| Plan Review Notes For Permit 14050157 |
| Permit Number |
14050157 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-05-09 16:39:18 | GEC TO BE INCREASED TO #2CU PER ARTICLE 250.66 OF THE | | | 2008 EDITION OF THE NEC | | | | | | AN INTERSYSTEM BONDING TERMINATION IS REQUIRED PER | | | ARTICLE 250.94 OF THE 2008 EDITION OF THE NEC |
|