| 2014-06-10 15:39:21 | DATE: 6/10/2014 |
| | PROJECT: LUX AUTO SPA |
| | PERMIT#: 14050151 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 2012 FBC |
| | SUPPLEMENTS. |
| | ELECTRICAL PLAN REVIEW |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) CLARIFY THE RISER DIAGRAM. INDICATE THE LOCATION OF |
| | EACH OF THE PANELS ON THE RISER DIAGRAM AND INCLUDE THE |
| | BUILDINGS IN WHICH THEY RESIDE. |
| | |
| | 2) CLARIFY THE FLOOR PLANS AND SITE PLAN. INDICATE THE |
| | LOCATION OF EACH OF THE PANELS ON THE FLOOR PLAN AND |
| | SITE PLAN INCLUDING THE BUILDINGS IN WHICH THEY RESIDE. |
| | |
| | 3) CLARIFY GROUNDING. THE GROUND SYMBOLS ON THE PLANS |
| | INDICATE MULTIPLE GROUNDING ELECTRODES. ALL GROUNDING |
| | TO BE COMMON FOR THE GROUNDING SYSTEM 250.64, 250.86, |
| | 250.94, 250.106 AND OTHER SECTIONS AS APPLICABLE. |
| | |
| | 4) PROVIDE SAFETY LABELING FOR FLASH PROTECTION AND FOR |
| | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| | 110.22, 110.16, 110.22 |
| | |
| | 5) ILLUMINATION OF MEANS OF EGRESS SHALL BE PROVIDED IN |
| | ACCORDANCE WITH THIS SECTION FOR EVERY BUILDING AND |
| | STRUCTURE. FOR THE PURPOSE OF THIS REQUIREMENT, EXIT |
| | ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, |
| | CORRIDORS, RAMPS, ESCELATORS, WALKWAYS AND EXIT |
| | PASSAGEWAYS LEADING TO A PUBLIC WAY. ADDITIONAL |
| | EMERGENCY BATTERY BACKED LIGHTING IS REQUIRED FOR |
| | ADAQUATE ILLUMINATION OF THE EGRESS PATH. FBC 1006.1.1 |
| | |
| | 6) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY |
| | AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS |
| | THAT SERVING THE NORMAL LIGHTING IN THE AREA AND |
| | CONNECTED AHEAD OF ANY LOCAL SWITCHES. NEC 701.11(G) |
| | |
| | 7) INDICATE COMPLIANCE WITH FBC-ENERGY. ELECTRICAL |
| | POWER AND LIGHTING SYSTEMS. (MANDATORY) SECTION 505. |
| | LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS |
| | REQUIRED IN SECTIONS FBC-ENERGY, 505.2.1, 505.2.2, |
| | 505.2.3, AND 505.2.4 |
| | |
| | 8) INTERNALLY ILLUMINATED EXIT SIGNS SHALL NOT EXCEED 5 |
| | WATTS PER SIDE. FBC-ENERGY, 505.4 |
| | |
| | 9) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN |
| | SHOWING COMPLIANCE WITH THE FBC ENERGY 505.5.3 |
| | |
| | 10) LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED |
| | IN SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE |
| | OF TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT |
| | DAYLIGHT IS AVAILABLE OR WHEN THE LIGHTING IS NOT |
| | REQUIRED DURING NIGHTTIME HOURS. LIGHTING NOT |
| | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE |
| | CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR |
| | PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF |
| | RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS |
| | OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. |
| | |
| | 11) MECHANICAL EQUIPMENT, ELECTRICAL, TRANSFORMER, |
| | TELEPHONE EQUIPMENT, ELEVATOR MACHINE OR SIMILAR ROOMS, |
| | A LISTED SMOKE DETECTOR SHALL BE INSTALLED. FBC |
| | 907.2.18.1 |
| | |
| | 12) ALL COMPONENTS AND CABLES SHALL BE UL LISTED AND |
| | LABELED FOR USE IN THE MANNER INSTALLED. NEC 110.3 |
| | NOTE: SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR |
| | SIGNS, SECURITY, NETWORK, CCTV, AUDIO/VIDEO AND FOR THE |
| | INSTALLATION AND TERMINATION OF THE OUTDOOR MENU |
| | BOARDS, CANOPY, AND PRE-SALE BOARD. |
| | |