| 2014-08-19 15:12:03 | FUEL GAS PLAN REVIEW |
| | PERMIT:14050111 |
| | ADD: 600 OKEECHOBEE BLVD |
| | CONT: COASTAL CONSTRUCTION |
| | TEL: (561) 630-3770 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | THE PALM BEACH CONVENTION CENTER HILTON HOTEL |
| | CONSTRUCTION OF NEW 400 ROOM HOTEL INCLUDING BALLROOMS, |
| | RESTAURANT(S), MEETING SPACE, POOL DECK AND AMENITIES |
| | |
| | 3RD REVIEW |
| | DATE: TUES. AUGUST 19/2014 |
| | |
| | ACTION: FUEL GAS PROVISO |
| | |
| | NOTE: FUEL GAS PERMITS ARE A SEPARATE PERMIT AND FEES, |
| | THE REVIEW WILL BE COMPLETED UNDER THE MASTER SET OF |
| | PLANS NO OTHER PLANS REQUIRED. |
| | |
| | 1) SHEET P3.02 THERE ARE (3) AREAS OF CONCERN, THE PIPE |
| | SIZING IS CORRECT, THERE SEEMS TO BE A DISCREPANCY IN |
| | THE BTU LOADS: |
| | |
| | 1A) PLEASE VIEW KEY NOTES 6 & 7, LAUNDRY & KITCHEN |
| | BOILERS INDICATES A TOTAL OF (5) BOILERS WHERE AS |
| | DEPICTED ONLY THE KITCHEN BOILERS ARE SHOWN. NO BOILERS |
| | # 6 ARE SHOWN ON THE PLAN. THE TOTAL LOAD FOR THESE |
| | BOILERS IS SHOWN AS 1,195,000 BTU LOAD, TYPO SHOULD BE |
| | 1,995,000. PLEASE NOTE THE COMBINED LOADS OF THE |
| | KITCHEN/ LAUNDRY BOILERS AND THE POOL(NOTE 8) AND SPA |
| | (NOTE 9) IS CORRECT AT 3,995,000 BTU. 2010 FUEL GAS |
| | CODE SECTIONS BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS |
| | SECS. 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(35) |
| | |
| | 1B) PLEASE VIEW KEY NOTES 6 & 7, LAUNDRY & KITCHEN |
| | BOILERS INDICATES A TOTAL OF (5) BOILERS WHERE AS |
| | DEPICTED ONLY THE KITCHEN BOILERS ARE SHOWN. NO BOILERS |
| | # 6 ARE SHOWN ON THE PLAN. THE OTAL LOAD FOR THESE |
| | BOILERS IS SHOWN AS 1,195,000 BTU LOAD, TYPO SHOULD BE |
| | 1,995,000. PLEASE NOTE THE COMBINED LOADS OF THE |
| | KITCHEN/ LAUNDRY BOILERS AND THE POOL(NOTE 8) AND SPA |
| | (NOTE 9) IS CORRECT AT 3,995,000 BTU. 2010 FUEL GAS |
| | CODE SECTIONS BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS |
| | SECS. 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(35) |
| | |
| | 1C) THE (3RD) AREA OF INTEREST IS THE RESTAURANT |
| | KITCHEN, IN TOTALING UP ALL THE TOTAL BTU LOADS FOR THE |
| | KITCHEN I COME UP WITH 922,000 BTU'S PLEASE RECHECK THE |
| | TOTAL LOADS, 107.2.1.3 ADDITIONAL INFORMATION, |
| | DISCREPANCY IN PLANS IN THIS AREA. NOTE THIS WILL |
| | INCREASE THE TOTAL BTU LOAD FOR THE SYSTEM, BUT NOT |
| | AFFECT THE PIPE SIZING. |
| | |
| | 2) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.4.2 |
| | DEFERRED SUBMITTALS. |
| | THIS ITEM CAN BE A DEFERRED SUBMITTAL BUT WILL BE |
| | REQUIRED TO VARIFY NOT OVER LOADING THE CAPACITY OF THE |
| | FUEL GAS SYSTEM AND FOR SIZING. SUBMIT MANUFACTURE |
| | SHEETS FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND FBC-2010 FUEL GAS SEC. |
| | 402.2 |
| | |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |