Plan Review Notes
Plan Review Notes For Permit 14050111
Permit Number 14050111
Review Stop P
Sequence Number 3
Notes
Date Text
2014-08-19 15:17:31P B CONVENTION CENTER HILTON HOTEL PLUMBING REVIEW
 PLUMBING PLAN REVIEW
 PERMIT:14050111
 ADD: 600 OKEECHOBEE BLVD
 CONT: COASTAL CONSTRUCTION
 TEL: (561) 630-3770
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 THE PALM BEACH CONVENTION CENTER HILTON HOTEL
 CONSTRUCTION OF NEW 400 ROOM HOTEL INCLUDING BALLROOMS,
 RESTAURANT(S), MEETING SPACE, POOL DECK AND AMENITIES
  
 3RD REVIEW
 DATE: TUESDAY AUGUST 19/ 2014
  
 ACTION: PLUMBING PROVISO
  
 FUEL GAS: THIS REVIEW IS UNDER A SEPARATE PLAN REVIEW
 STOP, SEE FOR STATUS AND COMMENTS.
  
 1) 2ND REQUEST: THE ASSOCIATES CAFETERIA PLUMBING PLAN
 LIST EQUIPMENT AND PLUMBING FIXTURES WITH A C-LABEL.
 THE PLUMBING INDEX LIST SHEET P2.01 AS THE BANQUET
 KITCHEN & ASSO. CAFE SCHEDULE, THERE ARE NO C EQUIPMENT
 ON SHEET P2.01, THIS LIST ALL FIXTURES & EQUIPMENT ON
 THIS SHEET ARE LISTED WITH A Q. I CAN'T IDENTIFY THE
 TYPE OF EQUIPMENT FOR THE TYPE OR WASTE REQUIRED. NOTE
 # 10 REFERS TO GREASY WASTE FOR THIS SHEET BUT NOT
 IDENTIFIED ON THE PLAN.
  
 2) SHEET P1.02 LEVEL 1 AREA Q2, NOTE# 21 INDICATES A
 NEW 750 GALLON CONCRETE VAULT TYPE GREASE INTERCEPTOR,
 NOTE 36 SEE SHEET P3.01D FOR THE CONTINUATION OF GREASY
 WASTE. PLEASE PROVIDE THE SIZING CALCULATIONS FOR THE
 CONCRETE VAULT TYPE GREASE INTERCEPTOR, SIZING IS TO BE
 IN ACCORDANCE WITH 2010 FBC-P SECTION 1003.5.1 AND
 TABLE 1003.5.1.
  
 3) SHEET P1.03 LEVEL 1 AREA Q3. SHEET P1.03 LEVEL 1
 AREA Q3, NOTE# 01 INDICATES A NEW 1,250 GALLON CONCRETE
 VAULT TYPE GREASE INTERCEPTOR, NOTE REFERS TO SHEET
 P4.03 THE GREASE INTERCEPTOR DETAIL. SHEET P3.00
 INDICATES 132 FU DRAINING INTO THE GREASE INTERCEPTOR.
 IF SIZING USING TABLE 1003.3.4.1 THIS TABLE IS TO BE
 USED WHEN THE DESIGN IS FOR HYDRO MECHANICAL GREASE
 INTERCEPTORS. PLEASE PROVIDE THE SIZING CALCULATIONS
 FOR THE CONCRETE VAULT TYPE GREASE INTERCEPTOR, SIZING
 IS TO BE IN ACCORDANCE WITH 2010 FBC-P SECTION 1003.5.1
 AND TABLE 1003.5.1.
  
 THE CITY FOG INSPECTORS (FATS, OILS & GREASE) MONITOR
 ALL GREASE INTERCEPTORS TO VERIFY COMPLIANCE WITH THE
 CITY?S MUNI CODE SEC. 90-126. PROHIBITIONS AND
 LIMITATIONS OF DISCHARGE.(7) MINERAL OIL IN EXCESS OF
 50 MG/L OR ANIMAL/VEGETABLE FATS, WAX, GREASE, OR OILS
 IN EXCESS OF 100 MG/L, WHETHER EMULSIFIED OR NOT; OR
 SUBSTANCES WHICH MAY SOLIDIFY OR BECOME VISCOUS AT
 TEMPERATURES LOWER THAN OR EQUAL TO 150 DEGREES
 FAHRENHEIT (65.56 DEGREES CELSIUS).
  
 4) SHEET P1.04 LEVEL 1 AREA Q4. KITCHEN 105 , NO GREASY
 WASTE IS SHOWN ON THE PLANS, NOTE # 15 INDICATES SEE
 P2.04 FOR CONTINUATION. THIS SHEET IS A EQUIPMENT
 SCHEDULE, PLEASE PROVIDE A GREASY WASTE ISOMETRIC OR
 WHERE TO LOCATE SUCH PLANS. PLEASE PROVIDE THE SIZING
 CALCULATIONS FOR THE CONCRETE VAULT TYPE GREASE
 INTERCEPTOR, SIZING IS TO BE IN ACCORDANCE WITH 2010
 FBC-P SECTION 1003.5.1 AND TABLE 1003.5.1.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  