Plan Review Notes
Plan Review Notes For Permit 14050183
Permit Number 14050183
Review Stop P
Sequence Number 1
Notes
Date Text
2014-05-27 08:51:31PLUMBING PLAN REVIEW
 PERMIT: 14050183
 ADD: 2800 S DIXIE HWY
 CONT: VERITAS DEVELOPMENT
 TEL: (561)346-4330
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUESDAY MAY 27/2014
 ACTION: DENIED
  
 1) PLEASE REVIEW THE 2010 FL ACCESSIBILITY CODE THERE
 IS ONLY ONE ACCESSIBLE RESTROOM AND NO FEES HAVE BEEN
 PUT FORTH FOR ACCESSBLE UPGRADES AS IN DISPROPORTIONATE
 COST 202.4.1. THERE SEAMS TO BE A ACCESSIBLE ENTRANCE
 AND A ACCESSIBLE ROUTETHE THIRD AREA TO PROVIDE
 ACCESSIBLE UPGRADES IS RESTROOMS (III) AT LEAST ONE
 ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS. THERE IS ONE ACCESSIBLE RESTROOM
 THAT IS CODE COMPLIANT UNDER THE 2007 FBC. THIS RESTROM
 DOES NOT NEED TO BE TOUCHED, IT IS THE OTHER RESTROOM.
 20% OF THE CONTRACT VALUE OR $12,000 NEEDS TO BE SPENT
 IN ACCESSIBLE UPGRADES, RESTROOMS, THEN A HIGH LOW
 DRINKING FOUNTAIN IF THE $12,000 DOLLARS HAS NOT BEEN
 USED UP INTHE RESTROOM REMODEL.
  
 2) THE PLANS ALSO SHOW A NEW MOP/ SERVICE SINK AND NO
 ISOMETRIC OF THE SANITARY, 2010 FBC-PLUMBING 907.1.
 WILL REQUIRE ITS OWN VENT IT CAN NOT BE ON A WET VENT
 SYSTEM, THESE ARE ONLY FOR SINGLE FAMILY RESIDENCES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]