Plan Review Notes
Plan Review Notes For Permit 14050112
Permit Number 14050112
Review Stop B
Sequence Number 1
Notes
Date Text
2014-06-05 07:16:212010 FBC
  
 DENIED BY BUILDING
  
 1) THE VALUE OF $25,000.00 SPECIFIED ON THE PERMIT
 APPLICATION IS LOW FOR THE SCOPE OF WORK SHOWN ON THE
 PLANS. PER CITY AMENDMENTS 109.3 FOR PERMITTING
 PURPOSES VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 THE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 OVERHEAD AND PROFIT.
  
 2) THE ENERGY FORM 402 - 2010 CAN NOT BE USED FOR THIS
 PROJECT. THE GLASS AREA IN THE ADDITION EXCEEDS 20
 PERCENT OF THE CONDITIONED FLOOR AREA. SEE NOTE 1 UNDER
 GENERAL INSTRUCTIONS ON THE FORM.
  
 3) SUBMIT TWO COPIES OF ICC EVALUATION REPORT ESR 1826
 FOR THE ICYNENE FOAM INSULATION. FBC R316
  
 4) PLAN SHEET SP-1 SPECIFIES THE STRUCTURE IS LOCATED
 IN EXPOSURE "C" AND ON SHEET S-000 IT IS SPECIFIED AS
 EXPOSURE "D". PLEASE CORRECT. CITY AMENDMENTS 107.2.1
 AND FBC R301.2.1.4.3
  
 5) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 CALCULATIONS FOR ENHANCED FASTENING OF THE TAMKO
 MODIFIED ROOF SYSTEM ON PAGE 12 OF NOA NO. 12-0716.18.
 FBC R301.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]