| 2014-06-06 15:05:16 | PLUMBING PLAN REVIEW |
| | PERMIT: 14050116 |
| | ADD: 610 CLEMATIS ST UNITS- 2, 3 &4 |
| | CONT: PRETI CONSTRUCTION, INC |
| | TEL: (561)282-8860 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JUNE 06/2014 |
| | ACTION: DENIED |
| | |
| | SHEET P2.1 INDICATES THE USE OF AIR ADMITTANCE VALVES |
| | ON THE 1ST FLOOR SINK OF A 8 STORY BUILDING. PLEASE |
| | PROVIDE COM,PLIANCE WITH 917.3.1 LOCATION OF BRANCH. |
| | THE HORIZONTAL BRANCH DRAIN SHALL CONNECT TO THE |
| | DRAINAGE STACK OR BUILDING DRAIN A MAXIMUM OF FOUR |
| | BRANCH INTERVALS FROM THE TOP OF THE STACK. |
| | |
| | 917.3.2 RELIEF VENT. |
| | WHERE THE HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR |
| | BRANCH INTERVALS FROM THE TOP OF THE STACK, THE |
| | HORIZONTAL BRANCH SHALL BE PROVIDED WITH A RELIEF VENT |
| | THAT SHALL CONNECT TO A VENT STACK OR STACK VENT, OR |
| | EXTEND OUTDOORS TO THE OPEN AIR. THE RELIEF VENT SHALL |
| | CONNECT TO THE HORIZONTAL BRANCH DRAIN BETWEEN THE |
| | STACK AND THE MOST DOWNSTREAM FIXTURE DRAIN CONNECTED |
| | TO THE HORIZONTAL BRANCH DRAIN. THE RELIEF VENT SHALL |
| | BE SIZED IN ACCORDANCE WITH SECTION 916.2 AND INSTALLED |
| | IN ACCORDANCE WITH SECTION 905. THE RELIEF VENT SHALL |
| | BE PERMITTED TO SERVE AS THE VENT FOR OTHER FIXTURES. |
| | |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |