| 2014-05-28 06:21:56 | PLUMBING PLAN REVIEW |
| | PERMIT: 14050167 |
| | ADD: 400 N FLAGLER DR # PH-D2 |
| | CONT: MARYJULI CONSTRUCTION |
| | TEL: (561)386-6032 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. MAY 27/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) THERE HAVE BEEN NO PLUMBING SHEETS PROVIDED, THE |
| | GUEST BATH # 2 PLEASE SHOW THE LOCATION OF THE VENT FOR |
| | THE NEWLY PLACED VANITY, DISTANCE FROM TRAP TO VENT, |
| | 2010 FBC-P TABLE 906.1. |
| | |
| | 2) IN THE MASTER BATH THE PLANS INDICATE THE ROTATING |
| | OF THE WATERCLOSET, HOW WILL THE SANITARY PIPE BE MOVED |
| | IN THE FLOOR, HOW WILL THE FIRE RATING OF THE FLOOR BE |
| | PRESERVED. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 2010 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. 2010 FBC-P 307.3 |
| | PENETRATIONS OF FLOOR/CEILING ASSEMBLIES AND |
| | FIRE-RESISTANCE-RATED ASSEMBLIES. PENETRATIONS OF |
| | FLOOR/CEILING ASSEMBLIES AND ASSEMBLIES REQUIRED TO |
| | HAVE A FIRE-RESISTANCE RATING SHALL BE PROTECTED IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3) PLEASE PROVIDE THE VENT LOCATION OF THE KITCHEN SINK |
| | AND THE DITANCE FROM THE TRAP 2010 FBC-P TABLE 906.1. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |