| 2014-05-23 16:13:32 | PLUMBING PLAN REVIEW |
| | PERMIT:14050254 |
| | ADD: 109 S OLIVE AVE |
| | CONT: TRI-R CONSTRUCTION |
| | TEL: (772)336-6444 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRIDAY MAY 23/2014 |
| | ACTION: DENIED |
| | |
| | 1) 2010 FBC-P ) 315.1 REQUIREMENTS. PUBLIC FOOD SERVICE |
| | ESTABLISHMENTS AND FOOD ESTABLISHMENTS, AS DEFINED IN |
| | CHAPTER 381 FLORIDA STATUTES, CHAPTER 500 FLORIDA |
| | STATUTES AND CHAPTER 509 FLORIDA STATUTES, SHALL COMPLY |
| | WITH THE APPLICABLE CODE REQUIREMENTS FOUND IN THE |
| | FLORIDA BUILDING CODE, BUILDING, CHAPTER 4, SPECIAL |
| | DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY. |
| | PLEASE SEE DBPR WEBSITE FOR ADDITIONAL INFO: |
| | HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/HR/LICENSING/ |
| | PLANREVIEWINDEX.HTML |
| | |
| | 2) SHEET A-0.00 & A-1.00 : THE UPCOMING COMMENT WILL OR |
| | WILL NOT BE RELEVENT DEPENDING ON HOW THIS PROJECT IS |
| | LOOKED AT. UNDER THE HEADING OF RESTAURANT THERE ARE |
| | MORE THAN ADEQUITE FIXTURES, THE 2010 FBC-PLUMBING CODE |
| | SECTION 403.5 DOES LOOK AT REQUIRED FIXTURES NOT IS |
| | PROVIDED, UNDER THE HEADING OF RESTARAUNT THE FIXTURE |
| | COUNT IS ABOVE THE CODE REQUIREMENTS. |
| | |
| | THE PROBLEM WE ARE HAVING IS UNDER A RESTAURANT YOU |
| | HAVE A COMMERCIAL KITCHEN FOR FIXING MEALS, THERE IS NO |
| | EQUIPMENT FOR THE HEATING AND PREPARING OF FOOD. THE |
| | SECOND ISSUE WITH THE CLASSIFICATION OF A RESTAURANT |
| | ,THERE IS NO TABLES AND CHAIRS THAT WOULD BE ASSOCIATED |
| | WITH A RESTAURANT. WE DO NOT SEE ANY TABLE AND CHAIRS |
| | ON THE LIFE SAFETY PLANS FOR FLOOR PLANS FOR THE FIRST |
| | OR SECOND FLOOR. |
| | |
| | IF THIS PROJECT IS REVIEWED UNDER THE NIGHTCLUB USAGE, |
| | NOT REQUIRING A FULL BLOWN KITCHEN, NOT REQUIRING TABLE |
| | AND CHAIRS THE REQUIRED 40 SQ FT/ OCC GOES TO 75 SQ FT/ |
| | OCC ALMOST DOUBLING THE REQUIRED FIXTURE COUNT, THEN |
| | WITH THE COMBINED REQUIRED WATER CLOSET COUNT FOR MENS |
| | & LADIES RESTROOMS A SEPERATE UNISEX RESTROOM WILL BE |
| | REQUIRED. OUR PROBLEM IS THE PLANS APPEAR TO BE A |
| | NIGHTCLUB SETTING AND NOT THE RESTAURANT DECLARED BY |
| | THE DESIGN PROFESSIONAL. |
| | |
| | 2A)IF CONSIDERED A NIGHTCLUB: CODE ANALYSIS UNDER THE |
| | HEADING USE & OCCUPANCY INDICATES THIS TO BE AN A2 |
| | OCCUPANCY / RESTARAUNT. THE PLUMBING FIXTURE COUNT ALSO |
| | REFLECTS |
| | THE REQUIRED FIXTURES FOR A RESTARAUNT USE. THE |
| | REQUIRED WATER CLOSET COUNT OF 2 REQUIRED WATER CLOSETS |
| | ARE PROVIDED WITH A 3RD ACCESSIBLE RESTROOM FOR EACH |
| | THE MENS AND WOMENS RESTROOMS. THE ISSUE IS THERE IS NO |
| | UNISEX RESTROOM AS REQUIRED BY 2010 FL ACC CODE 403.5. |
| | |
| | 2010 FL ACC CODE SECTION :2010 FL ACC CODE 403.1.2 |
| | FAMILY OR ASSISTED-USE TOILET AND BATH FIXTURES. |
| | FIXTURES LOCATED WITHIN FAMILY OR ASSISTED-USE TOILET |
| | AND BATHING ROOMS REQUIRED BY THE FLORIDA BUILDING |
| | CODE, ACCESSIBILITY ARE PERMITTED TO BE INCLUDED IN THE |
| | NUMBER OF REQUIRED FIXTURES FOR EITHER THE MALE OR |
| | FEMALE OCCUPANTS IN ASSEMBLY AND MERCANTILE |
| | OCCUPANCIES. THIS IS A GENERAL CODE ARTICLE THAT ALLOWS |
| | THE FAMILY OR ASSITED- USE RESTROOMS TO BE COUNTED IN |
| | EITHER OR MALE OR FEMALE FIXTURE COUNT. |
| | |
| | SECTION 403.5 IS A SPECIFIC CODE ARTILE THAT DEALS ONLY |
| | WITH ASSEMBLY & MERCANTILE OCCUPANCIES. 403.5 UNISEX |
| | TOILET AND BATHING ROOMS. IN ASSEMBLY AND MERCANTILE |
| | OCCUPANCIES, AN ACCESSIBLE UNISEX TOILET ROOM SHALL BE |
| | PROVIDED WHERE AN AGGREGATE OF SIX OR MORE MALE AND |
| | FEMALE WATER CLOSETS IS REQUIRED, AGAIN UNDER A |
| | NIGHTCLUB SETTING. |
| | WITH THE SINGLE MENS ACCESIBLE RESTROOM THE PLANS ARE |
| | MISSING THE REQUIRED UNISEX RESTROOM REQUIRED BY THE |
| | 2010 FL ACCESSIBILITY CODE UNDER THE NIGHTCLUB SETTING. |
| | |
| | 3) SHEET P-1 NOTE # 3 INDICATES THE REUSE OF THE |
| | EXISTING GREASE INTERCEPTOR. PLEASE CONTACT WEST PALM |
| | BEACH FOG (FATS, OILS & GREASE) INSPECTORS TO VERIFY |
| | THE EXISITNG INTERCEPTOR SIZE AS WELL AS CONDITION TO |
| | SEE IF THE EXISITNG INTERCEPTOR CAN BE REUSED. THE |
| | CONCRETE TYPE VAULT INTERCEPTORS ARE TO BE LOCATED ON |
| | THE EXTERIOR OF THE BUILDING. |
| | CONTACT INFO: JOCELYN BROWN 822-2170 PUBLIC UTILITIES |
| | DEPARTMENT. |
| | |
| | 4) IF THE EXISITNG GREASE INTERCEPTOR CAN BE REUSED |
| | PLEASE PROVIDE THE CALCULATIONS TO VERIFY THE GREASE |
| | INTERCEPTOR IS SIZED PROPERLY. FOR THE HYDROCEMICAL |
| | TYPE OF GREASE INTERCEPTORS THERE ARE VARIOUS METHODS |
| | FOR SIZING. FOR THE CONCRETE TYPE VAULT INTERCEPTORS |
| | SEE SIZING TABLE 1003.5.1 2010 FBC-P SIZING FORMULA FOR |
| | RESTAURANTS. |
| | |
| | 5) SHEET P-3.0 IN THE LADIES RESTROOM THE WATER CLOSETS |
| | NEED TO BE EITHER INDIVIDUALLY VENTED OR A CIRCUIT VENT |
| | AS DRAWN IT APPEARS TO BE A VET VENT SYSTEM, |
| | WET VENT SYSSTEMS ARE TO BE USED ON 1 & 2 FAMILY |
| | RESIDENCE. |
| | INFORMAL INTERPRETATION BOAF & FL DEPART COMMUNITY |
| | AFFAIRS |
| | DATE: MON APR 13 2009 |
| | REPORT: 6090 |
| | CODE: PLUMBING CODE YEAR: 2007 |
| | SECTION: 909 |
| | QUESTION: |
| | IS IT THE INTENT OF THE FLORIDA BUILDING CODE - |
| | PLUMBING SECTION 909 TO ALLOW A URINAL TO WET VENT A |
| | SINGLE COMMERCIAL |
| | WATER CLOSET OR TO DRAIN INTO THAT WATER CLOSET?S |
| | INDIVIDUAL VENT? |
| | COMMENT: |
| | ANSWER: |
| | NO. ONLY FIXTURES IN BATHROOM GROUPS AS DEFINED IN |
| | FLORIDA BUILDING CODE - PLUMBING CHAPTER 2 ARE |
| | PERMITTED TO |
| | CONNECT TO THE WET VENT. ANY ADDITIONAL FIXTURES MUST |
| | DISCHARGE DOWNSTREAM OF THE WET VENT. |
| | COMMENTARY: |
| | A URINAL IS NOT INCLUDED IN THE DEFINITION OF A |
| | BATHROOM GROUP. |
| | NOTICE: |
| | THE BUILDING OFFICIALS ASSOCIATION OF FLORIDA, IN |
| | COOPERATION WITH THE FLORIDA BUILDING COMMISSION, THE |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ICC, AND INDUSTRY AND PROFESSIONAL EXPERTS OFFER THIS |
| | INTERPRETATION OF THE FLORIDA BUILDING CODE IN THE |
| | INTEREST OF CONSISTENCY IN THEIR APPLICATION |
| | STATEWIDE. THIS INTERPRETATION IS INFORMAL, NON-BINDING |
| | AND SUBJECT TO ACCEPTANCE AND APPROVAL BY THE LOCAL |
| | BUILDING OFFICIAL. |
| | |
| | 6) THE SAME SITUATION OCCURS WITHIN THE MENS RESTROOM |
| | WITH THE WATER CLOSETS, THEY SHOULD BE EITHER |
| | INDIVIDUALLY VENTED. 2010 FBC- P 907.1. |
| | |
| | 7) THE PLANS DO NOT SHOW ANY VENTING THA TIES BACK INTO |
| | THE BUILDING TO THE OUTDOORS. 2010 FBC-P 903.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |