| 2014-11-21 15:21:42 | 1) SUBMIT SIZING CALCULATIONS FOR THE OIL/SAND |
| | SEPARATORS. THE SEPARATOR'S DESIGN SHALL COMPLY W/2010 |
| | FPC SEC.1003.4.2 THRU 1004.4.2.2. 2ND REQUEST. |
| | 2) SUBMIT PIPING DETAILS & PLAINS FOR THE RECLAIM |
| | SYSTEM. 2ND REQUEST. WPB AMEND. TO 2010 FBC SEC. |
| | 107.2.1. |
| | 3) SHOW THE PIPE SIZE FOR THE PIPE COMING FROM THE HAND |
| | WASH BAY TO THE INTERCEPTORS. WPB AMEND. TO 2010 FBC |
| | SEC. 107.2.1. 2ND REQUEST. |
| | 4) SHT.2-2.5 - THE DRINKING FOUNTAINS SHALL BE DESIGNED |
| | FOR A FORWARD APPROACH PER THE 2010 FAC SEC.602.3. THE |
| | REQUIRED CLEAR FLOOR SPACE SHALL BE CENTERED ON THE |
| | INDIVIDUAL UNIT, NOT AS A PAIR. |
| | 5) WHAT TYPE OF EQUIPMENT WILL BE IN THE MECHANICAL |
| | ROOM? THE FLOOR DRAINS MAY HAVE TO DISCHARGE TO THE |
| | INTERCEPTORS. |
| | 6) SHT. P-3 - NOTE # 9 STATES "SEE CIVIL DRAWING FOR |
| | CONTINUATION" OF ROOF DRAIN RISER. THERE IS NO CIVIL |
| | DRAWIGN FOR THIS INFO. 2ND REQUEST. |
| | 7) SUBMIT DETAILS FOR THE OIL/SAND SEPARATORS.WPB |
| | AMENDMENTS TO 2010 FBC SEC. 107.2.1. |
| | 8) THE PLANS SHOW A FLOOR DRAIN THAT APPEARS TO BE ON |
| | THE EXTERIOR OF THE CENTRAL VACUUM BUILDING. WHAT IS |
| | THE PURPOSE FOR THIS DRAIN? IF ON THE EXTERIOR IN THE |
| | OPEN IT WILL CONVEY RAINWATER TO THE SANITARY WHICH IS |
| | A CODE VIOLATION OF FPC 1101.3. |
| | 9) THE FLOOR DRAINS IN THE DETAIL BUILDING SHALL |
| | DISCHARGE TO THE OIL/SAND SEPARATORS. |
| | 10) ALL HOSE BIBBS SHALL HAVE SHUT-OFF VALVES PER |
| | SEC.606.2 OF FPC. |
| | 11) SHT.P-2 & P-3 - THE FLOOR DRAINS IN THE DETAIL |
| | BUILDING AND THE MECHANICAL ROOM SHALL BE VENTED PER |
| | THE 2010 FPC SEC.901.2, 901.2.1. |
| | 12) TOILET ROOM # A-104 IS NOT SHOWN ON THE WATER |
| | RISER. |
| | 13) PROVISIONS SHALL BE MADE FOR THERMAL EXPANSION OF |
| | THE HOT WATER SYSTEM PER FPC SEC.607.3. |
| | 14) INDICATE THE AMOUNT OF STORAGE ONSITE OF THE |
| | ULTRAFLEX HIGH ALKALINE CLEANER. THE AMOUNT SHALL NOT |
| | EXCEED THE QUANTITY ALLOWED PER TABLE 307.1 (2) OF THE |
| | 2010 FBCV. ALSO, PROVIDE DETAILS AS TO HOW THE PRODUCT |
| | IS STORED AND WHERE. |
| | 15) INDICATE THE AMOUNT OF STORAGE ONSITE OF THE |
| | ULTRAFLEX LIQUIBASE. THE AMOUNT SHALL NOT EXCEED THE |
| | QUANTITY ALLOWED PER TABLE 307.1 (2) OF THE 2010 FBC. |
| | ALSO, PROVIDE DETAILS AS TO HOW THE PRODUCT IS STORED |
| | AND WHERE. |
| | 16) THE 2ND FLR. AREA IN THE MAIN BUILDING SHALL |
| | REQUIRE VERTICAL ACCESSIBILITY PER THE 2010 FL. |
| | ACCESSIBILITY CODE SEC.201.1.1 UNLESS ONE OF THE |
| | EXCEPTIONS ARE MET. |
| | |
| | NOTE: I SUGGEST CONTACTING ME AT 561-805-6692 TO GO |
| | OVER THESE COMMENTS SO WE CAN GET THE PLAN APPROVED. |
| | |