Plan Review Notes
Plan Review Notes For Permit 14050183
Permit Number 14050183
Review Stop M
Sequence Number 1
Notes
Date Text
2014-05-27 13:17:42PLAN DENIED
 1) PROVIDE FRESH AIR CALCULATIONS PER TABLE 401.3
 2010 FBC (M)
 2) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS
 2010 FLORIDA ENERGY CODE.
 3) PROVIDE ENERGY CALCULATIONS PER SECTION 503.2.1
 CALCULATION OF HEATING AND COOLING 2010 FLORIDA ENERGY
 CODE.
 4) PROVIDE A DETAIL FROM THE ENGINEER ON UNIT TIEDOWN
 TO ROOF.
 PER SECTION 301.12 WIND RESISTANCE FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER