| 2014-05-22 17:19:42 | FAILED FIRST ELECTRICAL REVIEW AS FOLLOWS: |
| | |
| | 1. NEC 110.26(D) REQUIRES THAT THEREE BE PROPER |
| | ILLUMINATION IN THE AREA ABOUT THE ELECTRICAL PANELS, |
| | THIS BEING BOTH PANEL "B" AND THE FACP |
| | 2. NEC 600.5 REQUIRES A DEDICATED SIGN OUTLET BY EACH |
| | ENTRY DOOR. |
| | 3. MISSING EMERGENCY LIGHTING IN THE BATHROOMS AS PER |
| | FBC-B1006.2.2 |
| | 4. STAIR 013 IS MISSING THE EMERGENCY LIGHT ON THE |
| | FIRST FLR. |
| | 5. ELECTRIC ROOM IS MISSING AN EMERGENCY LIGHT |
| | 6. AS PER THE SUBMITTED PLANS, THER IS NOT SUFFICIENT |
| | LIGHTING IN THE STAIRWAYS |
| | 7. THOUGH A SEPARATE PLAN & SET OF SHOP DRAWINGS IS |
| | REQUIRED FOR THE FIRE ALARM, THE SUBMITTED PLANS SHOW |
| | THE FACP IN THE 011 STAIRWELL, THEREFORE A DEDICATED 20 |
| | AMP CIRCUIT FOR THE FIRE ALARM SHALL BE PROVIDED. |
| | 8. VERIFY THE FEEDER FOR CU1; TAKING INTO ACCOUNT ANY |
| | APPLICABLE VOLTAGE DROP AND EXPOSURE DERATIONS. |
| | 9 IF PANEL RP1` IS A SINGLE PHASE 120/240, WHY DOES THE |
| | FEEDER SHOW FOUR 4/0 CONDUCTORS PLUS THE GRD. |
| | |
| | THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL |
| | PLANS EXAMINER |
| | YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE |
| | FOLLOWING LINK: |
| | |
| | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT |
| | US.ASPX |
| | |
| | ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS |
| | EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER, |
| | AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB |
| | ABOVE THE SECOND PERMIT INFORMATION). |
| | AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR |
| | COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER |
| | PERMIT CONDITIONS. |
| | FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME. |
| | I CAN BE REACHED AT 561-805-6718 OR |
| | [email protected] |
| | |