2014-06-06 12:01:50FAILED FIRST ELECTRICAL REVIEW AS FOLLOWS:
 1. INDICATE ON PAGE E1 THE LOCATION OF THE EXISTING
 SERVICE.
 2. CORRECT ELECTRICAL RISER DIAGRAM TO MATCH EXISTING
 CONDITIONS.
 3. PROVIDE A PANEL SCHEDULE FOR OF THE THE PANELS (A,
 B, C)
 4. REVISE THE LOAD CALCS. PROVIDE LOAD CALCS FOR EACH
 PANEL FOR CLARIFICATION.
 5. CORRECT THE ELECTRICAL NOTES ON PAGE A0 TO REFLECT
 THE 2008 EDITION OF THE NEC RATHER THAN THE NOT YET
 ADOPTED LATEST EDITION. THE SMOKE DETECTOR INSTRUCTIONS
 AS STATED ARE NOT CODE COMPLIANT AND DO NOT MATCH THOSE
 OF E1. SAME WITH THE ARC-FAULT REQUIREMENTS.
  