2014-06-05 11:11:242010 FBC
  
 DENIED BY BUILDING
  
 1) THE TYPE OF CONSTRUCTION SPECIFIED ON SHEET CVR IS
 III - B. THIS IS INCORRECT. THIS STRUCTURE DOES NOT
 HAVE 2 HOUR FIRE RATED EXTERIOR WALLS. IT SHOULD BE
 TYPE V - B. FBC TABLE 601
  
 2) ON SHEET S-1 THE F1 FOOTING IN THE SCHEDULE IS 18"
 WIDE AND 16" IN DEPTH AND DETAIL 4 ON S-1 HAS 12" + 6"
 FOR A DEPTH OF 18". PLEASE CORRECT. CITY AMENDMENTS
 107.2.1
  
 3) ON SHEET S-2, THE WIND PRESSURES LISTED BELOW THE
 ROOF AREA DIAGRAM ARE NOT CORRECT FOR A STRUCTURE WITH
 A 5/12 SLOPE ROOF AND A 25' MRH LOCATED IN A 170 MPH
 VULT WINDSPEED AND EXPOSURE CATEGORY C. PLEASE CORRECT.
 FBCR 301.2.1
  
 4) THE UPLIFT CONNECTOR NOTES ON SHEET S-2 SPECIFY
 HUGHES CONNECTORS. THAT COMPANY IS NO LONGER IN
 EXISTENCE. IT WAS PURCHASED BY USP SEVERAL YEARS AGO.
 PLEASE UPDATE THE PLANS TO REFERENCE CONNECTORS WITH
 CURRENT PRODUCT
 APPROVALS. DCA RULE 9N-3.
  
 5) ON SHEET A-2 THE ID TAGS ON THE WINDOWS IN THE REAR
 OF THE ADDITION ARE INCORRECT. THE WINDOWS MARKED 'D'
 SHOULD BE 'B' AND THE HALF MOON WINDOW FIXED WINDOW
 SHOULD BE 'D' RATHER THAN 'F' IN ORDER TO CORRESPOND
 WITH THE WINDOW SCHEDULE. PLEASE CORRECT.
  
 6) THE ENERGY COMPLIANCE FORM 402 - 2010 CAN NOT BE
 USED FOR THIS PROJECT. THE GLASS AREA EXCEEDS 20
 PERCENT OF THE CONDITIONED FLOOR AREA. SEE NOTE 1 UNDER
 GENERAL INSTRUCTIONS. SHOW THAT ADDITION WILL COMPLY
 WITH 2010 FBC ENERGY CONSERVATION SECTION 401.2.
  
 7) SHOW COMPLIANCE WITH FBCR 806 FOR REQUIRED ROOF
 VENTILATION.
  
 8) SHOW COMPLIANCE WITH FBCR 807 FOR ATTIC ACCESS TO
 THE NEW ADDITION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]