Plan Review Notes
Plan Review Notes For Permit 14050151
Permit Number 14050151
Review Stop B
Sequence Number 2
Notes
Date Text
2014-08-24 11:36:01BUILDING PLAN REVIEW
 PERMIT: 14050151
 ADD: 1950 GOLDEN LAKES BLVD.
 CONT: ANTIOCH CONSTRUCTION
 TEL: (813)220-0281
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: SUN AUGUST 24/2014
 ACTION: DENIED
  
 NOTICE:
 CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A
 LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE
 FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED OR MORE TIMES FOR
 REPEATED FAILURE TO CORRECT A CODE VIOLATION.
  
  
 1) THE SUBMITTED VALUE FOR THE 3 BUILDINGS $
 1,948,959.38 IS LOW, THE CALCUALTED VALUE THE CITY
 VALUES THIS PROJECT AT IS $2,408,748.60. THIS IS
 DERIVED BY THE SQUARE FOOTAGE OF THE 3 BUILDINGS 15,178
 @ $158.70= $2,408,748.60.
  
 W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES.
 ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL,
 AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT,
 A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) 2ND REQUEST, THE RESPONSE INDICATED THE SOILS REPORT
 WAS ATTACHED? THIS IS NEW CONSTRUCTION AND WILL REQUIRE
 A SOILS TEST & REPORT. 2010 FBC-B 1803.5.2 QUESTIONABLE
 SOIL. WHERE THE CLASSIFICATION, STRENGTH OR
 COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED. 1803.6 REPORTING. WHERE GEOTECHNICAL
 INVESTIGATIONS ARE REQUIRED, A WRITTEN REPORT OF THE
 INVESTIGATIONS SHALL BE SUBMITTED TO THE BUILDING
 OFFICIAL BY THE OWNER OR AUTHORIZED AGENT AT THE TIME
 OF PERMIT APPLICATION.
  
 3) 2ND REQUEST, THE RESPONSE INDICATED THE FLOOD
 ELEVATION CERTIFICATE WAS ATTACHED. FBC BUILDING
 3110.1.2 / CITY OF WPB CODE OF ORDINANCES SECTION
 94-546. STRUCTURE IS LOCATED IN AN "A -H" FLOOD ZONE ,
 BASE FLOOD IS ELEVATION 17'-0" NGVD.
 NOTE THAT THE SURVEY DOES NOT PROVIDE THE PROPOSED
 FINISH FLOOR HEIGHT OF THE MECHANICAL ROOM, WASH
 TUNNEL, VENDING ROOM,OR WASHER ROOM.
  
 . A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION ABOVE THE
 BASE FLOOD.
  
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANT
 A/C PADS OR OTHER SLABS FOR GENERATORS
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31,2015
  
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
 FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE
 NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 4) 2ND REQUEST. THE SURVEY SHEET 2 OF 16 INDICATES BY
 SCALE THE TUNNEL BAY IS APPROXIMATELY 7 FT. FROM THE
 PROPERTY LINE. 2010 FBC-B TABLE 602 WILL REQUIRE THIS
 WALL TO BE A 1 HOUR FIRE RATED WALL AND TABLE 705.8
 WILL ALLOW 10% OF THE WALL TO HAVE UNPROTECTED OPENINGS
 ,PLEASE CALCULATE THE PERCENTAGE OF UNPROTECTED
 OPENINGS WITH THIS WALL.
 1ST REQUEST. PLEASE PROVIDE A SURVEY WITH THE
 DIMENSIONS OF HE PROPOSED BUILDING AND HOW FAR AWAY
 THEY WILL BE FROM THE PROPERTY LINE. 2010 FBC-B TABLE
 602.
 FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS
 BASED ON FIRE SEPARATION DISTANCE
  
 5A) SHEET 03 & 04 NOA 11-101314 & NOA 10-09022
 PRESSURES ARE GOOD BUT THE PAGE 1, E-1 & E-2 AS WELL AS
 TECHNICAL SHEETS ARE TO SMALL FOR RECORD RECORDING.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION,107.2.1.4 QUALITY OF
 BUILDING PLANS. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 5B) SHEET 07
 FL16554 YKK 35H MISSING PRESSURES AND INSTALLATION
 INSTRUCTIONS
 FL15869 REPUBLIC EXTERIOR DOOR +/- 70 , MISSING
 INSTALLATION INSTRUCTIONS
 FL2211 ROLL UP DOOR +/- 98.3 MISSING INSTALLATION
 INSTRUCTIONS
 FL10234 RUSKIN LOUVER +/- 130 MISSING INSTALLATION
 INSTRUCTIONS
  
 5C) SHEET 08
 FL 2524 EFIS MISSING PRESSURES & INSTALLATION
 INSTRUCTIONS
 FL GAF FL 5680 MISSING SUB-SYSTEMS AND PRESSURES
 FL 5680 TRINTY ERD MISSING SHEET 2 /61 NOTE # 2
 FASTENER LENGTH FOR WOOD, STEEL & CONCRETE
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION,107.2.1.4 QUALITY OF
 BUILDING PLANS. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
  
 6) 2ND REQUEST. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS. SWING AND ROLL UP DOORS
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, DENSE GLASS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 8) COMPLIED. SUBMITTED PRESSURES ARE IN VULT FOR 165
 MPH, EXP. C MEAN ROOF HEIGHT 34 FT.
  
  
 9) COMPLIED.
  
 10- 11) DEFERRED SUBMITTAL BY SPECIALTY ENGINEER, TOWER
 AND TRIM.
 11C) SHEET S6-13 DETAIL 4 TOWER TRIM ABOVE THE ROOFING
 SYSTEM, THERE IS NO STRUCTURAL DETAILS OF HOW THIS
 COMPONENT IS TO BE DESIGNED OR TO BE ANCHORED TO THE
 TOWER ROOFING AND OR PARAPET. IS THIS SYSTEM TO BE A
 COMPOSITE MATERIAL (MCM PANELS) NEEDING TO COMPLY WITH
 1407.
  
 12-17 ) COMPLIED.
  
 18) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 19) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  