| Plan Review Notes For Permit 14050183 |
| Permit Number |
14050183 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-08-12 11:35:08 | DATE: 8/6/2014 | | | PROJECT: THE EXIT FACILITY | | | PERMIT#: 14050183 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: PROVISO | | | | | | 1) FBC-ENERGY | | | 505.2 LIGHTING CONTROLS (MANDATORY). | | | LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS | | | REQUIRED IN SECTIONS 505.2.1, 505.2.2, 505.2.3 AND | | | 505.2.4. | | | AUTOMATIC LIGHTING SHUTOFF IS REQUIRED IN BUILDINGS | | | LARGER THAN 5,000 SQUARE FEET AND SHALL BE EQUIPPED | | | WITH AN AUTOMATIC CONTROL DEVICE TO SHUT OFF LIGHTING | | | IN THOSE AREAS. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR | | | SIGNS, SECURITY, NETWORK, CCTV, AUDIO/VIDEO . | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT | | | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM | | | ITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARATIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|