Text |
| 2014-08-04 08:03:53 | FAILED |
| | |
| | PLEASE PROVIDE WRITTEN RESPONSES TO THE COMMENTS. |
| | |
| | 1) THE FOLLOWING CONDITION WAS LISTED IN RESOLUTION NO. |
| | 329-13 AS REQUIRED PRIOR TO THE ISSUANCE OF THE FIRST |
| | BUILDING PERMIT IN ORDER TO ADDRESS PERMANENT |
| | CONSTRUCTION ACROSS THE PROPERTY LINE. THE BUILDING |
| | OFFICIAL HAS DETERMINED THAT THE CURRENT TEMPORARY |
| | CONSTRUCTION EASEMENT WILL SUFFICE FOR BUILDING PERMIT |
| | TO BE ISSUED; HOWEVER, HE HAS STATED THAT THE PERMANENT |
| | INSTRUMENT SHALL BE RECORDED IN ACCORDANCE WITH THE |
| | CONDITION PRIOR TO ISSUANCE OF THE CO OR TCO, OR THE |
| | CONNECTOR BETWEEN THE HOTEL AND THE CONVENTION CENTER |
| | AND ANY OTHER STRUCTURES OR SYSTEMS THAT CROSS THE |
| | SHARED PROPERTY LINE SHALL BE REMOVED. |
| | |
| | A. PRIOR TO THE ISSUANCE OF THE SPECIFIC BUILDING |
| | PERMIT FOR STRUCTURES OR SYSTEMS THAT CROSS THE SHARED |
| | PROPERTY LINE WITH THE PALM BEACH COUNTY CONVENTION |
| | CENTER PARCEL, TO INCLUDE WALKWAY CONNECTIONS, THE |
| | POOL, POOL DECK, POOL EQUIPMENT, IRRIGATION LINES, |
| | ETC., THE APPLICANT SHALL RECORD IN THE PUBLIC RECORD A |
| | UNITY OF TITLE, UNITY OF CONTROL, A RESTRICTIVE |
| | COVENANT, IN LIEU OF UNITY OF TITLE, OR OTHER |
| | APPROPRIATE INSTRUMENT, AS APPROVED BY THE OFFICE OF |
| | THE CITY ATTORNEY, TO ADDRESS THE HOTEL STRUCTURES OR |
| | SYSTEMS THAT ARE ON THE CONVENTION CENTER PARCEL OR |
| | WHICH CROSS THE SHARED PROPERTY LINE. |
| | |
| | 2) THE FOLLOWING CONDITIONS WERE LISTED IN RESOLUTION |
| | NO. 329-13 AS REQUIRED PRIOR TO THE ISSUANCE OF THE |
| | FIRST BUILDING PERMIT FOR VERTICAL CONSTRUCTION; |
| | HOWEVER, UPON ENGINEERING SERVICES DEPARTMENT AND CITY |
| | SURVEYOR REVIEW OF THE PROJECT AND RELATED PLANS, IT |
| | HAS BEEN DETERMINED THAT THESE CONDITIONS SHALL BE |
| | ADDRESSED PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF |
| | OCCUPANCY. |
| | |
| | A. RECORD EASEMENTS IN FAVOR OF THE CITY FOR ANY PUBLIC |
| | SIDEWALKS OR UTILITIES ON THE HOTEL OR PARKING |
| | STRUCTURE PARCELS. ****FINAL EASEMENT LOCATIONS WILL BE |
| | BASED ON THE AS BUILT SURVEY OF THE SITE.**** |
| | |
| | B. SECURE A RIGHT-OF-WAY PERMIT FROM THE CITY FOR THE |
| | RECONFIGURATION OF THE MEDIANS AND INSTALLATION OF |
| | LANDSCAPE MATERIAL WITHIN THE FLORIDA AVENUE |
| | RIGHT-OF-WAY. AS PART OF THE RECONFIGURATION OF THE |
| | MEDIANS, THE APPLICANT SHALL INSTALL APPROPRIATE |
| | SIGNAGE TO WARN MOTORISTS OF THE MID-BLOCK PEDESTRIAN |
| | CROSSING ON FLORIDA AVENUE IN ACCORDANCE WITH THE |
| | LATEST VERSION OF THE MANUAL ON UNIFORM TRAFFIC CONTROL |
| | DEVICES (MUTCD). ****THE ENGINEERING SERVICES |
| | DEPARTMENT HAS DETERMINED THAT IT IS TOO PREMATURE TO |
| | ISSUE A RIGHT-OF-WAY PERMIT SINCE THE ACTUAL |
| | RIGHT-OF-WAY WORK IS NOT SET TO BEGIN UNTIL THE |
| | CONSTRUCTION IS FURTHER ALONG.**** |
| | |
| | 3) REPEAT COMMENT: LIGHTING SHALL BE PROVIDED FOR THE |
| | ART NICHES. WHILE A NOTE WAS ADDED TO THE ENLARGED |
| | ELEVATIONS REFERRING TO THE ELECTRICAL DRAWINGS FOR THE |
| | LIGHTING IN THE NICHES, THE REVIEWER IS UNABLE TO |
| | LOCATE THE LIGHTING ON THE ELECTRICAL DRAWINGS. PLEASE |
| | CLEARLY IDENTIFY ON WHAT SHEETS THE LIGHTING DETAILS |
| | ARE LOCATED. |
| | |
| | 4) PARTIAL REPEAT COMMENT: THE FLOOR PLANS FAIL TO SHOW |
| | THE NEW GLAZING AND ARCHITECTURAL DETAILS ON THE |
| | SOUTHERN ELEVATION OF THE TOWER THAT WAS SHOWN ON THE |
| | MINOR AMENDMENT AND THE REVISED ELEVATIONS. EXAMPLE |
| | HALLWAY AND END ROOMS DO NOT HAVE WINDOWS. |
| | |
| | 5) DATA ON SHEET A0.03 SHALL BE REVISED TO MATCH THE |
| | MINOR AMENDMENT DATA. |
| | |
| | 6) SHEET A3.01 SHOWS DIFFERENT SQUARE FOOTAGE NUMBERS |
| | FOR THE PUBLIC AREAS (RESTAURANT, BAR, ETC.) THAT ON |
| | THE SUBMITTED MINOR AMENDMENT AND THE LIFE SAFETY PLAN |
| | (SHEET A2.02). ADDITIONALLY, NO SQUARE FOOTAGE IS |
| | PROVIDED FOR THE MARKET. THE NUMBERS SHALL BE SHOWS AND |
| | BE CONSISTENT AMONG ALL PLANS. |
| | |
| | 7) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE |
| | FOLLOWING ITEMS. THE VALUE OF THE WORK SHALL BE |
| | SUBMITTED WITH EACH PERMIT AND NOT THE MAIN PERMIT. |
| | FULL ZONING REVIEW WILL OCCUR UPON SUBMITTAL OF THE |
| | SEPARATE PERMITS PLANS. |
| | |
| | A. SITE FURNITURE THAT WILL BE PERMANENTLY AFFIXED TO |
| | THE GROUND (EX. TRASH CANS, BENCHES, FIRE PIT, ETC.) |
| | STAFF HAS REVIEWED THE LOCATIONS OF THE SITE FURNITURE |
| | AND THEY COMPLY WITH THE APPROVED SITE PLAN. |
| | B. SITE LIGHTING |
| | C. BICYCLE RACKS |
| | D. ENTRY DRIVE - A RIGHT-OF-WAY PERMIT IS REQUIRED FOR |
| | THE CONNECTION TO FLORIDA AVENUE. |
| | E. CIVIL PLANS AND RIGHT-OF-WAY PERMIT (THROUGH |
| | ENGINEERING SERVICES) |
| | F. SIGNS - SEE COMMENT 10 FOR ADDITIONAL INFORMATION. |
| | G. POOL, SPA AND POOL DECK H |
| | H. FENCES/GATES - THE OVERALL HEIGHT OF THE |
| | FENCE/RETAINING WALL/COLUMNS MAY NOT EXCEED EIGHT (8) |
| | FEET IN HEIGHT WHEN MEASURED ON THE EXTERIOR SIDE |
| | (CONVENTION CENTER SIDE) FROM GRADE. DIMENSIONS WERE |
| | NOT PROVIDED. |
| | I. CABANAS, INCLUDING THE TOWEL ISSUE CABANA |
| | J. SUN SHADE |
| | K. FOUNTAIN WALL |
| | L. SIDEWALKS, COVERED WALKWAY AND OTHER ITEMS WHOLLY ON |
| | THE CONVENTION CENTER PARCEL. |
| | M. IRRIGATION PERMIT |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE GENERATED BASED ON THE |
| | RESUBMITTAL AND THE FULL ZONING REVIEW OF THE PLANS |
| | SUBMITTED WITH THE SEPARATE PERMITS. |
| | |
| | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
| | |
| | |
| | |
| | |
| | |
| 2014-07-01 12:59:06 | 7/1/14 ZONING SENT TO ES. SG |