Plan Review Notes
Plan Review Notes For Permit 14050183
Permit Number 14050183
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-05-09 12:46:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENT:
  
 SHEET A-1; THE FIRE RATING OF THE SEPARATION WALL OF
 UNIT #3 SHALL BE INDICATED ON THE PLAN. ANY
 RE-CONSTRUCTION ON THAT WALL SHALL NOT BE LESS THAN
 EXISTING AND INDICATED AND OUTLINED ON THE PLAN;SHEET
 A-3.
  
 SHEET A/C; THE HEIGHT FROM THE FLOOR TO THE BOTTOM OF
 THE A/C DUCT WORK SHALL BE INDICATED AND WITHIN THE
 REQUIREMENTS OF THE CODE FOR EXIT ROUTES.