| 2014-08-24 11:36:01 | BUILDING PLAN REVIEW |
| | PERMIT: 14050151 |
| | ADD: 1950 GOLDEN LAKES BLVD. |
| | CONT: ANTIOCH CONSTRUCTION |
| | TEL: (813)220-0281 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2ND REVIEW |
| | DATE: SUN AUGUST 24/2014 |
| | ACTION: DENIED |
| | |
| | NOTICE: |
| | CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A |
| | LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE |
| | FEE FOR |
| | PLAN REVIEW, IF PLANS ARE REJECTED OR MORE TIMES FOR |
| | REPEATED FAILURE TO CORRECT A CODE VIOLATION. |
| | |
| | |
| | 1) THE SUBMITTED VALUE FOR THE 3 BUILDINGS $ |
| | 1,948,959.38 IS LOW, THE CALCUALTED VALUE THE CITY |
| | VALUES THIS PROJECT AT IS $2,408,748.60. THIS IS |
| | DERIVED BY THE SQUARE FOOTAGE OF THE 3 BUILDINGS 15,178 |
| | @ $158.70= $2,408,748.60. |
| | |
| | W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. |
| | ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, |
| | AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, |
| | A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| | ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| | APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2) 2ND REQUEST, THE RESPONSE INDICATED THE SOILS REPORT |
| | WAS ATTACHED? THIS IS NEW CONSTRUCTION AND WILL REQUIRE |
| | A SOILS TEST & REPORT. 2010 FBC-B 1803.5.2 QUESTIONABLE |
| | SOIL. WHERE THE CLASSIFICATION, STRENGTH OR |
| | COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A |
| | LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE |
| | PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION |
| | BE CONDUCTED. 1803.6 REPORTING. WHERE GEOTECHNICAL |
| | INVESTIGATIONS ARE REQUIRED, A WRITTEN REPORT OF THE |
| | INVESTIGATIONS SHALL BE SUBMITTED TO THE BUILDING |
| | OFFICIAL BY THE OWNER OR AUTHORIZED AGENT AT THE TIME |
| | OF PERMIT APPLICATION. |
| | |
| | 3) 2ND REQUEST, THE RESPONSE INDICATED THE FLOOD |
| | ELEVATION CERTIFICATE WAS ATTACHED. FBC BUILDING |
| | 3110.1.2 / CITY OF WPB CODE OF ORDINANCES SECTION |
| | 94-546. STRUCTURE IS LOCATED IN AN "A -H" FLOOD ZONE , |
| | BASE FLOOD IS ELEVATION 17'-0" NGVD. |
| | NOTE THAT THE SURVEY DOES NOT PROVIDE THE PROPOSED |
| | FINISH FLOOR HEIGHT OF THE MECHANICAL ROOM, WASH |
| | TUNNEL, VENDING ROOM,OR WASHER ROOM. |
| | |
| | . A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. |
| | PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS |
| | REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION ABOVE THE |
| | BASE FLOOD. |
| | |
| | |
| | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| | HEIGHT. |
| | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| | ELEVATION CERTIFICATE IS REQUIRED |
| | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| | ATTENDANT |
| | A/C PADS OR OTHER SLABS FOR GENERATORS |
| | |
| | FEMA FORM OMB NO. 1660-0008 EXPIRES: |
| | JULY 31,2015 |
| | |
| | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| | USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. |
| | FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE |
| | NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| | |
| | 4) 2ND REQUEST. THE SURVEY SHEET 2 OF 16 INDICATES BY |
| | SCALE THE TUNNEL BAY IS APPROXIMATELY 7 FT. FROM THE |
| | PROPERTY LINE. 2010 FBC-B TABLE 602 WILL REQUIRE THIS |
| | WALL TO BE A 1 HOUR FIRE RATED WALL AND TABLE 705.8 |
| | WILL ALLOW 10% OF THE WALL TO HAVE UNPROTECTED OPENINGS |
| | ,PLEASE CALCULATE THE PERCENTAGE OF UNPROTECTED |
| | OPENINGS WITH THIS WALL. |
| | 1ST REQUEST. PLEASE PROVIDE A SURVEY WITH THE |
| | DIMENSIONS OF HE PROPOSED BUILDING AND HOW FAR AWAY |
| | THEY WILL BE FROM THE PROPERTY LINE. 2010 FBC-B TABLE |
| | 602. |
| | FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS |
| | BASED ON FIRE SEPARATION DISTANCE |
| | |
| | 5A) SHEET 03 & 04 NOA 11-101314 & NOA 10-09022 |
| | PRESSURES ARE GOOD BUT THE PAGE 1, E-1 & E-2 AS WELL AS |
| | TECHNICAL SHEETS ARE TO SMALL FOR RECORD RECORDING. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION,107.2.1.4 QUALITY OF |
| | BUILDING PLANS. THE BUILDING OFFICIAL MAY |
| | ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS |
| | FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| | CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY |
| | MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, |
| | CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS |
| | MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH |
| | THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. |
| | |
| | 5B) SHEET 07 |
| | FL16554 YKK 35H MISSING PRESSURES AND INSTALLATION |
| | INSTRUCTIONS |
| | FL15869 REPUBLIC EXTERIOR DOOR +/- 70 , MISSING |
| | INSTALLATION INSTRUCTIONS |
| | FL2211 ROLL UP DOOR +/- 98.3 MISSING INSTALLATION |
| | INSTRUCTIONS |
| | FL10234 RUSKIN LOUVER +/- 130 MISSING INSTALLATION |
| | INSTRUCTIONS |
| | |
| | 5C) SHEET 08 |
| | FL 2524 EFIS MISSING PRESSURES & INSTALLATION |
| | INSTRUCTIONS |
| | FL GAF FL 5680 MISSING SUB-SYSTEMS AND PRESSURES |
| | FL 5680 TRINTY ERD MISSING SHEET 2 /61 NOTE # 2 |
| | FASTENER LENGTH FOR WOOD, STEEL & CONCRETE |
| | |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION,107.2.1.4 QUALITY OF |
| | BUILDING PLANS. THE BUILDING OFFICIAL MAY |
| | ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS |
| | FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| | CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY |
| | MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, |
| | CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS |
| | MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH |
| | THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. |
| | |
| | |
| | 6) 2ND REQUEST. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS. SWING AND ROLL UP DOORS |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, DENSE GLASS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. |
| | |
| | 8) COMPLIED. SUBMITTED PRESSURES ARE IN VULT FOR 165 |
| | MPH, EXP. C MEAN ROOF HEIGHT 34 FT. |
| | |
| | |
| | 9) COMPLIED. |
| | |
| | 10- 11) DEFERRED SUBMITTAL BY SPECIALTY ENGINEER, TOWER |
| | AND TRIM. |
| | 11C) SHEET S6-13 DETAIL 4 TOWER TRIM ABOVE THE ROOFING |
| | SYSTEM, THERE IS NO STRUCTURAL DETAILS OF HOW THIS |
| | COMPONENT IS TO BE DESIGNED OR TO BE ANCHORED TO THE |
| | TOWER ROOFING AND OR PARAPET. IS THIS SYSTEM TO BE A |
| | COMPOSITE MATERIAL (MCM PANELS) NEEDING TO COMPLY WITH |
| | 1407. |
| | |
| | 12-17 ) COMPLIED. |
| | |
| | 18) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 19) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |