Plan Review Notes
Plan Review Notes For Permit 14050151
Permit Number 14050151
Review Stop P
Sequence Number 3
Notes
Date Text
2014-11-21 15:21:421) SUBMIT SIZING CALCULATIONS FOR THE OIL/SAND
 SEPARATORS. THE SEPARATOR'S DESIGN SHALL COMPLY W/2010
 FPC SEC.1003.4.2 THRU 1004.4.2.2. 2ND REQUEST.
 2) SUBMIT PIPING DETAILS & PLAINS FOR THE RECLAIM
 SYSTEM. 2ND REQUEST. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 3) SHOW THE PIPE SIZE FOR THE PIPE COMING FROM THE HAND
 WASH BAY TO THE INTERCEPTORS. WPB AMEND. TO 2010 FBC
 SEC. 107.2.1. 2ND REQUEST.
 4) SHT.2-2.5 - THE DRINKING FOUNTAINS SHALL BE DESIGNED
 FOR A FORWARD APPROACH PER THE 2010 FAC SEC.602.3. THE
 REQUIRED CLEAR FLOOR SPACE SHALL BE CENTERED ON THE
 INDIVIDUAL UNIT, NOT AS A PAIR.
 5) WHAT TYPE OF EQUIPMENT WILL BE IN THE MECHANICAL
 ROOM? THE FLOOR DRAINS MAY HAVE TO DISCHARGE TO THE
 INTERCEPTORS.
 6) SHT. P-3 - NOTE # 9 STATES "SEE CIVIL DRAWING FOR
 CONTINUATION" OF ROOF DRAIN RISER. THERE IS NO CIVIL
 DRAWIGN FOR THIS INFO. 2ND REQUEST.
 7) SUBMIT DETAILS FOR THE OIL/SAND SEPARATORS.WPB
 AMENDMENTS TO 2010 FBC SEC. 107.2.1.
 8) THE PLANS SHOW A FLOOR DRAIN THAT APPEARS TO BE ON
 THE EXTERIOR OF THE CENTRAL VACUUM BUILDING. WHAT IS
 THE PURPOSE FOR THIS DRAIN? IF ON THE EXTERIOR IN THE
 OPEN IT WILL CONVEY RAINWATER TO THE SANITARY WHICH IS
 A CODE VIOLATION OF FPC 1101.3.
 9) THE FLOOR DRAINS IN THE DETAIL BUILDING SHALL
 DISCHARGE TO THE OIL/SAND SEPARATORS.
 10) ALL HOSE BIBBS SHALL HAVE SHUT-OFF VALVES PER
 SEC.606.2 OF FPC.
 11) SHT.P-2 & P-3 - THE FLOOR DRAINS IN THE DETAIL
 BUILDING AND THE MECHANICAL ROOM SHALL BE VENTED PER
 THE 2010 FPC SEC.901.2, 901.2.1.
 12) TOILET ROOM # A-104 IS NOT SHOWN ON THE WATER
 RISER.
 13) PROVISIONS SHALL BE MADE FOR THERMAL EXPANSION OF
 THE HOT WATER SYSTEM PER FPC SEC.607.3.
 14) INDICATE THE AMOUNT OF STORAGE ONSITE OF THE
 ULTRAFLEX HIGH ALKALINE CLEANER. THE AMOUNT SHALL NOT
 EXCEED THE QUANTITY ALLOWED PER TABLE 307.1 (2) OF THE
 2010 FBCV. ALSO, PROVIDE DETAILS AS TO HOW THE PRODUCT
 IS STORED AND WHERE.
 15) INDICATE THE AMOUNT OF STORAGE ONSITE OF THE
 ULTRAFLEX LIQUIBASE. THE AMOUNT SHALL NOT EXCEED THE
 QUANTITY ALLOWED PER TABLE 307.1 (2) OF THE 2010 FBC.
 ALSO, PROVIDE DETAILS AS TO HOW THE PRODUCT IS STORED
 AND WHERE.
 16) THE 2ND FLR. AREA IN THE MAIN BUILDING SHALL
 REQUIRE VERTICAL ACCESSIBILITY PER THE 2010 FL.
 ACCESSIBILITY CODE SEC.201.1.1 UNLESS ONE OF THE
 EXCEPTIONS ARE MET.
  
 NOTE: I SUGGEST CONTACTING ME AT 561-805-6692 TO GO
 OVER THESE COMMENTS SO WE CAN GET THE PLAN APPROVED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692