| Plan Review Notes For Permit 14050112 |
| Permit Number |
14050112 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-06-05 07:16:21 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE VALUE OF $25,000.00 SPECIFIED ON THE PERMIT | | | APPLICATION IS LOW FOR THE SCOPE OF WORK SHOWN ON THE | | | PLANS. PER CITY AMENDMENTS 109.3 FOR PERMITTING | | | PURPOSES VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | | THE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | OVERHEAD AND PROFIT. | | | | | | 2) THE ENERGY FORM 402 - 2010 CAN NOT BE USED FOR THIS | | | PROJECT. THE GLASS AREA IN THE ADDITION EXCEEDS 20 | | | PERCENT OF THE CONDITIONED FLOOR AREA. SEE NOTE 1 UNDER | | | GENERAL INSTRUCTIONS ON THE FORM. | | | | | | 3) SUBMIT TWO COPIES OF ICC EVALUATION REPORT ESR 1826 | | | FOR THE ICYNENE FOAM INSULATION. FBC R316 | | | | | | 4) PLAN SHEET SP-1 SPECIFIES THE STRUCTURE IS LOCATED | | | IN EXPOSURE "C" AND ON SHEET S-000 IT IS SPECIFIED AS | | | EXPOSURE "D". PLEASE CORRECT. CITY AMENDMENTS 107.2.1 | | | AND FBC R301.2.1.4.3 | | | | | | 5) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 | | | CALCULATIONS FOR ENHANCED FASTENING OF THE TAMKO | | | MODIFIED ROOF SYSTEM ON PAGE 12 OF NOA NO. 12-0716.18. | | | FBC R301.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|