2014-05-25 18:12:05BUILDING PLAN REVIEW
 PERMIT: 14050151
 ADD: 1950 GOLDEN LAKES BLVD.
 CONT: ANTIOCH CONSTRUCTION
 TEL: (813)220-0281
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: SUN MAY 25/2014
 ACTION: DENIED
  
 1) THE SUBMITTED VALUE FOR THE 3 BUILDINGS $
 1,948,959.38 IS LOW, THE CALCUALTED VALUE THE CITY
 VALUES THIS PROJECT AT IS $2,408,748.60. THIS IS
 DERIVED BY THE SQUARE FOOTAGE OF THE 3 BUILDINGS 15,178
 @ $158.70= $2,408,748.60.
  
 W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES.
 ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL,
 AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT,
 A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) THIS IS NEW CONSTRUCTION AND WILL REQUIRE A SOILS
 TEST & REPORT. 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED. 1803.6
 REPORTING. WHERE GEOTECHNICAL INVESTIGATIONS ARE
 REQUIRED, A WRITTEN REPORT OF THE INVESTIGATIONS SHALL
 BE SUBMITTED TO THE BUILDING OFFICIAL BY THE OWNER OR
 AUTHORIZED AGENT AT THE TIME OF PERMIT APPLICATION.
  
 3) FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF
 ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN
 "A -H" FLOOD ZONE , BASE FLOOD IS ELEVATION 17'-0" NGVD
 . A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION ABOVE THE
 BASE FLOOD.
  
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANT
 A/C PADS OR OTHER SLABS FOR GENERATORS
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31,2015
  
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
 FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE
 NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 4) PLEASE PROVIDE A SURVEY WITH THE DIMENSIONS OF HE
 PROPOSED BUILDING AND HOW FAR AWAY THEY WILL BE FROM
 THE PROPERTY LINE. 2010 FBC-B TABLE 602.
 FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS
 BASED ON FIRE SEPARATION DISTANCE
  
 5A) SHEET 03 IS A PRODUCT APPROVAL (NOA) THE FIRST 2
 COLUMNS THE RIGHT SIDE OF EACH COLUMN IS CUT OFF,
 MISSING THE PRODUCT APPROVAL NUMBER AND EXPIRATION
 DATE.
  
 5B) ON BOTH SHEETS 03 & 04 THESE PRODUCT APPROVALS ARE
 FOR GLAZED WINDOW OPENINGS, PLEASE IDENTIFY TYPES OF
 GLAZING, WIDTH AND HEIGHT OF OPENINGS AND ASSOCIATED
 PRESSURES.
  
 6) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS. SWING AND ROLL UP DOORS
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, DENSE GLASS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 8) SHEET S1.2 COMPONENTS AND CLADDING PRESSURES ARE LOW
 FOR VULT AT 165 MPH. THE PLANS INDICATE A "B" EXPOSURE.
 TO THE NORTHEAST OF THIS PROPERTY YOU HAVE OVER 6 LANES
 OF TRAFFIC AND THE RIGHT OF WAY PLUS THE LAKE SYSTEM OF
 RIVERWALK AS WELL AS THE LAKES TO THE SOUTHEAST AND
 SOUTHWEST OF THE PROPERETY. PEASE REVIEW:
 2010 FBC-B 1609.4.2 SURFACE ROUGHNESS CATEGORIES.
  
 A GROUND SURFACE ROUGHNESS WITHIN EACH 45-DEGREE (0.79
 RAD) SECTOR SHALL BE DETERMINED FOR A DISTANCE UPWIND
 OF THE SITE AS DEFINED IN SECTION 1609.4.3 FROM THE
 CATEGORIES DEFINED BELOW, FOR THE PURPOSE OF ASSIGNING
 AN EXPOSURE CATEGORY AS DEFINED IN SECTION 1609.4.3.
  
 SURFACE ROUGHNESS C. OPEN TERRAIN WITH SCATTERED
 OBSTRUCTIONS HAVING HEIGHTS GENERALLY LESS THAN 30 FEET
 (9144 MM). THIS CATEGORY INCLUDES FLAT OPEN COUNTRY AND
 GRASSLANDS.THIS SURFACE ROUGHNESS SHALL ALSO APPLY TO
 ANY BUILDING LOCATED WITHIN SURFACE ROUGHNESS B-TYPE
 TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET
 HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF SURFACE
 ROUGHNESS C OR D-TYPE TERRAIN THAT EXTENDS MORE THAN
 600 FEET (182.9 M) AND WIDTH GREATER THAN 150 FEET IN
 THE UPWIND DIRECTION.
  
 NOTE A C-EXPOSURE WITH A HEIGHT (BUILDING HEIGHT OF 34
 FEET) ADJUSTMENT FACTOR OF 1.45 WILL GREATLY INCREASE
 THESE PRESSURES. TABLE 1609.7(2).
  
 9) SHEET S1.2 THE WIND DESIGN CRITERIA HAS A STATEMENT
 ABOUT SECTION 2610.3 WHICH IS ON THE TOPIC OF SLOPED
 GLAZING FOR FLAT OR CORREGATED PLASTIC SKYLIGHTS?
 ADDITIONAL INFORMATION REQUIED, TYPO. 107.2.1.3.
  
 10) SHEET S4.3 DETAIL S10 TOWER WALL BEING STEEL STUD
 WALL AND THE A-6-7 SHOW THE SAME TOWER CONFIGURATION
 WITH NOTES BY SPECIALLITY ENGINEER, PLEASE PROVIDE
 THESE DRAWINGS SINCE THEY WILL BE PART OF THE MAIN WIND
 FORCE RESISTING SYSTEM, ENCLOSING THE DESIGN. THE STEEL
 FRAME WALL DOES NOT INDICATE HOW IT WILL BE ATTACHED TO
 THE FIRST FLOOR CBS WALL SYSTEM CONTINUEING THE LOAD
 PATH TO THE FOUNDATION. PLEASE SHOW ALSO THE ROOF
 FRAMING MEMBERS AND HOW THEY WILL ALSO BE SECURED AND
 PART OF THE MWFRS. NOTE SHEET S4.3 DETAIL S10 ALSO
 INDICATES THE TOWER ROOFING TO BE PLYWOOD SHEATHING SEE
 PLAN. THIS IS A BUILDING TYPE IIB WHICH IN SECTION
 603.1.1.3 WILL ONLY ALLOW FOR FIRE RETARDANT TREATED
 WOOD.
  
 11) SHEETS A6 SERIES HAVE DETAILS FOR VARIOUS ROOF TRIM
 AND OR OVERHANGS:
  
 11A) SHEET 6-11 DETAIL #9 THE VENDING / VACUMM BLDG,
 THIS DETAIL AGAIN INDICATES THE USE OF WOOD PRODUCTS,
 IT WILL NEED TO BE FIRE RETARDANT TREATED WOOD PRODUCTS
 603.1.1.3. PLEASE ALSO PROVIDE DETAILS OF HOW THIS OVER
 HANG WILL ATTACH TO THE BUILDING AND WITHSTAND THE 165
 VULT WINDS. COMPONENTS AND CLADDING.
  
 11B) SHEET 6-13 DETAIL #1 HAS THE SAME ISSUES WITH WOOD
 AND PLYWOOD REQUIRING FIRE RETARDANT TREATED WOOD AS
 WELL AS ANCHORING TO THE BUILDING, COMPONENTS AND
 CLADDING.
  
 11C) SHEET S6-13 DETAIL 4 TOWER TRIM ABOVE THE ROOFING
 SYSTEM, THERE IS NO STRUCTURAL DETAILS OF HOW THIS
 COMPONENT IS TO BE DESIGNED OR TO BE ANCHORED TO THE
 TOWER ROOFING AND OR PARAPET. IS THIS SYSTEM TO BE A
 COMPOSITE MATERIAL (MCM PANELS) NEEDING TO COMPLY WITH
 1407.
  
 12) SHEET 6-13 DETAIL # 7 PROVIDE SILL FLASHING DETAILS
 IN ACCORDANCE WITH 1405.4.
  
 13) BOTH SHEETS S-11 & S13 ON THE ROOFING OVER HANG
 DETAILS INDICATE THE USE OF PAPER BACKED WIRE LATH, NEW
 TO THE 2007 FBC-B THERE ALSO HAS TO BE A BOND BREAK NOT
 SHOWN ON THE PLANS. SEE 1404.2.1
 WHERE CEMENT PLASTER (STUCCO) IS TO BE APPLIED TO LATH
 OVER FRAME CONSTRUCTION, MEASURES SHALL BE TAKEN TO
 PREVENT BONDING BETWEEN THE CEMENT PLASTER AND THE
 WATER RESISTIVE BARRIER. A BOND BREAK SHALL BE PROVIDED
 BETWEEN THE WATER RESISTIVE BARRIER AND THE CEMENT
 PLASTER (STUCCO) CONSISTING OF ONE OF THE FOLLOWING:
 1. TWO LAYERS OF AN APPROVED WATER RESISTANT BARRIER OR
 2. ONE LAYER OF AN APPROVED WATER RESISTANT BARRIER
 OVER AN APPROVED PLASTIC HOUSE WRAP, OR
 3. OTHER APPROVED METHODS OR MATERIALS APPLIED IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS.
  
 14) SHEET 2-2 RESTROOMS BACK TO BACK THE INSIDE
 DIMENSION IS 7'-0" THE MINIMUM DIMENSION WITHOUT ANY
 EXTRA TOLERANCES IS 7'-0" MINIMUM UNLESS YOU ARE USING
 A LAVATORY LESS THAN 19 INCHES IN WIDTH. THAT IS AN
 ABSOLUTE NO CHANCE OF A MISTAKE.
  
 15) SHEET 2-1 WHERE IS THE LEGEND FOR THE WALL
 IDENTIFICATION TAGS THERE IS NO LEGEND ON THIS SHEET.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. PLEASE
 IDENTIFY THE WALL BETWEEN THE STORAGE AND STAIR AS A
 ONE HOUR FIRE RATED WALL.
  
 16) SHEET 3-1 THE PLANS INDICATE ROOF DRAINS AND A
 ARROW POINTING TO OVERFLOW SCUPPERS? THE PLANS DO NOT
 PROVIDE NOTATION TO WHERE THEY CAN BE FOUND, HOW LAGRE
 IS THE OPENING FOR THE OVER FLOW SCUPPERS AND HOW FAR
 ABOVE THE ROOF ARE THEY LOCATED. 2010 FBC-B 1503.42.1.
  
 17) SHEET 3-1 PLEASE PROVIDE THE ROOF SIZING
 CALCUALTION FOR AREA AND 1/2 OF THE PARAPETS AND AND
 CONTRIBUTING WALLS AND OR ROOF AREAS. 2010 FBC-B P]
 1503.4 ROOF DRAINAGE. UNLESS ROOFS ARE SLOPED TO DRAIN
 OVER ROOF EDGES, DESIGN AND INSTALLATION OF ROOF
 DRAINAGE SYSTEMS SHALL COMPLY WITH SECTION 1503 AND THE
 FLORIDA BUILDING CODE, PLUMBING, CHAPTER 11.
  
 18) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 19) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  