Plan Review Notes
Plan Review Notes For Permit 14050116
Permit Number 14050116
Review Stop P
Sequence Number 1
Notes
Date Text
2014-06-06 15:05:16PLUMBING PLAN REVIEW
 PERMIT: 14050116
 ADD: 610 CLEMATIS ST UNITS- 2, 3 &4
 CONT: PRETI CONSTRUCTION, INC
 TEL: (561)282-8860
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JUNE 06/2014
 ACTION: DENIED
  
 SHEET P2.1 INDICATES THE USE OF AIR ADMITTANCE VALVES
 ON THE 1ST FLOOR SINK OF A 8 STORY BUILDING. PLEASE
 PROVIDE COM,PLIANCE WITH 917.3.1 LOCATION OF BRANCH.
 THE HORIZONTAL BRANCH DRAIN SHALL CONNECT TO THE
 DRAINAGE STACK OR BUILDING DRAIN A MAXIMUM OF FOUR
 BRANCH INTERVALS FROM THE TOP OF THE STACK.
  
 917.3.2 RELIEF VENT.
 WHERE THE HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR
 BRANCH INTERVALS FROM THE TOP OF THE STACK, THE
 HORIZONTAL BRANCH SHALL BE PROVIDED WITH A RELIEF VENT
 THAT SHALL CONNECT TO A VENT STACK OR STACK VENT, OR
 EXTEND OUTDOORS TO THE OPEN AIR. THE RELIEF VENT SHALL
 CONNECT TO THE HORIZONTAL BRANCH DRAIN BETWEEN THE
 STACK AND THE MOST DOWNSTREAM FIXTURE DRAIN CONNECTED
 TO THE HORIZONTAL BRANCH DRAIN. THE RELIEF VENT SHALL
 BE SIZED IN ACCORDANCE WITH SECTION 916.2 AND INSTALLED
 IN ACCORDANCE WITH SECTION 905. THE RELIEF VENT SHALL
 BE PERMITTED TO SERVE AS THE VENT FOR OTHER FIXTURES.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]