| 2014-07-01 17:27:03 | PLUMBING PLAN REVIEW |
| | PERMIT:14050254 |
| | ADD: 109 S OLIVE AVE |
| | CONT: TRI-R CONSTRUCTION |
| | TEL: (772)336-6444 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JULY 01/2014 |
| | ACTION: PLUMBING PROVISO: |
| | |
| | |
| | 1) SHEET P-1 NOTE # 3 INDICATES THE REUSE OF THE |
| | EXISTING GREASE INTERCEPTOR. PLEASE CONTACT WEST PALM |
| | BEACH FOG (FATS, OILS & GREASE) INSPECTORS TO VERIFY |
| | THE EXISITNG INTERCEPTOR SIZE AS WELL AS CONDITION TO |
| | SEE IF THE EXISITNG INTERCEPTOR CAN BE REUSED. THE |
| | CONCRETE TYPE VAULT INTERCEPTORS ARE TO BE LOCATED ON |
| | THE EXTERIOR OF THE BUILDING. |
| | CONTACT INFO: JOCELYN BROWN 822-2170 PUBLIC UTILITIES |
| | DEPARTMENT. |
| | |
| | 2) IF THE EXISITNG GREASE INTERCEPTOR CAN BE REUSED |
| | PLEASE PROVIDE THE CALCULATIONS TO VERIFY THE GREASE |
| | INTERCEPTOR IS SIZED PROPERLY. FOR THE HYDROCEMICAL |
| | TYPE OF GREASE INTERCEPTORS THERE ARE VARIOUS METHODS |
| | FOR SIZING. FOR THE CONCRETE TYPE VAULT INTERCEPTORS |
| | SEE SIZING TABLE 1003.5.1 2010 FBC-P SIZING FORMULA FOR |
| | RESTAURANTS. |
| | |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |