Plan Review Notes
Plan Review Notes For Permit 14050111
Permit Number 14050111
Review Stop Z
Sequence Number 2
Notes
Date Text
2014-08-04 08:03:53FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO THE COMMENTS.
  
 1) THE FOLLOWING CONDITION WAS LISTED IN RESOLUTION NO.
 329-13 AS REQUIRED PRIOR TO THE ISSUANCE OF THE FIRST
 BUILDING PERMIT IN ORDER TO ADDRESS PERMANENT
 CONSTRUCTION ACROSS THE PROPERTY LINE. THE BUILDING
 OFFICIAL HAS DETERMINED THAT THE CURRENT TEMPORARY
 CONSTRUCTION EASEMENT WILL SUFFICE FOR BUILDING PERMIT
 TO BE ISSUED; HOWEVER, HE HAS STATED THAT THE PERMANENT
 INSTRUMENT SHALL BE RECORDED IN ACCORDANCE WITH THE
 CONDITION PRIOR TO ISSUANCE OF THE CO OR TCO, OR THE
 CONNECTOR BETWEEN THE HOTEL AND THE CONVENTION CENTER
 AND ANY OTHER STRUCTURES OR SYSTEMS THAT CROSS THE
 SHARED PROPERTY LINE SHALL BE REMOVED.
  
 A. PRIOR TO THE ISSUANCE OF THE SPECIFIC BUILDING
 PERMIT FOR STRUCTURES OR SYSTEMS THAT CROSS THE SHARED
 PROPERTY LINE WITH THE PALM BEACH COUNTY CONVENTION
 CENTER PARCEL, TO INCLUDE WALKWAY CONNECTIONS, THE
 POOL, POOL DECK, POOL EQUIPMENT, IRRIGATION LINES,
 ETC., THE APPLICANT SHALL RECORD IN THE PUBLIC RECORD A
 UNITY OF TITLE, UNITY OF CONTROL, A RESTRICTIVE
 COVENANT, IN LIEU OF UNITY OF TITLE, OR OTHER
 APPROPRIATE INSTRUMENT, AS APPROVED BY THE OFFICE OF
 THE CITY ATTORNEY, TO ADDRESS THE HOTEL STRUCTURES OR
 SYSTEMS THAT ARE ON THE CONVENTION CENTER PARCEL OR
 WHICH CROSS THE SHARED PROPERTY LINE.
  
 2) THE FOLLOWING CONDITIONS WERE LISTED IN RESOLUTION
 NO. 329-13 AS REQUIRED PRIOR TO THE ISSUANCE OF THE
 FIRST BUILDING PERMIT FOR VERTICAL CONSTRUCTION;
 HOWEVER, UPON ENGINEERING SERVICES DEPARTMENT AND CITY
 SURVEYOR REVIEW OF THE PROJECT AND RELATED PLANS, IT
 HAS BEEN DETERMINED THAT THESE CONDITIONS SHALL BE
 ADDRESSED PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF
 OCCUPANCY.
  
 A. RECORD EASEMENTS IN FAVOR OF THE CITY FOR ANY PUBLIC
 SIDEWALKS OR UTILITIES ON THE HOTEL OR PARKING
 STRUCTURE PARCELS. ****FINAL EASEMENT LOCATIONS WILL BE
 BASED ON THE AS BUILT SURVEY OF THE SITE.****
  
 B. SECURE A RIGHT-OF-WAY PERMIT FROM THE CITY FOR THE
 RECONFIGURATION OF THE MEDIANS AND INSTALLATION OF
 LANDSCAPE MATERIAL WITHIN THE FLORIDA AVENUE
 RIGHT-OF-WAY. AS PART OF THE RECONFIGURATION OF THE
 MEDIANS, THE APPLICANT SHALL INSTALL APPROPRIATE
 SIGNAGE TO WARN MOTORISTS OF THE MID-BLOCK PEDESTRIAN
 CROSSING ON FLORIDA AVENUE IN ACCORDANCE WITH THE
 LATEST VERSION OF THE MANUAL ON UNIFORM TRAFFIC CONTROL
 DEVICES (MUTCD). ****THE ENGINEERING SERVICES
 DEPARTMENT HAS DETERMINED THAT IT IS TOO PREMATURE TO
 ISSUE A RIGHT-OF-WAY PERMIT SINCE THE ACTUAL
 RIGHT-OF-WAY WORK IS NOT SET TO BEGIN UNTIL THE
 CONSTRUCTION IS FURTHER ALONG.****
  
 3) REPEAT COMMENT: LIGHTING SHALL BE PROVIDED FOR THE
 ART NICHES. WHILE A NOTE WAS ADDED TO THE ENLARGED
 ELEVATIONS REFERRING TO THE ELECTRICAL DRAWINGS FOR THE
 LIGHTING IN THE NICHES, THE REVIEWER IS UNABLE TO
 LOCATE THE LIGHTING ON THE ELECTRICAL DRAWINGS. PLEASE
 CLEARLY IDENTIFY ON WHAT SHEETS THE LIGHTING DETAILS
 ARE LOCATED.
  
 4) PARTIAL REPEAT COMMENT: THE FLOOR PLANS FAIL TO SHOW
 THE NEW GLAZING AND ARCHITECTURAL DETAILS ON THE
 SOUTHERN ELEVATION OF THE TOWER THAT WAS SHOWN ON THE
 MINOR AMENDMENT AND THE REVISED ELEVATIONS. EXAMPLE
 HALLWAY AND END ROOMS DO NOT HAVE WINDOWS.
  
 5) DATA ON SHEET A0.03 SHALL BE REVISED TO MATCH THE
 MINOR AMENDMENT DATA.
  
 6) SHEET A3.01 SHOWS DIFFERENT SQUARE FOOTAGE NUMBERS
 FOR THE PUBLIC AREAS (RESTAURANT, BAR, ETC.) THAT ON
 THE SUBMITTED MINOR AMENDMENT AND THE LIFE SAFETY PLAN
 (SHEET A2.02). ADDITIONALLY, NO SQUARE FOOTAGE IS
 PROVIDED FOR THE MARKET. THE NUMBERS SHALL BE SHOWS AND
 BE CONSISTENT AMONG ALL PLANS.
  
 7) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE
 FOLLOWING ITEMS. THE VALUE OF THE WORK SHALL BE
 SUBMITTED WITH EACH PERMIT AND NOT THE MAIN PERMIT.
 FULL ZONING REVIEW WILL OCCUR UPON SUBMITTAL OF THE
 SEPARATE PERMITS PLANS.
  
 A. SITE FURNITURE THAT WILL BE PERMANENTLY AFFIXED TO
 THE GROUND (EX. TRASH CANS, BENCHES, FIRE PIT, ETC.)
 STAFF HAS REVIEWED THE LOCATIONS OF THE SITE FURNITURE
 AND THEY COMPLY WITH THE APPROVED SITE PLAN.
 B. SITE LIGHTING
 C. BICYCLE RACKS
 D. ENTRY DRIVE - A RIGHT-OF-WAY PERMIT IS REQUIRED FOR
 THE CONNECTION TO FLORIDA AVENUE.
 E. CIVIL PLANS AND RIGHT-OF-WAY PERMIT (THROUGH
 ENGINEERING SERVICES)
 F. SIGNS - SEE COMMENT 10 FOR ADDITIONAL INFORMATION.
 G. POOL, SPA AND POOL DECK H
 H. FENCES/GATES - THE OVERALL HEIGHT OF THE
 FENCE/RETAINING WALL/COLUMNS MAY NOT EXCEED EIGHT (8)
 FEET IN HEIGHT WHEN MEASURED ON THE EXTERIOR SIDE
 (CONVENTION CENTER SIDE) FROM GRADE. DIMENSIONS WERE
 NOT PROVIDED.
 I. CABANAS, INCLUDING THE TOWEL ISSUE CABANA
 J. SUN SHADE
 K. FOUNTAIN WALL
 L. SIDEWALKS, COVERED WALKWAY AND OTHER ITEMS WHOLLY ON
 THE CONVENTION CENTER PARCEL.
 M. IRRIGATION PERMIT
  
 8) ADDITIONAL COMMENTS MAY BE GENERATED BASED ON THE
 RESUBMITTAL AND THE FULL ZONING REVIEW OF THE PLANS
 SUBMITTED WITH THE SEPARATE PERMITS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
  
  
  
2014-07-01 12:59:067/1/14 ZONING SENT TO ES. SG