| 2014-08-19 16:30:12 | BUILDING PLAN REVIEW |
| | PERMIT:14050111 |
| | ADD: 600 OKEECHOBEE BLVD |
| | CONT: COASTAL CONSTRUCTION |
| | TEL: (561) 630-3770 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | THE PALM BEACH CONVENTION CENTER HILTON HOTEL |
| | CONSTRUCTION OF NEW 400 ROOM HOTEL INCLUDING BALLROOMS, |
| | RESTAURANT(S), MEETING SPACE, POOL DECK AND AMENITIES |
| | |
| | 3RD REVIEW |
| | DATE: TUES. AUGUST 19/ 2014 |
| | |
| | ACTION:BUILDING PROVISO |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) THE PERMIT DESCRIPTION LISTED ABOVE TO BUILD THE |
| | HOTEL, POOL, POOL DECK & AMENITIES IS A INCLUSIVE |
| | PACKAGE WITHIN THE SUBMITTED PLANS. THERE ARE CIVIL, |
| | SITE, LANDSCAPING, IRRIGATION, GREASE INTERCEPTORS, |
| | FUEL GAS, GENERATOR, FIRE SPRINKLER, FIRE ALARM, |
| | LOWVOLTAGE, AWNINGS AND SIGNAGE PLANS WITHIN THE |
| | SUBMITTED DOCUMENTS. |
| | THESE TYPE OF ACTIVITIES REQUIRE A SEPARATE PERMIT |
| | APPLICATION, REVIEW AND ASSOCIATED FEES. PLEASE BACK |
| | OUT THE VALUE OF WORK TO BE COMPLETED UNDER EACH OF |
| | THESE PERMITS SO THE BUILDING DEPARTMENT DOES NOT |
| | CHARGE YOU TWICE FOR THESE SERVICES. 2010 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION 105.1 PERMITS |
| | |
| | 2) 0211-A2.01/ BASEMENT LEVEL: REVISION IS REQUIRED. |
| | THE FIRST COMMENT ASKED WHY THER WAS STORAGE BINS IN |
| | THE CORRIDOR, THE RESPONSE INDICATES THESE ARE SOILED |
| | LAUNDRY BINS. |
| | SOILED LAUNDRY IS CONSIDERED AN INCIDENTIAL ACCESSORY |
| | OCCUPANY IN ITSELF, AND IS TO BE SEPARATE WITHIN A |
| | ROOM, NOT IN A EXIT ACCESS COORIDOR, |
| | SEE THE 2010 FBC-B TABLE 508.2.5. IT STATES THAT |
| | LAUNDRY ROOMS ARE TO BE SEPARATED BY 1 HR ROOM OR |
| | PROVIDE FIRE SPRINKLERS. PLEASE REVIEW 508.2.5.2 |
| | NONFIRE-RESISTANCE-RATED SEPARATION AND PROTECTION. |
| | WHERE TABLE 508.2.5 PERMITS AN AUTOMATIC |
| | FIRE-EXTINGUISHING SYSTEM WITHOUT A FIRE BARRIER, THE |
| | INCIDENTAL ACCESSORY OCCUPANCIES SHALL BE SEPARATED |
| | FROM THE REMAINDER OF THE BUILDING BY CONSTRUCTION |
| | CAPABLE OF RESISTING THE PASSAGE OF SMOKE. THE WALLS |
| | SHALL EXTEND FROM THE TOP OF THE FOUNDATION OR FLOOR |
| | ASSEMBLY BELOW TO THE UNDERSIDE OF THE CEILING THAT IS |
| | A COMPONENT OF A FIRE-RESISTANCE-RATED FLOOR ASSEMBLY |
| | OR ROOF ASSEMBLY ABOVE OR TO THE UNDERSIDE OF THE FLOOR |
| | OR ROOF SHEATHING, DECK OR SLAB ABOVE. DOORS SHALL BE |
| | SELF- OR AUTOMATIC-CLOSING UPON DETECTION OF SMOKE IN |
| | ACCORDANCE WITH SECTION 715.4.8.3. DOORS SHALL NOT HAVE |
| | AIR TRANSFER OPENINGS AND SHALL NOT BE UNDERCUT IN |
| | EXCESS OF THE CLEARANCE PERMITTED IN ACCORDANCE WITH |
| | NFPA 80. WALLS SURROUNDING THE INCIDENTAL ACCESSORY |
| | OCCUPANCY SHALL NOT HAVE AIR TRANSFER OPENINGS UNLESS |
| | PROVIDED WITH SMOKE DAMPERS IN ACCORDANCE WITH SECTION |
| | 711.7. |
| | |
| | 3) COMPLIED ,LULA LIFT. |
| | |
| | 4A) NEW COMMENT/ SEMI NEW, NEW LOCATION, THE EXECUTIVE |
| | LOUNGE HAS BEEN MOVED TO ROOM # 207 THE COMMENTS STILL |
| | EXIST. THE EXECUTIVE LOUNGE HAS A OCCUPANT LOAD OF 73 |
| | THIS IS AN ASSEMBLY OCCUPANCY PLEASE PROVIDE A |
| | FURNATURE LATOUT. SHEET A3.00 DOES NOT INCLUDE THIS |
| | ROOM IN THE PLUMBING FIXTURE COUNT. DEPENDING ON THE |
| | USAGE THIS MAY BE CONSIDERED EIHER AN A2 OR A3, IF |
| | CONSIDERED MORE AS A LOUNGE A-2 THE WATER CLOSET RATIO |
| | WILL BE 1/40 REQUIRING ADDITIONAL FIXTURES. |
| | |
| | 4B) ROOM 207 THE EXECUTIVE LOUNGE, THERE IS A SMALL |
| | ROOM THAT NO INFORMATION HAS BEEN PROVIDED, IS THIS FOR |
| | STORAGE, BAR OR KITCHEN TO BE USED IN CONJUNCTION WITH |
| | THE LOUNGE? FBC-B 302.1. NOTE FBC-B 1014.2 EGRESS |
| | THROUGH INTERVENING SPACES. 4. EGRESS SHALL NOT PASS |
| | THROUGH KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES USED |
| | FOR SIMILAR PURPOSES. |
| | |
| | 5) SHEET A4.20 SECTION THRU BUILDING A12.10 : 2010 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION |
| | SHOW COMPLIANCE NOTES ON PLANS QUATING CODE DOES NOT |
| | MEAN COMPLIED. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS SUCH INFORMATION SHALL BE SPECIFIC, AND THE |
| | TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN |
| | PART, NOR SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE |
| | USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION. |
| | 16A NOTES ON THE PLANS INDICATES THE USE OF ALUMINUM |
| | COMPOSITE WALL PANELS, PLEASE PROVIDE DOCUMENTATION FOR |
| | CODE COMPLIANCE WITH: 2010 FBC-B 1407.2 EXTERIOR WALL |
| | FINISH. |
| | MCM USED AS EXTERIOR WALL FINISH OR AS ELEMENTS OF |
| | BALCONIES AND SIMILAR PROJECTIONS AND BAY AND ORIEL |
| | WINDOWS TO PROVIDE CLADDING OR WEATHER RESISTANCE SHALL |
| | COMPLY WITH SECTIONS 1407.4 THROUGH 1407.14. |
| | |
| | 6) DEFFERED SUBMITTAL; A12.10 DETAILS 1 & 8 BOTH |
| | INDICATE THE PERIMETER SUN SCREEN , DETAIL 3 A12.09 |
| | ALSO A CLOSE UP OF THE PERIMETER SUNSCREEN INDICATE THE |
| | USE OF STEEL EMBEDS W/ NELSON BOLTS PER THE |
| | MANUFACTURERS REQUIREMENTS. PLEASE PROVIDE ENGINEERING |
| | FOR THIS SYSTEM THAT THE DESIGN AND ATTACHMENTS WILL |
| | MEET THE WINDLOADS AND HEIGHT ADJUSTMENT FACTORS FOR |
| | THIS ELEVATION, TO BE DESIGNED TO ASCE 7-10 .1609.1.1 |
| | DETERMINATION OF WIND LOADS. WIND LOADS ON EVERY |
| | BUILDING OR STRUCTURE SHALL BE DETERMINED IN ACCORDANCE |
| | WITH CHAPTERS 26 THROUGH 30 OF ASCE 7 OR THE PROVISIONS |
| | OF THE ALTERNATE ALL HEIGHTS METHOD IN SECTION 1609.6. |
| | L |
| | |
| | 7) THE FPL VAULT REQUIRES 3 HR WALLS 2008 NEC THE DOORS |
| | ALSO REQUIRE A 3 HR RATING PER 2008 NEC 450.43(A) & |
| | 2010 FBC-B TABLE 715.4. |
| | |
| | |
| | 8) PLEASE CLARIFY: MICHAEL STELLINO & I HAVE SPOKEN ON |
| | THIS SUBJECT. WHAT APPEARS TO BE A LINEN CHUTE DOOR IS |
| | SUPPOSE TO BE A RECESSED FIRE EXTINGUISHER CABINET. |
| | PLEASE CLARIFY. THE RESPONSE INDICATES THAT THE LINEN |
| | CHUTE DOOR IS IDENTIFIED AS T26. PLEASE REVIEW THE DOOR |
| | SCHEDULE ON A14.01, T26 IS FOR THE ICE ROOM NEXT TO THE |
| | LAUNDRY CHUTE, THAT DOES NOT HAVE ANY DOOR, NOR IS THE |
| | ARK OF A DOOR INDICATED ON THE PLANS. |
| | |
| | SHEET A2.10 SHOWS THE LAUNDRY CHUTE LOCATED ON THE GRID |
| | LINES X.1 JUST NORTH & Y.2 CENTERED ON THE GRID LINE |
| | WHICH IS LOCATED IN THE MAIDS ROOM.FLOORS 10-12 SEE |
| | SHEET A2.11 THE LAUBDRY CHUTE IS OFFSET TO THE |
| | NORTHEAST OR TO THE EAST OF GRID LINE Y.2 . THE PLANS |
| | SHOW THE ACCESS TO THE ACCESS CHUTE DOOR LOCATED WITH |
| | THE CORRADOR. PLEASE CONFORM WITH: |
| | |
| | 2010 FBC-B 708.13.3 REFUSE AND LAUNDRY CHUTE ACCESS |
| | ROOMS. |
| | ACCESS OPENINGS FOR REFUSE AND LAUNDRY CHUTES SHALL BE |
| | LOCATED IN ROOMS OR COMPARTMENTS ENCLOSED BY NOT LESS |
| | THAN 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE |
| | WITH SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED |
| | IN ACCORDANCE WITH SECTION 712, OR BOTH. OPENINGS INTO |
| | THE ACCESS ROOMS SHALL BE PROTECTED BY OPENING |
| | PROTECTIVES HAVING A FIRE PROTECTION RATING OF NOT LESS |
| | THAN 3/4 HOUR. DOORS SHALL BE SELF- OR |
| | AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE IN |
| | ACCORDANCE WITH SECTION 715.4.8.3. |
| | |
| | 8B) . SHEET A12.16 SHOWS A NEW DETAIL WITH A FIRE RISER |
| | WITHIN THE 2 HR FIRE RATED CHASE BUT THE SPRINKLER HEAD |
| | DOES NOT PENETRATE INTO THE THE LINEN CHUTE NOR DOES |
| | THERE SHOW HOW THE SPRINKLER HEAD HAS ACCESSIBILITY FOR |
| | MAINTENANCE. |
| | SHEET A7.15 THE LINEN CHUTE DETAILS DO NOT MENTION THE |
| | REQUIREMENT OR ANY ALLOWANCES FOR FIRE SPRINKLERS IN |
| | THE LINEN CHUTE. THE FIRE SPRINKLER SHEETS ONLY PROVIDE |
| | A DEAIL ON FP0.01 INDICATING SERVICE CHUTE DETAIL. |
| | 708.13.6 AUTOMATIC SPRINKLER SYSTEM. |
| | AN APPROVED AUTOMATIC SPRINKLER SYSTEM SHALL BE |
| | INSTALLED IN ACCORDANCE WITH SECTION 903.2.11.2 F] |
| | 903.2.11.2 RUBBISH AND LINEN CHUTES. |
| | AN AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED AT THE |
| | TOP OF RUBBISH AND LINEN CHUTES AND IN THEIR TERMINAL |
| | ROOMS. CHUTES EXTENDING THROUGH THREE OR MORE FLOORS |
| | SHALL HAVE ADDITIONAL SPRINKLER HEADS INSTALLED WITHIN |
| | SUCH CHUTES AT ALTERNATE FLOORS. CHUTE SPRINKLERS SHALL |
| | BE ACCESSIBLE FOR SERVICING. |
| | |
| | THE LAUNDRY CHUTE DETAIL SHEET ALSO DOESN'T MAKE |
| | REFERANCE TO THE REQUIREMENT FOR CHUTE SPRINKLERS SHALL |
| | BE ACCESSIBLE FOR SERVICING THIS MAY BE A ISSUE WHERE |
| | THE RECESSED FIRE EXTINGUISHER BOXES ARE LOCATED ON THE |
| | 10-12TH FLOORS IN FRONT OF THE LAUNDRY CHUTE. |
| | |
| | 9A) DEFERRED SUBMITTAL UNDER 107.3.4.2 BUT THE |
| | PRESSURES HAVE TO BE INALLIZED BEFORE PERMIT ISSUANCE. |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 9B) DEFERRED SUBMITTAL UNDER 107.3.4.2. 2010 FBC |
| | 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 |
| | (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND |
| | REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS |
| | ETC.. |
| | |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |