| 2014-05-27 08:51:31 | PLUMBING PLAN REVIEW |
| | PERMIT: 14050183 |
| | ADD: 2800 S DIXIE HWY |
| | CONT: VERITAS DEVELOPMENT |
| | TEL: (561)346-4330 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUESDAY MAY 27/2014 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE REVIEW THE 2010 FL ACCESSIBILITY CODE THERE |
| | IS ONLY ONE ACCESSIBLE RESTROOM AND NO FEES HAVE BEEN |
| | PUT FORTH FOR ACCESSBLE UPGRADES AS IN DISPROPORTIONATE |
| | COST 202.4.1. THERE SEAMS TO BE A ACCESSIBLE ENTRANCE |
| | AND A ACCESSIBLE ROUTETHE THIRD AREA TO PROVIDE |
| | ACCESSIBLE UPGRADES IS RESTROOMS (III) AT LEAST ONE |
| | ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| | RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| | DRINKING FOUNTAINS. THERE IS ONE ACCESSIBLE RESTROOM |
| | THAT IS CODE COMPLIANT UNDER THE 2007 FBC. THIS RESTROM |
| | DOES NOT NEED TO BE TOUCHED, IT IS THE OTHER RESTROOM. |
| | 20% OF THE CONTRACT VALUE OR $12,000 NEEDS TO BE SPENT |
| | IN ACCESSIBLE UPGRADES, RESTROOMS, THEN A HIGH LOW |
| | DRINKING FOUNTAIN IF THE $12,000 DOLLARS HAS NOT BEEN |
| | USED UP INTHE RESTROOM REMODEL. |
| | |
| | 2) THE PLANS ALSO SHOW A NEW MOP/ SERVICE SINK AND NO |
| | ISOMETRIC OF THE SANITARY, 2010 FBC-PLUMBING 907.1. |
| | WILL REQUIRE ITS OWN VENT IT CAN NOT BE ON A WET VENT |
| | SYSTEM, THESE ARE ONLY FOR SINGLE FAMILY RESIDENCES. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |