Plan Review Notes
Plan Review Notes For Permit 14050254
Permit Number 14050254
Review Stop P
Sequence Number 2
Notes
Date Text
2014-07-01 17:27:03PLUMBING PLAN REVIEW
 PERMIT:14050254
 ADD: 109 S OLIVE AVE
 CONT: TRI-R CONSTRUCTION
 TEL: (772)336-6444
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 01/2014
 ACTION: PLUMBING PROVISO:
  
  
 1) SHEET P-1 NOTE # 3 INDICATES THE REUSE OF THE
 EXISTING GREASE INTERCEPTOR. PLEASE CONTACT WEST PALM
 BEACH FOG (FATS, OILS & GREASE) INSPECTORS TO VERIFY
 THE EXISITNG INTERCEPTOR SIZE AS WELL AS CONDITION TO
 SEE IF THE EXISITNG INTERCEPTOR CAN BE REUSED. THE
 CONCRETE TYPE VAULT INTERCEPTORS ARE TO BE LOCATED ON
 THE EXTERIOR OF THE BUILDING.
 CONTACT INFO: JOCELYN BROWN 822-2170 PUBLIC UTILITIES
 DEPARTMENT.
  
 2) IF THE EXISITNG GREASE INTERCEPTOR CAN BE REUSED
 PLEASE PROVIDE THE CALCULATIONS TO VERIFY THE GREASE
 INTERCEPTOR IS SIZED PROPERLY. FOR THE HYDROCEMICAL
 TYPE OF GREASE INTERCEPTORS THERE ARE VARIOUS METHODS
 FOR SIZING. FOR THE CONCRETE TYPE VAULT INTERCEPTORS
 SEE SIZING TABLE 1003.5.1 2010 FBC-P SIZING FORMULA FOR
 RESTAURANTS.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]