| 2014-08-19 15:17:31 | P B CONVENTION CENTER HILTON HOTEL PLUMBING REVIEW |
| | PLUMBING PLAN REVIEW |
| | PERMIT:14050111 |
| | ADD: 600 OKEECHOBEE BLVD |
| | CONT: COASTAL CONSTRUCTION |
| | TEL: (561) 630-3770 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | THE PALM BEACH CONVENTION CENTER HILTON HOTEL |
| | CONSTRUCTION OF NEW 400 ROOM HOTEL INCLUDING BALLROOMS, |
| | RESTAURANT(S), MEETING SPACE, POOL DECK AND AMENITIES |
| | |
| | 3RD REVIEW |
| | DATE: TUESDAY AUGUST 19/ 2014 |
| | |
| | ACTION: PLUMBING PROVISO |
| | |
| | FUEL GAS: THIS REVIEW IS UNDER A SEPARATE PLAN REVIEW |
| | STOP, SEE FOR STATUS AND COMMENTS. |
| | |
| | 1) 2ND REQUEST: THE ASSOCIATES CAFETERIA PLUMBING PLAN |
| | LIST EQUIPMENT AND PLUMBING FIXTURES WITH A C-LABEL. |
| | THE PLUMBING INDEX LIST SHEET P2.01 AS THE BANQUET |
| | KITCHEN & ASSO. CAFE SCHEDULE, THERE ARE NO C EQUIPMENT |
| | ON SHEET P2.01, THIS LIST ALL FIXTURES & EQUIPMENT ON |
| | THIS SHEET ARE LISTED WITH A Q. I CAN'T IDENTIFY THE |
| | TYPE OF EQUIPMENT FOR THE TYPE OR WASTE REQUIRED. NOTE |
| | # 10 REFERS TO GREASY WASTE FOR THIS SHEET BUT NOT |
| | IDENTIFIED ON THE PLAN. |
| | |
| | 2) SHEET P1.02 LEVEL 1 AREA Q2, NOTE# 21 INDICATES A |
| | NEW 750 GALLON CONCRETE VAULT TYPE GREASE INTERCEPTOR, |
| | NOTE 36 SEE SHEET P3.01D FOR THE CONTINUATION OF GREASY |
| | WASTE. PLEASE PROVIDE THE SIZING CALCULATIONS FOR THE |
| | CONCRETE VAULT TYPE GREASE INTERCEPTOR, SIZING IS TO BE |
| | IN ACCORDANCE WITH 2010 FBC-P SECTION 1003.5.1 AND |
| | TABLE 1003.5.1. |
| | |
| | 3) SHEET P1.03 LEVEL 1 AREA Q3. SHEET P1.03 LEVEL 1 |
| | AREA Q3, NOTE# 01 INDICATES A NEW 1,250 GALLON CONCRETE |
| | VAULT TYPE GREASE INTERCEPTOR, NOTE REFERS TO SHEET |
| | P4.03 THE GREASE INTERCEPTOR DETAIL. SHEET P3.00 |
| | INDICATES 132 FU DRAINING INTO THE GREASE INTERCEPTOR. |
| | IF SIZING USING TABLE 1003.3.4.1 THIS TABLE IS TO BE |
| | USED WHEN THE DESIGN IS FOR HYDRO MECHANICAL GREASE |
| | INTERCEPTORS. PLEASE PROVIDE THE SIZING CALCULATIONS |
| | FOR THE CONCRETE VAULT TYPE GREASE INTERCEPTOR, SIZING |
| | IS TO BE IN ACCORDANCE WITH 2010 FBC-P SECTION 1003.5.1 |
| | AND TABLE 1003.5.1. |
| | |
| | THE CITY FOG INSPECTORS (FATS, OILS & GREASE) MONITOR |
| | ALL GREASE INTERCEPTORS TO VERIFY COMPLIANCE WITH THE |
| | CITY?S MUNI CODE SEC. 90-126. PROHIBITIONS AND |
| | LIMITATIONS OF DISCHARGE.(7) MINERAL OIL IN EXCESS OF |
| | 50 MG/L OR ANIMAL/VEGETABLE FATS, WAX, GREASE, OR OILS |
| | IN EXCESS OF 100 MG/L, WHETHER EMULSIFIED OR NOT; OR |
| | SUBSTANCES WHICH MAY SOLIDIFY OR BECOME VISCOUS AT |
| | TEMPERATURES LOWER THAN OR EQUAL TO 150 DEGREES |
| | FAHRENHEIT (65.56 DEGREES CELSIUS). |
| | |
| | 4) SHEET P1.04 LEVEL 1 AREA Q4. KITCHEN 105 , NO GREASY |
| | WASTE IS SHOWN ON THE PLANS, NOTE # 15 INDICATES SEE |
| | P2.04 FOR CONTINUATION. THIS SHEET IS A EQUIPMENT |
| | SCHEDULE, PLEASE PROVIDE A GREASY WASTE ISOMETRIC OR |
| | WHERE TO LOCATE SUCH PLANS. PLEASE PROVIDE THE SIZING |
| | CALCULATIONS FOR THE CONCRETE VAULT TYPE GREASE |
| | INTERCEPTOR, SIZING IS TO BE IN ACCORDANCE WITH 2010 |
| | FBC-P SECTION 1003.5.1 AND TABLE 1003.5.1. |
| | |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |