2014-06-10 15:39:21DATE: 6/10/2014
 PROJECT: LUX AUTO SPA
 PERMIT#: 14050151
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 2012 FBC
 SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 1ST REVIEW
 ACTION: DENIED
  
 1) CLARIFY THE RISER DIAGRAM. INDICATE THE LOCATION OF
 EACH OF THE PANELS ON THE RISER DIAGRAM AND INCLUDE THE
 BUILDINGS IN WHICH THEY RESIDE.
  
 2) CLARIFY THE FLOOR PLANS AND SITE PLAN. INDICATE THE
 LOCATION OF EACH OF THE PANELS ON THE FLOOR PLAN AND
 SITE PLAN INCLUDING THE BUILDINGS IN WHICH THEY RESIDE.
  
 3) CLARIFY GROUNDING. THE GROUND SYMBOLS ON THE PLANS
 INDICATE MULTIPLE GROUNDING ELECTRODES. ALL GROUNDING
 TO BE COMMON FOR THE GROUNDING SYSTEM 250.64, 250.86,
 250.94, 250.106 AND OTHER SECTIONS AS APPLICABLE.
  
 4) PROVIDE SAFETY LABELING FOR FLASH PROTECTION AND FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.22, 110.16, 110.22
  
 5) ILLUMINATION OF MEANS OF EGRESS SHALL BE PROVIDED IN
 ACCORDANCE WITH THIS SECTION FOR EVERY BUILDING AND
 STRUCTURE. FOR THE PURPOSE OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCELATORS, WALKWAYS AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY. ADDITIONAL
 EMERGENCY BATTERY BACKED LIGHTING IS REQUIRED FOR
 ADAQUATE ILLUMINATION OF THE EGRESS PATH. FBC 1006.1.1
  
 6) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY
 AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS
 THAT SERVING THE NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES. NEC 701.11(G)
  
 7) INDICATE COMPLIANCE WITH FBC-ENERGY. ELECTRICAL
 POWER AND LIGHTING SYSTEMS. (MANDATORY) SECTION 505.
 LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 REQUIRED IN SECTIONS FBC-ENERGY, 505.2.1, 505.2.2,
 505.2.3, AND 505.2.4
  
 8) INTERNALLY ILLUMINATED EXIT SIGNS SHALL NOT EXCEED 5
 WATTS PER SIDE. FBC-ENERGY, 505.4
  
 9) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN
 SHOWING COMPLIANCE WITH THE FBC ENERGY 505.5.3
  
 10) LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED
 IN SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE
 OF TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT
 DAYLIGHT IS AVAILABLE OR WHEN THE LIGHTING IS NOT
 REQUIRED DURING NIGHTTIME HOURS. LIGHTING NOT
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS.
  
 11) MECHANICAL EQUIPMENT, ELECTRICAL, TRANSFORMER,
 TELEPHONE EQUIPMENT, ELEVATOR MACHINE OR SIMILAR ROOMS,
 A LISTED SMOKE DETECTOR SHALL BE INSTALLED. FBC
 907.2.18.1
  
 12) ALL COMPONENTS AND CABLES SHALL BE UL LISTED AND
 LABELED FOR USE IN THE MANNER INSTALLED. NEC 110.3
 NOTE: SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR
 SIGNS, SECURITY, NETWORK, CCTV, AUDIO/VIDEO AND FOR THE
 INSTALLATION AND TERMINATION OF THE OUTDOOR MENU
 BOARDS, CANOPY, AND PRE-SALE BOARD.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR AT [email protected]
  