| Plan Review Notes For Permit 14050154 |
| Permit Number |
14050154 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-05-07 16:18:16 | 1) FBC- 107.3.5.3 ELECTRIC SERVICE RISER WITH WIRE | | | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE | | | LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON | | | FLOOR PLAN. PLEASE CLARIFY RISER TO INDICATE WIRE SIZE | | | AND TYPE. | | | | | | 2) 2010 FBC RESIDENTIAL SECTION 314 AND 315 FLOOR PLAN | | | INDICATING SMOKE DETECTORS IN REQUIRED LOCATIONS. | | | | | | 3) AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | | SERVICE GROUND. NEC 250.94 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR AT [email protected] | | | | | | |
|