| 2014-05-08 13:28:40 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE PALM BEACH COUNTY PROPERTY APPRAISER RECORDS |
| | SHOW THAT THIS STRUCTURE IS A ONE STORY GARAGE |
| | APARTMENT. THE CITY OF WEST PALM BEACH DOES NOT HAVE |
| | ANY RECORDS THAT INDICATE THAT THE 16' X 22' GARAGE |
| | PORTION WAS CONVERTED TO LIVING AREA WITH THE REQUIRED |
| | PERMITS AND INSPECTIONS. IN ORDER TO BRING THE GUEST |
| | HOUSE INTO COMPLIANCE, THE AREA THAT WAS CONVERTED FROM |
| | GARAGE TO LIVING SPACE WILL HAVE TO BE MADE CODE |
| | COMPLIANT OR RETURNED TO A GARAGE. THE FOLLOWING REVIEW |
| | WILL BE WHAT IS REQUIRED TO BRING THE CONVERTED GARAGE |
| | INTO COMPLIANCE. 2010 FBC EXISTING BUILDING, 2010 FBC |
| | RESIDENTIAL AND 2008 NEC |
| | |
| | 2) GENERAL NOTE #9 ON SHEET GH1 NEEDS TO BE CORRECTED. |
| | THE WINDSPEED IS 170 MPH VULT , THE EXPOSURE CATEGORY |
| | IS D AND THE APPLICABLE BUILDING CODE IS THE 2010 |
| | FLORIDA BUILDING CODE. |
| | |
| | 3) UNLESS YOU CAN SHOW THAT THE EXTERIOR FRENCH DOOR |
| | AND THE WINDOWS IN THE CONVERTED GARAGE WERE PERMITTED |
| | AND INSPECTED, PRODUCT APPROVALS WILL NEED TO BE |
| | SUBMITTED AS REQUIRED BY DCA RULE 9N-3. |
| | |
| | 4) SHOW COMPLIANCE WITH FBCR 301.2.1.2 WHICH REQUIRES |
| | THE WINDOWS AND DOORS WITH GLAZED AREAS TO PROTECTED |
| | FROM LARGE MISSILE IMPACT. IMPACT RATED EXTERIOR DOORS |
| | AND WINDOWS OR STORM PANELS WILL BE REQUIRED. |
| | |
| | 5) PRODUCT APPROVALS WILL BE REQUIRED FOR THE STORM |
| | PANELS. A KEY PLAN AND INSTALLATION SCHEDULE THAT |
| | PROVIDES COMPLETE INSTALLATION DETAILS IS REQUIRED. DCA |
| | RULE 9N-3, CITY AMENDMENTS 107.2.1 AND 107.2.1.3 |
| | |
| | 6) THE CONTINUOUS LOAD PATH FROM THE ROOF THE THE |
| | FOUNDATION WILL NEED TO BE EVALUATED. IF IT IS NOT CODE |
| | COMPLIANT, ADDITION STRAPS AND CONNECTORS MAY BE |
| | REQUIRED. FBC R301.1 |
| | |
| | 7) SMOKE ALARMS AS REQUIRED FOR NEW DWELLINGS WILL BE |
| | REQUIRED. FBC R314.3.1 |
| | |
| | 8)THE ELECTRICAL SYSTEM WILL NEED TO BE MADE CODE |
| | COMPLIANT. SEE ELECTRICAL REVIEW NOTES. 2008 NEC |
| | |
| | 9) BECAUSE THE STRUCTURE IS HISTORIC PER FS 267.021, IT |
| | IS EXEMPT FROM THE 2010 FBC ENERGY CODE PER SECTION |
| | 101.4.2. |
| | |