Plan Review Notes
Plan Review Notes For Permit 14050183
Permit Number 14050183
Review Stop E
Sequence Number 1
Notes
Date Text
2014-06-04 14:05:14ADDRESS: 2800 S. DIXIE HIGHWAY WPB
 PERMIT#:14050183
 1ST ELECTRICAL REVIEW
 ACTION: DENIED.
 CODE: 2008 NEC AND 2010 FBC
  
 DEFICIENCIES:
  
 1) A BUILDING OR OTHER STRUCTURE SERVED SHALL BE
 SUPPLIED BY ONE SERVICE UNLESS PERMITTED IN 230.2(A)
 THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2
 ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND
 LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED
 TOGETHER AT THEIR SUPPLY END BUT NOT CONNECTED TOGETHER
 AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING
 ONE SERVICE. NEC 230.2 PLEASE MAKE THE NECESSARY
 CORRECTIONS TO THIS CONDITION AND RE-SUBMIT.
  
 2) PROVIDE SAFETY LABELING FOR FLASH PROTECTION AND FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.22, 110.16, 110.22
  
 3) LISTED SINGLE AND MULTIPLE STATION SMOKE ALARMS
 COMPLYING WITH UL 217 SHALL BE INSTALLED IN ACCORDANCE
 WITH SECTIONS 907.2.11.1 THROUGH 907.2.11.4 AND NFPA
 72.
  
 4) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY
 AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS
 THAT SERVING THE NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES. NEC 701.11(G)
  
 5) ILLUMINATION OF MEANS OF EGRESS SHALL BE PROVIDED IN
 ACCORDANCE WITH THIS SECTION FOR EVERY BUILDING AND
 STRUCTURE. FOR THE PURPOSE OF THIS REQUIRMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCELATORS, WALKWAYS AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY. ADDITIONAL
 EMERGENCY BATTERY BACKED LIGHTING IS REQUIRED FOR
 ADAQUATE ILLUMINATION OF THE EGRESS PATH. FBC 1006.1.1
  
 6) LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED
 IN SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE
 OF TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT
 DAYLIGHT IS AVAILABLE OR WHEN THE LIGHTING IS NOT
 REQUIRED DURING NIGHTTIME HOURS. LIGHTING NOT
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS.
  
 7) FOR SHOW-WINDOW LIGHTING, A LOAD OF NOT LESS THAN
 200 VOLT-AMPS PER LINEAL FT. SHALL BE INCLUDED FOR A
 SHOW WINDOW MEASURED HORIZONTALLY ALONG ITS BASE. NEC
 220.43(A)
  
 8) FOR TRACK LIGHTING IN OTHER THAN DWELLING UNITS AN
 ADDITIONAL LOAD OF 150 VOLT-AMPS PER LINEAL FT. SHALL
 BE INCLUDED FOR EVERY 2 LINEAL FT. OF TRACK LIGHTING OR
 FRACTION THEREOF. WHERE MULTI-CIRCUIT TRACK IS
 INSTALLED THE LOAD SHALL BE DISTRIBUTED EQUALLY AMONG
 THE TRACK CIRCUITS.
  
 9) ALL COMPONENTS AND CABLES SHALL BE UL LISTED AND
 LABELED FOR USE IN THE MANNER INSTALLED. NEC 110.3
  
 10) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR
 SIGNS, SECURITY, NETWORK, CCTV, AUDIO/VIDEO AND FOR THE
 INSTALLATION AND TERMINATION OF THE OUTDOOR MENU
 BOARDS, CANOPY, AND PRE-SALE BOARD.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421.
 561-805-6717 OR [email protected]