDS TO: (A) SMOKE DETECTOR
 PLACEMENT NEAR THE ELEVATOR LOBBY AND ELEVATOR RECAL.
 (B) AUXILIARY AUDIO SYSTEMS SHALL BE AUTOMATICALLY
 MUTED BY THE FIRE ALARM CONTROL PANEL IN THE EVENT OF
 AN ALARM CONDITION.
  
 6) PLEASE INDICATE COMPLIANCE WITH THE FBC - ENERGY FOR
 INTERIOR AND EXTERIOR LIGHTING CONTROL. SEE THE
 FOLLOWING CODE REFERENCE:
  
 ELECTRICAL POWER AND LIGHTING SYSTEMS. (MANDATORY)
 SECTION 505
 505.2.2 AUTOMATIC LIGHTING SHUTOFF.
 BUILDINGS LARGER THAN 5,000 SQUARE FEET (465 M2) SHALL
 BE EQUIPPED WITH AN AUTOMATIC CONTROL DEVICE TO SHUT
 OFF LIGHTING IN THOSE AREAS. THIS AUTOMATIC CONTROL
 DEVICE SHALL FUNCTION ON EITHER:
 1. A SCHEDULED BASIS, USING TIME-OF-DAY, WITH AN
 INDEPENDENT PROGRAM SCHEDULE THAT CONTROLS THE INTERIOR
 LIGHTING IN AREAS THAT DO NOT EXCEED 25,000 SQUARE FEET
 (2323 M2) AND ARE NOT MORE THAN ONE FLOOR; OR
 2. AN OCCUPANT SENSOR THAT SHALL TURN LIGHTING OFF
 WITHIN 30 MINUTES OF AN OCCUPANT LEAVING A SPACE; OR
 3. A SIGNAL FROM ANOTHER CONTROL OR ALARM SYSTEM THAT
 INDICATES THE AREA IS UNOCCUPIED.
  
 505.2.2.1 OCCUPANT OVERRIDE.
 WHERE AN AUTOMATIC TIME SWITCH CONTROL DEVICE IS
 INSTALLED TO COMPLY WITH SECTION 505.2.2, ITEM 1, IT
 SHALL INCORPORATE AN OVERRIDE SWITCHING DEVICE THAT:
 1. IS READILY ACCESSIBLE.
 2. IS LOCATED SO THAT A PERSON USING THE DEVICE CAN SEE
 THE LIGHTS OR THE AREA CONTROLLED BY THAT SWITCH, OR SO
 THAT THE AREA BEING LIT IS ANNUNCIATED.
 3. IS MANUALLY OPERATED BY AN OCCUPANT OR AUTOMATICALLY
 BY SENSING AN OCCUPANT.
 4.MEETS THE REQUIREMENTS OF SECTION 505.2.1.2.
  
 505.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN
 SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF
 TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT
 IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED
 DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH. LIGHTING DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN
 ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMMING AND
 THE TIME SETTING DURING LOSS OF POWER FOR A PERIOD OF
 AT LEAST 10 HOURS.
  
 A SEPARATE ELECTRICAL PERMIT APPLICATION SHALL BE
 SUBMITTED ACCOMPANIED BY SHOP DRAWINGS, EQUIPMENT
 SUBMITTALS, PRODUCT APPROVALS FOR ALL OF THE FOLLOWING:
 NETWORK, DATA/COM, FIRE ALARM, SECURITY, CCTV, AND
 AUDIO/ VIDEO WORK.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT
 /WPCONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBMI
 TTAL_FORM_04132010.PDF.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND
 LEAVE THE PREVIOUSLY REVIEWED SHEETS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  