| 2014-07-10 09:03:32 | DATE: 7/9/2014 |
| | PROJECT: WALDMAN APT. |
| | PERMIT#: 14050167 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) IN KITCHENS, PANTRIES, BREAKFAST ROOMS, DINING |
| | ROOMS, AND SIMILAR AREAS OF DWELLING UNITS, RECEPTACLE |
| | OUTLETS FOR COUNTERTOP SPACES SHALL BE INSTALLED IN |
| | ACCORDANCE WITH NEC 210.52(C)(1) THROUGH (C)(5). THE |
| | PLANS DO NOT SHOW THE LOCATIONS OF ANY RECEPTACLE |
| | OUTLETS REVISE PLANS TO TO SHOW LOCATIONS OF ALL NEW |
| | OUTLETS INCLUDING ANY ADDITIONAL OUTLETS REQUIRED FOR |
| | COMPLIANCE IN ACCORDANCE WITH NEC 210.52(C)(1) THROUGH |
| | (C)(5). |
| | |
| | 2) RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT |
| | ALONG THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A |
| | RECEPTACLE OUTLET. NEC 210.52 (A)(2).THE PLANS DO NOT |
| | SHOW THE LOCATIONS OF ANY RECEPTACLE OUTLETS EXCEPT FOR |
| | SOME REQUIRED FOR NEW MOTORIZED BLINDS.. REVISE PLANS |
| | TO TO SHOW LOCATIONS OF ALL NEW OUTLETS INCLUDING ANY |
| | ADDITIONAL OUTLETS REQUIRED FOR COMPLIANCE IN |
| | ACCORDANCE WITH NEC 210.52 (A)(2) |
| | |
| | 3) PROVIDE PRODUCT APPROVALS AND INSTALLATION DETAILS |
| | FOR MOTORIZED BLINDS. LISTING AND LABELING REQUIRED BY |
| | AN APPROVED TESTING LAB. IN JUDGING EQUIPMENT, |
| | CONSIDERATION SUCH AS THE FOLLOWING SHALL BE EVALUATED: |
| | SUITABILITY OF EQUIPMENT MAY BE EVIDENCED BY LISTING OR |
| | LABELING. SUITABILITY FOR INSTALLATION AND USE IN |
| | CONFORMITY WITH THE PROVISIONS OF THIS CODE. NEC |
| | 110.3(A)(1 THRU 8) LISTED OR LABELED EQUIPMENT SHALL BE |
| | INSTALLED AND USED IN ACCORDANCE WITH ANY INSTRUCTIONS |
| | INCLUDED IN THE LISTING AND LABELING. NEC 110.3(B) |
| | |
| | 4) LUMINAIRES IN CLOTHES CLOSETS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH THE PROVISIONS OF NEC 410.16(A) AND |
| | (B). REVISE PLANS TO INDICATE COMPLIANCE. |
| | |
| | 5) METAL FRAMING MEMBERS SHALL BE BONDED TO THE |
| | EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY |
| | ENERGIZE THE FRAMING AND BE SIZED IN ACCORDANCE WITH |
| | THE NEC TABLE 250.122. FOR THE PURPOSE OF THIS SECTION, |
| | A GROUNDED METAL OUTLET BOX ATTACHED TO THE FRAMING |
| | SHALL BE PERMITTED. FBC CHAPTER 27 SECTION 2704. REVISE |
| | PLANS TO INDICATE COMPLIANCE. |
| | |
| | 6) ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP GFI |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HEATING, |
| | AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND |
| | WITHIN 25FT OF THE HEATING, AIR-CONDITIONING, AND |
| | REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET SHALL |
| | NOT BE CONNECTED TO THE LOAD SIDE OF THE EQUIPMENT |
| | DISCONNECTING MEANS. NEC 210.63 SEE ALSO 210.8(A)(3), |
| | AND 406.8(B)(1). REVISE PLANS TO INDICATE COMPLIANCE. |
| | |
| | 7) INDICATE DISCONNECTS WHERE REQUIRED AT A/C EQUIPMENT |
| | ETC.. NEC 440.14. REVISE PLANS TO INDICATE COMPLIANCE. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |