| 2014-05-27 13:17:42 | PLAN DENIED | | | 1) PROVIDE FRESH AIR CALCULATIONS PER TABLE 401.3 | | | 2010 FBC (M) | | | 2) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS | | | 2010 FLORIDA ENERGY CODE. | | | 3) PROVIDE ENERGY CALCULATIONS PER SECTION 503.2.1 | | | CALCULATION OF HEATING AND COOLING 2010 FLORIDA ENERGY | | | CODE. | | | 4) PROVIDE A DETAIL FROM THE ENGINEER ON UNIT TIEDOWN | | | TO ROOF. | | | PER SECTION 301.12 WIND RESISTANCE FBC (M) | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|