| 2014-05-23 13:28:08 | BUILDING PLAN REVIEW |
| | PERMIT:14050254 |
| | ADD: 109 S OLIVE AVE |
| | CONT: TRI-R CONSTRUCTION |
| | TEL: (772)336-6444 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRIDAY MAY 23/2014 |
| | ACTION: DENIED |
| | |
| | 1) THE LIFE SAFETY SHEET A-0.00 |
| | 1A) CODE ANALYSIS INDICATES THIS BUILDING TO A TYPE V - |
| | ASSUMED, PLEASE PROVIDE THE HEIGHT OF THE BUILDING, |
| | THIS SPACE BEING TWO FLOORS AND HOW MANY ADDITIONAL |
| | FLOORS ONE OR TWO. PLEASE REVIEW TABLE 503, IT APPEARS |
| | IF THIS IS A 3 STORY BUILDING EITHER A III-B OR V-A OR |
| | IF A 4 STORY A III-A. TAKING INTO ACCOUNT A STORY |
| | INCREASE FOR FIRE SPRINKLERS. |
| | |
| | 1B) SHEET A101 NOW HAS A NEW 1 HOUR CHASE, IT APPEARS |
| | TO BE IN THE STAIRWELL TO THE OTHER TENANTS. PLEASE |
| | PROVIDE ON THE PLANS THE UL LISTING U415 SYSTEM A SINCE |
| | THE INSPECTORS WILL NEED THE COMPONENTS OF THE ASSEMBLY |
| | TO BE ABLE TO ACCOMPLISH THEIR INSPECTIONS. FBC-B 708.4 |
| | AND 708.5 CONTINUITY. 708.8 PENETRATIONS. |
| | |
| | 1C) SHEET A-1.01 DOES HAVE A WALL TAG S2 WALL TYPE |
| | IDENTIFYING FIRE RATED WALLS. NONE OF THE TENANT |
| | SEPERATION WALLS ARE IDENTIFIED WITH THIS WALL TAG. FBC |
| | 709.1.6. |
| | |
| | 1D )2ND REQUEST. ONLY NEW SHEET IS P3 NOT FOUND ON THIS |
| | SHEET, CONTRACTOR FAILED TO COLATE PLANS INTO ONE SET |
| | OF PLANS. THE TENANT SEPARATION WALL WITHIN THE LADIES |
| | RESTROOM WILL HAVE VENTING THAT WILL PETRUDE OUT OF THE |
| | FIRE RATED WALL, WHAT TYPE OF FIRE STOPPING DESIGN IS |
| | TO BE SUBMITTED FOR THROUGH PENETRATIONS, 2010 FBC-B |
| | 713.4.1.1. |
| | |
| | 1E) COMPLIED. |
| | |
| | 1F) SEMI COMPLIED MISSING THE NEW A4.01 AS INDICATED IN |
| | RESPONSE. |
| | 2) SHEET A-1.01: |
| | 2A-J)COMPLIED. |
| | |
| | 3) 2ND REQUEST, SHEET M-4 INDICATES THE USE OF WALL |
| | LOUVERS AND PRE-MANUFACTURED A/C STANDS, PLEAS PROVIDE |
| | COMPLIANCE WITH : FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(C) WALL LOUVERS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 4) 2ND REQUEST, 2010 FBC 107.3.4.1 PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 5) 2ND REQUEST, PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING |
| | FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE |
| | DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | |
| | PLEASE PROVIDE THE WIND DESIGN CRITERIA, PRESSURES FOR |
| | THE WALL LOUVER & ROOFTOP A/C STAND. |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 5.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |
| | 6) SHEET M-1 NOTE # 3 INDICATES TO RUN THE REFRIGARANT |
| | LINES THROUGH CHASE TO ROOF. THERE IS NO DETAILS WITHIN |
| | THE PLANS INDICATING HOW THIS CHASE WILL BE BUILT,AND |
| | ACHIEVE FIRE RATINGS IN COMPLIANCE WITH 2010 FBC-B |
| | 713.4.1 FIRE-RESISTANCE-RATED ASSEMBLIES. |
| | |
| | 6A) COMPLIED SEE SHEET M-5. |
| | PENETRATIONS OF THE FIRE-RESISTANCE-RATED FLOOR, |
| | FLOOR/CEILING ASSEMBLY OR THE CEILING MEMBRANE OF A |
| | ROOF/CEILING ASSEMBLY SHALL COMPLY WITH SECTIONS |
| | 713.4.1.1 THROUGH 713.4.1.4. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |