| 2014-05-25 18:14:03 | PLUMBING PLAN REVIEW |
| | PERMIT: 14050151 |
| | ADD: 1950 GOLDEN LAKES BLVD. |
| | CONT: ANTIOCH CONSTRUCTION |
| | TEL: (813)220-0281 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: SUN MAY 25/2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 3-1 PLEASE PROVIDE THE ROOF SIZING CALCUALTION |
| | FOR AREA AND 1/2 OF THE PARAPETS AND AND CONTRIBUTING |
| | WALLS AND OR ROOF AREAS. 2010 FBC-B P] 1503.4 ROOF |
| | DRAINAGE. UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF |
| | EDGES, DESIGN AND INSTALLATION OF ROOF DRAINAGE SYSTEMS |
| | SHALL COMPLY WITH SECTION 1503 AND THE FLORIDA BUILDING |
| | CODE, PLUMBING, CHAPTER 11. PROVIDE THE 100 YEAR, 1 |
| | HOUR RAIN FALL FOR THIS AREA AND SIZE ROOF DRAINAGE |
| | INACCORDANCE WITH TABLES 1106.2(1) VERTICAL AND 1106.3 |
| | FOR HORIZONTAL RUNS. |
| | |
| | 2) SHEET SHEET A2-1 THE FRONT OFFICE HAS A TOILET ROOM |
| | DIRECTLY BEHIND THE OFFICE, WHICH IS NOT ACCESSIBLE AS |
| | THE OTHER 2 RETROOMS LOCATED ON THE FIRST FLOOR. PLEASE |
| | REVIEW |
| | 2010 FL ACCESS CODE 213.2 TOILET ROOMS AND BATHING |
| | WHERE TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL |
| | COMPLY WITH 603. WHERE BATHING ROOMS ARE PROVIDED, EACH |
| | BATHING ROOM SHALL COMPLY WITH 603. |
| | EXCEPTION # 4. WHERE MULTIPLE SINGLE USER TOILET ROOMS |
| | ARE CLUSTERED AT A SINGLE LOCATION, NO MORE THAN 50 |
| | PERCENT OF THE SINGLE USER TOILET ROOMS FOR EACH USE AT |
| | EACH CLUSTER SHALL BE REQUIRED TO COMPLY WITH 603. THE |
| | RESTROOM BEHIND THE OFFICE IS A SEPERATE CLUSTER ANAD |
| | WOULD NEED TO BE ACCESSIBLE. |
| | |
| | 3) THE BATHROOM UPSTAIRS IS SHOWN TO BE A ACCESSIBLE |
| | BATHROOM WITH A ROLLIN SHOWER, NO CURB IS SHOWN. THE |
| | PLANS DO NOT INDICATE WHAT MATERIAL THE SHOWER LINER |
| | WILL BE MADE OF AND WHAT WILL STOP THE WATER FROM GOING |
| | OUT ONTO THE FLOOR. 2010 FBC-P 312.9. |
| | |
| | 4) NONE OF THE PLUMBING SHEETS INDICATE HOW THE CITY'S |
| | WATER SUPPLY WILL BE PROTECTED SHOW COMPLIANCE WITH |
| | 2010 FBC-PLUMBING 312.10 INSPECTION AND TESTING OF |
| | BACKFLOW PREVENTION ASSEMBLIES. INSPECTION AND TESTING |
| | SHALL COMPLY WITH SECTIONS 312.10.1 AND 312.10.2. |
| | 312.10.2 TESTING. REDUCED PRESSURE PRINCIPLE BACKFLOW |
| | PREVENTER ASSEMBLIES, DOUBLE CHECK-VALVE ASSEMBLIES, |
| | PRESSURE VACUUM BREAKER ASSEMBLIES, REDUCED PRESSURE |
| | DETECTOR FIRE PROTECTION BACKFLOW PREVENTION |
| | ASSEMBLIES, DOUBLE CHECK DETECTOR FIRE PROTECTION |
| | BACKFLOW PREVENTION ASSEMBLIES, HOSE CONNECTION |
| | BACKFLOW PREVENTERS, AND SPILL-PROOF VACUUM BREAKERS |
| | SHALL BE TESTED AT THE TIME OF INSTALLATION AND |
| | IMMEDIATELY AFTER REPAIRS OR RELOCATION. THE TESTING |
| | PROCEDURE SHALL BE PERFORMED IN ACCORDANCE WITH ONE OF |
| | THE FOLLOWING STANDARDS: |
| | ASSE 5013, ASSE 5015, ASSE 5020, ASSE 5047, ASSE 5048, |
| | ASSE 5052, ASSE 5056, CSA B64.10 OR CSA B64.10.1. |
| | |
| | 608.5 CHEMICALS AND OTHER SUBSTANCES. |
| | CHEMICALS AND OTHER SUBSTANCES THAT PRODUCE EITHER |
| | TOXIC CONDITIONS, TASTE, ODOR OR DISCOLORATION IN A |
| | POTABLE WATER SYSTEM SHALL NOT BE INTRODUCED INTO, OR |
| | UTILIZED IN, SUCH SYSTEMS. |
| | |
| | 608.6 CROSS-CONNECTION CONTROL. |
| | CROSS CONNECTIONS SHALL BE PROHIBITED, EXCEPT WHERE |
| | APPROVED PROTECTIVE DEVICES ARE INSTALLED. |
| | |
| | 5) SHEET P1 DOES NOT PROVIDE DETAILS FOR THE TRENCH |
| | DRAIN FOR THE CAR WASH NOR DOES THE PLAN INDICATE HOW |
| | COMPLIANCE WITH 1003.4.2 OIL SEPARATOR DESIGN. |
| | OIL SEPARATORS SHALL BE DESIGNED IN ACCORDANCE WITH |
| | SECTIONS 1003.4.2.1 AND 1003.4.2.2. |
| | |
| | 1003.4.2.1 GENERAL DESIGN REQUIREMENTS. |
| | OIL SEPARATORS SHALL HAVE A DEPTH OF NOT LESS THAN 2 |
| | FEET (610 MM) BELOW THE INVERT OF THE DISCHARGE DRAIN. |
| | THE OUTLET OPENING OF THE SEPARATOR SHALL HAVE NOT LESS |
| | THAN AN 18-INCH (457 MM) WATER SEAL. |
| | |
| | 1003.4.2.2 GARAGES AND SERVICE STATIONS. |
| | WHERE AUTOMOBILES ARE SERVICED, GREASED, REPAIRED OR |
| | WASHED OR WHERE GASOLINE IS DISPENSED, OIL SEPARATORS |
| | SHALL HAVE A MINIMUM CAPACITY OF 6 CUBIC FEET (0.168 |
| | M3) FOR THE FIRST 100 SQUARE FEET (9.3 M2) OF AREA TO |
| | BE DRAINED, PLUS 1 CUBIC FOOT (0.28 M3) FOR EACH |
| | ADDITIONAL 100 SQUARE FEET (9.3 M2) OF AREA TO BE |
| | DRAINED INTO THE SEPARATOR. PARKING GARAGES IN WHICH |
| | SERVICING, REPAIRING OR WASHING IS NOT CONDUCTED, AND |
| | IN WHICH GASOLINE IS NOT DISPENSED, SHALL NOT REQUIRE A |
| | SEPARATOR. AREAS OF COMMERCIAL GARAGES UTILIZED ONLY |
| | FOR STORAGE OF AUTOMOBILES ARE NOT REQUIRED TO BE |
| | DRAINED THROUGH A SEPARATOR. |
| | |
| | THE PLANS INDICATE TO BE DESIGNED BY OTHERS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |