| 2014-05-28 07:27:12 | BUILDING PLAN REVIEW |
| | REVISION: 14050223 |
| | PERMIT: 14021098 |
| | ADD: 915 S DIXIE HWY |
| | CONT: DEALERSHIP SOLUTIONS LLC |
| | TEL: (727)465-4413 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. MAY 28/ 2014 |
| | ACTION: PROVISO |
| | |
| | SHEET A201 NOTE # 1 INDICATES THE USE OF AUCOBOND |
| | PANELS, ACM WINGS FACIA ELEMENT, PLEASE PROVIDE |
| | COMPLIANCE WITH 2010 FBC-B 1407.3 ARCHITECTURAL TRIM |
| | AND EMBELLISHMENTS. |
| | MCM USED AS ARCHITECTURAL TRIM OR EMBELLISHMENTS SHALL |
| | COMPLY WITH SECTIONS 1407.7 THROUGH 1407.14. |
| | |
| | 1407.4 STRUCTURAL DESIGN. |
| | MCM SYSTEMS SHALL BE DESIGNED AND CONSTRUCTED TO RESIST |
| | WIND LOADS AS REQUIRED BY CHAPTER 16 FOR COMPONENTS AND |
| | CLADDING. |
| | |
| | 1407.5 APPROVAL. |
| | RESULTS OF APPROVED TESTS OR AN ENGINEERING ANALYSIS |
| | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO VERIFY |
| | COMPLIANCE WITH THE REQUIREMENTS OF CHAPTER 16 FOR WIND |
| | LOADS. |
| | |
| | 1407.6 WEATHER RESISTANCE. |
| | MCM SYSTEMS SHALL COMPLY WITH SECTION 1403 AND SHALL BE |
| | DESIGNED AND CONSTRUCTED TO RESIST WIND AND RAIN IN |
| | ACCORDANCE WITH THIS SECTION AND THE MANUFACTURER?S |
| | INSTALLATION INSTRUCTIONS. |
| | |
| | 1407.7 DURABILITY. |
| | MCM SYSTEMS SHALL BE CONSTRUCTED OF APPROVED MATERIALS |
| | THAT MAINTAIN THE PERFORMANCE CHARACTERISTICS REQUIRED |
| | IN SECTION 1407 FOR THE DURATION OF USE. |
| | |
| | 1407.8 FIRE-RESISTANCE RATING. |
| | WHERE MCM SYSTEMS ARE USED ON EXTERIOR WALLS REQUIRED |
| | TO HAVE A FIRE-RESISTANCE RATING IN ACCORDANCE WITH |
| | SECTION 705, EVIDENCE SHALL BE SUBMITTED TO THE |
| | BUILDING OFFICIAL THAT THE REQUIRED FIRE-RESISTANCE |
| | RATING IS MAINTAINED. |
| | |
| | EXCEPTION: MCM SYSTEMS NOT CONTAINING FOAM PLASTIC |
| | INSULATION, WHICH ARE INSTALLED ON THE OUTER SURFACE OF |
| | A FIRE-RESISTANCE-RATED EXTERIOR WALL IN A MANNER SUCH |
| | THAT THE ATTACHMENTS DO NOT PENETRATE THROUGH THE |
| | ENTIRE EXTERIOR WALL ASSEMBLY, SHALL NOT BE REQUIRED TO |
| | COMPLY WITH THIS SECTION. |
| | |
| | 1407.9 SURFACE-BURNING CHARACTERISTICS. |
| | UNLESS OTHERWISE SPECIFIED, MCM SHALL HAVE A FLAME |
| | SPREAD INDEX OF 75 OR LESS AND A SMOKE-DEVELOPED INDEX |
| | OF 450 OR LESS WHEN TESTED IN THE MAXIMUM THICKNESS |
| | INTENDED FOR USE IN ACCORDANCE WITH ASTM E 84 OR UL |
| | 723. |
| | |
| | 1407.10 TYPE I, II, III AND IV CONSTRUCTION. |
| | WHERE INSTALLED ON BUILDINGS OF TYPE I, II, III AND IV |
| | CONSTRUCTION, MCM SYSTEMS SHALL COMPLY WITH SECTIONS |
| | 1407.10.1 THROUGH 1407.10.4, OR SECTION 1407.11. |
| | |
| | 1407.10.1 SURFACE-BURNING CHARACTERISTICS. |
| | MCM SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 |
| | AND A SMOKE DEVELOPED INDEX OF NOT MORE THAN 450 WHEN |
| | TESTED AS AN ASSEMBLY IN THE MAXIMUM THICKNESS INTENDED |
| | FOR USE IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 1407.10.2 THERMAL BARRIERS. |
| | MCM SHALL BE SEPARATED FROM THE INTERIOR OF A BUILDING |
| | BY AN APPROVED THERMAL BARRIER CONSISTING OF 1/2-INCH |
| | (12.7 MM) GYPSUM WALLBOARD OR EQUIVALENT THERMAL |
| | BARRIER MATERIAL THAT WILL LIMIT THE AVERAGE |
| | TEMPERATURE RISE OF THE UNEXPOSED SURFACE TO NOT MORE |
| | THAN 250?F (121?C) AFTER 15 MINUTES OF FIRE EXPOSURE IN |
| | ACCORDANCE WITH THE STANDARD TIME-TEMPERATURE CURVE OF |
| | ASTM E 119 OR UL 263. THE THERMAL BARRIER SHALL BE |
| | INSTALLED IN SUCH A MANNER THAT IT WILL REMAIN IN PLACE |
| | FOR NOT LESS THAN 15 MINUTES BASED ON A TEST CONDUCTED |
| | IN ACCORDANCE WITH UL 1715. |
| | |
| | 1407.10.3 THERMAL BARRIER NOT REQUIRED. |
| | THE THERMAL BARRIER SPECIFIED FOR MCM IN SECTION |
| | 1407.10.2 IS NOT REQUIRED WHERE: |
| | |
| | 1. THE MCM SYSTEM IS SPECIFICALLY APPROVED BASED ON |
| | TESTS CONDUCTED IN ACCORDANCE WITH UL 1040 OR UL 1715. |
| | SUCH TESTING SHALL BE PERFORMED WITH THE MCM IN THE |
| | MAXIMUM THICKNESS INTENDED FOR USE. THE MCM SYSTEM |
| | SHALL INCLUDE SEAMS, JOINTS AND OTHER TYPICAL DETAILS |
| | USED IN THE INSTALLATION AND SHALL BE TESTED IN THE |
| | MANNER INTENDED FOR USE. |
| | |
| | 2. THE MCM IS USED AS ELEMENTS OF BALCONIES AND SIMILAR |
| | PROJECTIONS, ARCHITECTURAL TRIM OR EMBELLISHMENTS. |
| | |
| | 1407.10.4 FULL-SCALE TESTS. |
| | THE MCM SYSTEM SHALL BE TESTED IN ACCORDANCE WITH, AND |
| | COMPLY WITH, THE ACCEPTANCE CRITERIA OF NFPA 285. SUCH |
| | TESTING SHALL BE PERFORMED ON THE MCM SYSTEM WITH THE |
| | MCM IN THE MAXIMUM THICKNESS INTENDED FOR USE. |
| | |
| | 1407.11 ALTERNATE CONDITIONS. |
| | MCM AND MCM SYSTEMS SHALL NOT BE REQUIRED TO COMPLY |
| | WITH SECTIONS 1407.10.1 THROUGH 1407.10.4 PROVIDED SUCH |
| | SYSTEMS COMPLY WITH SECTION 1407.11.1 OR 1407.11.2. |
| | |
| | 1407.11.1 INSTALLATIONS UP TO 40 FEET IN HEIGHT. |
| | MCM SHALL NOT BE INSTALLED MORE THAN 40 FEET (12 190 |
| | MM) IN HEIGHT ABOVE GRADE WHERE INSTALLED IN ACCORDANCE |
| | WITH SECTIONS 1407.11.1.1 AND 1407.11.1.2. |
| | |
| | 1407.11.1.1 FIRE SEPARATION DISTANCE OF 5 FEET OR LESS. |
| | WHERE THE FIRE SEPARATION DISTANCE IS 5 FEET (1524 MM) |
| | OR LESS, THE AREA OF MCM SHALL NOT EXCEED 10 PERCENT OF |
| | THE EXTERIOR WALL SURFACE. |
| | |
| | 1407.11.1.2 FIRE SEPARATION DISTANCE GREATER THAN 5 |
| | FEET. |
| | WHERE THE FIRE SEPARATION DISTANCE IS GREATER THAN 5 |
| | FEET (1524 MM), THERE SHALL BE NO LIMIT ON THE AREA OF |
| | EXTERIOR WALL SURFACE COVERAGE USING MCM. |
| | |
| | 1407.11.2 INSTALLATIONS UP TO 50 FEET IN HEIGHT. |
| | MCM SHALL NOT BE INSTALLED MORE THAN 50 FEET (15 240 |
| | MM) IN HEIGHT ABOVE GRADE WHERE INSTALLED IN ACCORDANCE |
| | WITH SECTIONS 1407.11.2.1 AND 1407.11.2.2. |
| | |
| | 1407.11.2.1 SELF-IGNITION TEMPERATURE. |
| | MCM SHALL HAVE A SELF-IGNITION TEMPERATURE OF 650?F |
| | (343?C) OR GREATER WHEN TESTED IN ACCORDANCE WITH ASTM |
| | D 1929. |
| | |
| | 1407.11.2.2 LIMITATIONS. |
| | SECTIONS OF MCM SHALL NOT EXCEED 300 SQUARE FEET (27.9 |
| | M2) IN AREA AND SHALL BE SEPARATED BY A MINIMUM OF 4 |
| | FEET (1219 MM) VERTICALLY. |
| | |
| | 1407.12 TYPE V CONSTRUCTION. |
| | MCM SHALL BE PERMITTED TO BE INSTALLED ON BUILDINGS OF |
| | TYPE V CONSTRUCTION. |
| | |
| | 1407.13 FOAM PLASTIC INSULATION. |
| | MCM SYSTEMS CONTAINING FOAM PLASTIC INSULATION SHALL |
| | ALSO COMPLY WITH THE REQUIREMENTS OF SECTION 2603. |
| | |
| | 1407.14 LABELING. |
| | MCM SHALL BE LABELED IN ACCORDANCE WITH SECTION 1703.5. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |