Plan Review Notes
Plan Review Notes For Permit 14050111
Permit Number 14050111
Review Stop B
Sequence Number 3
Notes
Date Text
2014-08-19 16:30:12BUILDING PLAN REVIEW
 PERMIT:14050111
 ADD: 600 OKEECHOBEE BLVD
 CONT: COASTAL CONSTRUCTION
 TEL: (561) 630-3770
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 THE PALM BEACH CONVENTION CENTER HILTON HOTEL
 CONSTRUCTION OF NEW 400 ROOM HOTEL INCLUDING BALLROOMS,
 RESTAURANT(S), MEETING SPACE, POOL DECK AND AMENITIES
  
 3RD REVIEW
 DATE: TUES. AUGUST 19/ 2014
  
 ACTION:BUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) THE PERMIT DESCRIPTION LISTED ABOVE TO BUILD THE
 HOTEL, POOL, POOL DECK & AMENITIES IS A INCLUSIVE
 PACKAGE WITHIN THE SUBMITTED PLANS. THERE ARE CIVIL,
 SITE, LANDSCAPING, IRRIGATION, GREASE INTERCEPTORS,
 FUEL GAS, GENERATOR, FIRE SPRINKLER, FIRE ALARM,
 LOWVOLTAGE, AWNINGS AND SIGNAGE PLANS WITHIN THE
 SUBMITTED DOCUMENTS.
 THESE TYPE OF ACTIVITIES REQUIRE A SEPARATE PERMIT
 APPLICATION, REVIEW AND ASSOCIATED FEES. PLEASE BACK
 OUT THE VALUE OF WORK TO BE COMPLETED UNDER EACH OF
 THESE PERMITS SO THE BUILDING DEPARTMENT DOES NOT
 CHARGE YOU TWICE FOR THESE SERVICES. 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 105.1 PERMITS
  
 2) 0211-A2.01/ BASEMENT LEVEL: REVISION IS REQUIRED.
 THE FIRST COMMENT ASKED WHY THER WAS STORAGE BINS IN
 THE CORRIDOR, THE RESPONSE INDICATES THESE ARE SOILED
 LAUNDRY BINS.
 SOILED LAUNDRY IS CONSIDERED AN INCIDENTIAL ACCESSORY
 OCCUPANY IN ITSELF, AND IS TO BE SEPARATE WITHIN A
 ROOM, NOT IN A EXIT ACCESS COORIDOR,
 SEE THE 2010 FBC-B TABLE 508.2.5. IT STATES THAT
 LAUNDRY ROOMS ARE TO BE SEPARATED BY 1 HR ROOM OR
 PROVIDE FIRE SPRINKLERS. PLEASE REVIEW 508.2.5.2
 NONFIRE-RESISTANCE-RATED SEPARATION AND PROTECTION.
 WHERE TABLE 508.2.5 PERMITS AN AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM WITHOUT A FIRE BARRIER, THE
 INCIDENTAL ACCESSORY OCCUPANCIES SHALL BE SEPARATED
 FROM THE REMAINDER OF THE BUILDING BY CONSTRUCTION
 CAPABLE OF RESISTING THE PASSAGE OF SMOKE. THE WALLS
 SHALL EXTEND FROM THE TOP OF THE FOUNDATION OR FLOOR
 ASSEMBLY BELOW TO THE UNDERSIDE OF THE CEILING THAT IS
 A COMPONENT OF A FIRE-RESISTANCE-RATED FLOOR ASSEMBLY
 OR ROOF ASSEMBLY ABOVE OR TO THE UNDERSIDE OF THE FLOOR
 OR ROOF SHEATHING, DECK OR SLAB ABOVE. DOORS SHALL BE
 SELF- OR AUTOMATIC-CLOSING UPON DETECTION OF SMOKE IN
 ACCORDANCE WITH SECTION 715.4.8.3. DOORS SHALL NOT HAVE
 AIR TRANSFER OPENINGS AND SHALL NOT BE UNDERCUT IN
 EXCESS OF THE CLEARANCE PERMITTED IN ACCORDANCE WITH
 NFPA 80. WALLS SURROUNDING THE INCIDENTAL ACCESSORY
 OCCUPANCY SHALL NOT HAVE AIR TRANSFER OPENINGS UNLESS
 PROVIDED WITH SMOKE DAMPERS IN ACCORDANCE WITH SECTION
 711.7.
  
 3) COMPLIED ,LULA LIFT.
  
 4A) NEW COMMENT/ SEMI NEW, NEW LOCATION, THE EXECUTIVE
 LOUNGE HAS BEEN MOVED TO ROOM # 207 THE COMMENTS STILL
 EXIST. THE EXECUTIVE LOUNGE HAS A OCCUPANT LOAD OF 73
 THIS IS AN ASSEMBLY OCCUPANCY PLEASE PROVIDE A
 FURNATURE LATOUT. SHEET A3.00 DOES NOT INCLUDE THIS
 ROOM IN THE PLUMBING FIXTURE COUNT. DEPENDING ON THE
 USAGE THIS MAY BE CONSIDERED EIHER AN A2 OR A3, IF
 CONSIDERED MORE AS A LOUNGE A-2 THE WATER CLOSET RATIO
 WILL BE 1/40 REQUIRING ADDITIONAL FIXTURES.
  
 4B) ROOM 207 THE EXECUTIVE LOUNGE, THERE IS A SMALL
 ROOM THAT NO INFORMATION HAS BEEN PROVIDED, IS THIS FOR
 STORAGE, BAR OR KITCHEN TO BE USED IN CONJUNCTION WITH
 THE LOUNGE? FBC-B 302.1. NOTE FBC-B 1014.2 EGRESS
 THROUGH INTERVENING SPACES. 4. EGRESS SHALL NOT PASS
 THROUGH KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES USED
 FOR SIMILAR PURPOSES.
  
 5) SHEET A4.20 SECTION THRU BUILDING A12.10 : 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION
 SHOW COMPLIANCE NOTES ON PLANS QUATING CODE DOES NOT
 MEAN COMPLIED. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS SUCH INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE
 USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION.
 16A NOTES ON THE PLANS INDICATES THE USE OF ALUMINUM
 COMPOSITE WALL PANELS, PLEASE PROVIDE DOCUMENTATION FOR
 CODE COMPLIANCE WITH: 2010 FBC-B 1407.2 EXTERIOR WALL
 FINISH.
 MCM USED AS EXTERIOR WALL FINISH OR AS ELEMENTS OF
 BALCONIES AND SIMILAR PROJECTIONS AND BAY AND ORIEL
 WINDOWS TO PROVIDE CLADDING OR WEATHER RESISTANCE SHALL
 COMPLY WITH SECTIONS 1407.4 THROUGH 1407.14.
  
 6) DEFFERED SUBMITTAL; A12.10 DETAILS 1 & 8 BOTH
 INDICATE THE PERIMETER SUN SCREEN , DETAIL 3 A12.09
 ALSO A CLOSE UP OF THE PERIMETER SUNSCREEN INDICATE THE
 USE OF STEEL EMBEDS W/ NELSON BOLTS PER THE
 MANUFACTURERS REQUIREMENTS. PLEASE PROVIDE ENGINEERING
 FOR THIS SYSTEM THAT THE DESIGN AND ATTACHMENTS WILL
 MEET THE WINDLOADS AND HEIGHT ADJUSTMENT FACTORS FOR
 THIS ELEVATION, TO BE DESIGNED TO ASCE 7-10 .1609.1.1
 DETERMINATION OF WIND LOADS. WIND LOADS ON EVERY
 BUILDING OR STRUCTURE SHALL BE DETERMINED IN ACCORDANCE
 WITH CHAPTERS 26 THROUGH 30 OF ASCE 7 OR THE PROVISIONS
 OF THE ALTERNATE ALL HEIGHTS METHOD IN SECTION 1609.6.
 L
  
 7) THE FPL VAULT REQUIRES 3 HR WALLS 2008 NEC THE DOORS
 ALSO REQUIRE A 3 HR RATING PER 2008 NEC 450.43(A) &
 2010 FBC-B TABLE 715.4.
  
  
 8) PLEASE CLARIFY: MICHAEL STELLINO & I HAVE SPOKEN ON
 THIS SUBJECT. WHAT APPEARS TO BE A LINEN CHUTE DOOR IS
 SUPPOSE TO BE A RECESSED FIRE EXTINGUISHER CABINET.
 PLEASE CLARIFY. THE RESPONSE INDICATES THAT THE LINEN
 CHUTE DOOR IS IDENTIFIED AS T26. PLEASE REVIEW THE DOOR
 SCHEDULE ON A14.01, T26 IS FOR THE ICE ROOM NEXT TO THE
 LAUNDRY CHUTE, THAT DOES NOT HAVE ANY DOOR, NOR IS THE
 ARK OF A DOOR INDICATED ON THE PLANS.
  
 SHEET A2.10 SHOWS THE LAUNDRY CHUTE LOCATED ON THE GRID
 LINES X.1 JUST NORTH & Y.2 CENTERED ON THE GRID LINE
 WHICH IS LOCATED IN THE MAIDS ROOM.FLOORS 10-12 SEE
 SHEET A2.11 THE LAUBDRY CHUTE IS OFFSET TO THE
 NORTHEAST OR TO THE EAST OF GRID LINE Y.2 . THE PLANS
 SHOW THE ACCESS TO THE ACCESS CHUTE DOOR LOCATED WITH
 THE CORRADOR. PLEASE CONFORM WITH:
  
 2010 FBC-B 708.13.3 REFUSE AND LAUNDRY CHUTE ACCESS
 ROOMS.
 ACCESS OPENINGS FOR REFUSE AND LAUNDRY CHUTES SHALL BE
 LOCATED IN ROOMS OR COMPARTMENTS ENCLOSED BY NOT LESS
 THAN 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE
 WITH SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED
 IN ACCORDANCE WITH SECTION 712, OR BOTH. OPENINGS INTO
 THE ACCESS ROOMS SHALL BE PROTECTED BY OPENING
 PROTECTIVES HAVING A FIRE PROTECTION RATING OF NOT LESS
 THAN 3/4 HOUR. DOORS SHALL BE SELF- OR
 AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE IN
 ACCORDANCE WITH SECTION 715.4.8.3.
  
 8B) . SHEET A12.16 SHOWS A NEW DETAIL WITH A FIRE RISER
 WITHIN THE 2 HR FIRE RATED CHASE BUT THE SPRINKLER HEAD
 DOES NOT PENETRATE INTO THE THE LINEN CHUTE NOR DOES
 THERE SHOW HOW THE SPRINKLER HEAD HAS ACCESSIBILITY FOR
 MAINTENANCE.
 SHEET A7.15 THE LINEN CHUTE DETAILS DO NOT MENTION THE
 REQUIREMENT OR ANY ALLOWANCES FOR FIRE SPRINKLERS IN
 THE LINEN CHUTE. THE FIRE SPRINKLER SHEETS ONLY PROVIDE
 A DEAIL ON FP0.01 INDICATING SERVICE CHUTE DETAIL.
 708.13.6 AUTOMATIC SPRINKLER SYSTEM.
 AN APPROVED AUTOMATIC SPRINKLER SYSTEM SHALL BE
 INSTALLED IN ACCORDANCE WITH SECTION 903.2.11.2 F]
 903.2.11.2 RUBBISH AND LINEN CHUTES.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED AT THE
 TOP OF RUBBISH AND LINEN CHUTES AND IN THEIR TERMINAL
 ROOMS. CHUTES EXTENDING THROUGH THREE OR MORE FLOORS
 SHALL HAVE ADDITIONAL SPRINKLER HEADS INSTALLED WITHIN
 SUCH CHUTES AT ALTERNATE FLOORS. CHUTE SPRINKLERS SHALL
 BE ACCESSIBLE FOR SERVICING.
  
 THE LAUNDRY CHUTE DETAIL SHEET ALSO DOESN'T MAKE
 REFERANCE TO THE REQUIREMENT FOR CHUTE SPRINKLERS SHALL
 BE ACCESSIBLE FOR SERVICING THIS MAY BE A ISSUE WHERE
 THE RECESSED FIRE EXTINGUISHER BOXES ARE LOCATED ON THE
 10-12TH FLOORS IN FRONT OF THE LAUNDRY CHUTE.
  
 9A) DEFERRED SUBMITTAL UNDER 107.3.4.2 BUT THE
 PRESSURES HAVE TO BE INALLIZED BEFORE PERMIT ISSUANCE.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 9B) DEFERRED SUBMITTAL UNDER 107.3.4.2. 2010 FBC
 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015
 (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND
 REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS
 ETC..
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  