2014-05-23 13:28:08BUILDING PLAN REVIEW
 PERMIT:14050254
 ADD: 109 S OLIVE AVE
 CONT: TRI-R CONSTRUCTION
 TEL: (772)336-6444
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRIDAY MAY 23/2014
 ACTION: DENIED
  
 1) THE LIFE SAFETY SHEET A-0.00
 1A) CODE ANALYSIS INDICATES THIS BUILDING TO A TYPE V -
 ASSUMED, PLEASE PROVIDE THE HEIGHT OF THE BUILDING,
 THIS SPACE BEING TWO FLOORS AND HOW MANY ADDITIONAL
 FLOORS ONE OR TWO. PLEASE REVIEW TABLE 503, IT APPEARS
 IF THIS IS A 3 STORY BUILDING EITHER A III-B OR V-A OR
 IF A 4 STORY A III-A. TAKING INTO ACCOUNT A STORY
 INCREASE FOR FIRE SPRINKLERS.
  
 1B) SHEET A101 NOW HAS A NEW 1 HOUR CHASE, IT APPEARS
 TO BE IN THE STAIRWELL TO THE OTHER TENANTS. PLEASE
 PROVIDE ON THE PLANS THE UL LISTING U415 SYSTEM A SINCE
 THE INSPECTORS WILL NEED THE COMPONENTS OF THE ASSEMBLY
 TO BE ABLE TO ACCOMPLISH THEIR INSPECTIONS. FBC-B 708.4
 AND 708.5 CONTINUITY. 708.8 PENETRATIONS.
  
 1C) SHEET A-1.01 DOES HAVE A WALL TAG S2 WALL TYPE
 IDENTIFYING FIRE RATED WALLS. NONE OF THE TENANT
 SEPERATION WALLS ARE IDENTIFIED WITH THIS WALL TAG. FBC
 709.1.6.
  
 1D )2ND REQUEST. ONLY NEW SHEET IS P3 NOT FOUND ON THIS
 SHEET, CONTRACTOR FAILED TO COLATE PLANS INTO ONE SET
 OF PLANS. THE TENANT SEPARATION WALL WITHIN THE LADIES
 RESTROOM WILL HAVE VENTING THAT WILL PETRUDE OUT OF THE
 FIRE RATED WALL, WHAT TYPE OF FIRE STOPPING DESIGN IS
 TO BE SUBMITTED FOR THROUGH PENETRATIONS, 2010 FBC-B
 713.4.1.1.
  
 1E) COMPLIED.
  
 1F) SEMI COMPLIED MISSING THE NEW A4.01 AS INDICATED IN
 RESPONSE.
 2) SHEET A-1.01:
 2A-J)COMPLIED.
  
 3) 2ND REQUEST, SHEET M-4 INDICATES THE USE OF WALL
 LOUVERS AND PRE-MANUFACTURED A/C STANDS, PLEAS PROVIDE
 COMPLIANCE WITH : FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(C) WALL LOUVERS
 (G) PRE-ENGINEERED A/C STANDS
  
 4) 2ND REQUEST, 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) 2ND REQUEST, PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 PLEASE PROVIDE THE WIND DESIGN CRITERIA, PRESSURES FOR
 THE WALL LOUVER & ROOFTOP A/C STAND.
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 6) SHEET M-1 NOTE # 3 INDICATES TO RUN THE REFRIGARANT
 LINES THROUGH CHASE TO ROOF. THERE IS NO DETAILS WITHIN
 THE PLANS INDICATING HOW THIS CHASE WILL BE BUILT,AND
 ACHIEVE FIRE RATINGS IN COMPLIANCE WITH 2010 FBC-B
 713.4.1 FIRE-RESISTANCE-RATED ASSEMBLIES.
  
 6A) COMPLIED SEE SHEET M-5.
 PENETRATIONS OF THE FIRE-RESISTANCE-RATED FLOOR,
 FLOOR/CEILING ASSEMBLY OR THE CEILING MEMBRANE OF A
 ROOF/CEILING ASSEMBLY SHALL COMPLY WITH SECTIONS
 713.4.1.1 THROUGH 713.4.1.4.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER