2014-08-05 15:42:09P B CONVENTION CENTER HILTON HOTEL 1ST PLUMBING REVIEW
 PLUMBING PLAN REVIEW
 PERMIT:14050111
 ADD: 600 OKEECHOBEE BLVD
 CONT: COASTAL CONSTRUCTION
 TEL: (561) 630-3770
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 THE PALM BEACH CONVENTION CENTER HILTON HOTEL
 CONSTRUCTION OF NEW 400 ROOM HOTEL INCLUDING BALLROOMS,
 RESTAURANT(S), MEETING SPACE, POOL DECK AND AMENITIES
  
 2ND REVIEW
 DATE: TUESDAY AUGUST 05/ 2014
  
 ACTION: DENIED
  
 FUEL GAS: THIS REVIEW IS UNDER A SEPARATE PLAN REVIEW
 STOP, SEE FOR STATUS AND COMMENTS.
  
 1-2) COMPLIED.
 3) SHEET P0.01 BASEMENT LEVEL:
  
 3A) 2ND REQUEST: THE ASSOCIATES CAFETERIA PLUMBING PLAN
 LIST EQUIPMENT AND PLUMBING FIXTURES WITH A C-LABEL.
 THE PLUMBING INDEX LIST SHEET P2.01 AS THE BANQUET
 KITCHEN & ASSO. CAFE SCHEDULE, THERE ARE NO C EQUIPMENT
 ON SHEET P2.01, THIS LIST ALL FIXTURES & EQUIPMENT ON
 THIS SHEET ARE LISTED WITH A Q. I CAN'T IDENTIFY THE
 TYPE OF EQUIPMENT FOR THE TYPE OR WASTE REQUIRED. NOTE
 # 10 REFERS TO GREASY WASTE FOR THIS SHEET BUT NOT
 IDENTIFIED ON THE PLAN.
  
 3B)(1)(2)(3)(4) COMPLIED.
  
 3C) COMPLIED.
  
 3D) COMPLIED.
  
 3E) COMPLIED.
  
 3F) FOUND, NO COMMENT.
  
 3G) 2ND REQUEST, RESPONSE INDICATES SEE SHEET P4.02.
 SHEET P0.01 THE BASEMENT LEVEL/ POOL EQUIPMENT ROOM
 NOTE #10 INDICATES THE USE OF A SUMP PUMP TO PUMP THE
 POOL BACK WASH TO SANITARY, THERE IS NO PIT SHOWN ON
 THE PLANS, NOR IS THERE A NOTE PROVIDING DETAILS SIZE
 OF PUMP OR DISCHARGE REQUIRED. SUMPS ARE TO COMPLY WITH
 2010 FBC-P 712.
  
 3H) COMPLIED.
  
 4 ) COMPLIED.
  
 5) SHEET P1.02 LEVEL 1 AREA Q2:
  
 5A) COMPLIED.
  
 5B) 2ND REQUEST. SHEET P1.02 LEVEL 1 AREA Q2, NOTE# 21
 INDICATES A NEW 750 GALLON CONCRETE VAULT TYPE GREASE
 INTERCEPTOR, NOTE 36 SEE SHEET P3.01D FOR THE
 CONTINUATION OF GREASY WASTE. PLEASE PROVIDE THE SIZING
 CALCULATIONS FOR THE CONCRETE VAULT TYPE GREASE
 INTERCEPTOR,
 SIZING IS TO BE IN ACCORDANCE WITH 2010 FBC-P SECTION
 1003.5.1 AND TABLE 1003.5.1.
  
 5C) REVIEWED BY MECHANICAL PLAN REVIEW.NO ACTION
 REQUIRED. SHEET P1.02 LEVEL 1 AREA Q2, NOTES 22-25
 DEALS WITH FUEL LINES, PLEASE NOTE DIRECTLY ABOVE THE
 NEXT STORY IS THE DIESEL EMERGENCY GENERATOR. DIESEL,
 FUEL TANKS AND ASSOCIATED LINES WILL BE REVIEWED BY THE
 MECHANICAL REVIEWER AND INSPECTED BY THE MECHANICAL
 INSPECTOR. DETAIL P4.04.
  
 6) 2ND REQUEST. SHEET P1.03 LEVEL 1 AREA Q3. SHEET
 P1.03 LEVEL 1 AREA Q3, NOTE# 01 INDICATES A NEW 1,250
 GALLON CONCRETE VAULT TYPE GREASE INTERCEPTOR, NOTE
 REFERS TO SHEET P4.03 THE GREASE INTERCEPTOR DETAIL.
 SHEET P3.00 INDICATES 132 FU DRAINING INTO THE GREASE
 INTERCEPTOR. IF SIZING USING TABLE 1003.3.4.1 THIS
 TABLE IS TO BE USED WHEN THE DESIGN IS FOR HYDRO
 MECHANICAL GREASE INTERCEPTORS.
 PLEASE PROVIDE THE SIZING CALCULATIONS FOR THE CONCRETE
 VAULT TYPE GREASE INTERCEPTOR, SIZING IS TO BE IN
 ACCORDANCE WITH 2010 FBC-P SECTION 1003.5.1 AND TABLE
 1003.5.1.
  
 THE CITY FOG INSPECTORS (FATS, OILS & GREASE) MONITOR
 ALL GREASE INTERCEPTORS TO VERIFY COMPLIANCE WITH THE
 CITY?S MUNI CODE SEC. 90-126. PROHIBITIONS AND
 LIMITATIONS OF DISCHARGE.(7) MINERAL OIL IN EXCESS OF
 50 MG/L OR ANIMAL/VEGETABLE FATS, WAX, GREASE, OR OILS
 IN EXCESS OF 100 MG/L, WHETHER EMULSIFIED OR NOT; OR
 SUBSTANCES WHICH MAY SOLIDIFY OR BECOME VISCOUS AT
 TEMPERATURES LOWER THAN OR EQUAL TO 150 DEGREES
 FAHRENHEIT (65.56 DEGREES CELSIUS).
  
 7) 2ND REQUEST, RESPONSE INDICATES SEE SHEET P2.01 FOR
 THIS AREA. SHEET P1.04 LEVEL 1 AREA Q4. KITCHEN 105 ,
 NO GREASY WASTE IS SHOWN ON THE PLANS, NOTE # 15
 INDICATES SEE P2.04 FOR CONTINUATION. THIS SHEET IS A
 EQUIPMENT SCHEDULE, PLEASE PROVIDE A GREASY WASTE
 ISOMETRIC OR WHERE TO LOCATE SUCH PLANS. PLEASE PROVIDE
 THE SIZING CALCULATIONS FOR THE CONCRETE VAULT TYPE
 GREASE INTERCEPTOR, SIZING IS TO BE IN ACCORDANCE WITH
 2010 FBC-P SECTION 1003.5.1 AND TABLE 1003.5.1.
  
 8) COMPLIED.
  
 9) COMPLIED.
  
 10) COMPLIED
  
 11) COMPLIED.
  
 12) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO