| Plan Review Notes For Permit 14050164 |
| Permit Number |
14050164 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-05-09 11:37:03 | 2010 FBC / 2008 NEC | | | | | | DENIED BY ELECTRICAL | | | | | | 1) SHOW THE LOCATION OF THE EXISTING METER AND CIRCUIT | | | BREAKER PANEL. CITY AMENDMENTS 107.2.1 AND NEC | | | | | | 2) SUBMIT LOAD CALCULATIONS AND A PANEL SCHEDULE. NEC | | | 220.40 AND NEC 408.4 | | | | | | 3) SHOW COMPLIANCE WITH NEC 210.11 (C) (3) FOR THE | | | REQUIRED 20 AMP BATHROOM CIRCUIT. | | | | | | 4) SHOW COMPLIANCE WITH NEC 210.8 (A) (1), (2) AND (3) | | | FOR GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION. | | | | | | 5) SHOW COMPLIANCE WITH NEC 210.12 FOR ARC-FAULT | | | PROTECTION. | | | | | | 6) SHOW COMPLIANCE WITH NEC 406.11 FOR TAMPER-RESISTANT | | | RECEPTACLES. | | | | | | 7) SHOW COMPLIANCE WITH NEC 210.52 (A) (1) FOR | | | RECEPTACLE SPACING. | | | | | | 8) SHOW COMPLIANCE WITH NEC 210.52 (D) AND (E) (1) FOR | | | BATHROOM AND OUTDOOR RECEPTACLE OUTLETS. | | | | | | 9) SHOW COMPLIANCE WITH NEC 210.70 (A) (1), (2) AND (3) | | | FOR REQUIRED INTERIOR AND OUTDOOR LIGHTING OUTLETS. | | | | | | 10) THE NAME AND LICENSE NUMBER OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN IS REQUIRED ON THE | | | ELECTRICAL PLANS. CITY AMENDMENTS 107.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|