2014-08-19 15:12:03FUEL GAS PLAN REVIEW
 PERMIT:14050111
 ADD: 600 OKEECHOBEE BLVD
 CONT: COASTAL CONSTRUCTION
 TEL: (561) 630-3770
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 THE PALM BEACH CONVENTION CENTER HILTON HOTEL
 CONSTRUCTION OF NEW 400 ROOM HOTEL INCLUDING BALLROOMS,
 RESTAURANT(S), MEETING SPACE, POOL DECK AND AMENITIES
  
 3RD REVIEW
 DATE: TUES. AUGUST 19/2014
  
 ACTION: FUEL GAS PROVISO
  
 NOTE: FUEL GAS PERMITS ARE A SEPARATE PERMIT AND FEES,
 THE REVIEW WILL BE COMPLETED UNDER THE MASTER SET OF
 PLANS NO OTHER PLANS REQUIRED.
  
 1) SHEET P3.02 THERE ARE (3) AREAS OF CONCERN, THE PIPE
 SIZING IS CORRECT, THERE SEEMS TO BE A DISCREPANCY IN
 THE BTU LOADS:
  
 1A) PLEASE VIEW KEY NOTES 6 & 7, LAUNDRY & KITCHEN
 BOILERS INDICATES A TOTAL OF (5) BOILERS WHERE AS
 DEPICTED ONLY THE KITCHEN BOILERS ARE SHOWN. NO BOILERS
 # 6 ARE SHOWN ON THE PLAN. THE TOTAL LOAD FOR THESE
 BOILERS IS SHOWN AS 1,195,000 BTU LOAD, TYPO SHOULD BE
 1,995,000. PLEASE NOTE THE COMBINED LOADS OF THE
 KITCHEN/ LAUNDRY BOILERS AND THE POOL(NOTE 8) AND SPA
 (NOTE 9) IS CORRECT AT 3,995,000 BTU. 2010 FUEL GAS
 CODE SECTIONS BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS
 SECS. 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(35)
  
 1B) PLEASE VIEW KEY NOTES 6 & 7, LAUNDRY & KITCHEN
 BOILERS INDICATES A TOTAL OF (5) BOILERS WHERE AS
 DEPICTED ONLY THE KITCHEN BOILERS ARE SHOWN. NO BOILERS
 # 6 ARE SHOWN ON THE PLAN. THE OTAL LOAD FOR THESE
 BOILERS IS SHOWN AS 1,195,000 BTU LOAD, TYPO SHOULD BE
 1,995,000. PLEASE NOTE THE COMBINED LOADS OF THE
 KITCHEN/ LAUNDRY BOILERS AND THE POOL(NOTE 8) AND SPA
 (NOTE 9) IS CORRECT AT 3,995,000 BTU. 2010 FUEL GAS
 CODE SECTIONS BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS
 SECS. 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(35)
  
 1C) THE (3RD) AREA OF INTEREST IS THE RESTAURANT
 KITCHEN, IN TOTALING UP ALL THE TOTAL BTU LOADS FOR THE
 KITCHEN I COME UP WITH 922,000 BTU'S PLEASE RECHECK THE
 TOTAL LOADS, 107.2.1.3 ADDITIONAL INFORMATION,
 DISCREPANCY IN PLANS IN THIS AREA. NOTE THIS WILL
 INCREASE THE TOTAL BTU LOAD FOR THE SYSTEM, BUT NOT
 AFFECT THE PIPE SIZING.
  
 2) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.4.2
 DEFERRED SUBMITTALS.
 THIS ITEM CAN BE A DEFERRED SUBMITTAL BUT WILL BE
 REQUIRED TO VARIFY NOT OVER LOADING THE CAPACITY OF THE
 FUEL GAS SYSTEM AND FOR SIZING. SUBMIT MANUFACTURE
 SHEETS FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2010 FUEL GAS SEC.
 402.2
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715