| 2014-08-05 15:42:09 | P B CONVENTION CENTER HILTON HOTEL 1ST PLUMBING REVIEW |
| | PLUMBING PLAN REVIEW |
| | PERMIT:14050111 |
| | ADD: 600 OKEECHOBEE BLVD |
| | CONT: COASTAL CONSTRUCTION |
| | TEL: (561) 630-3770 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | THE PALM BEACH CONVENTION CENTER HILTON HOTEL |
| | CONSTRUCTION OF NEW 400 ROOM HOTEL INCLUDING BALLROOMS, |
| | RESTAURANT(S), MEETING SPACE, POOL DECK AND AMENITIES |
| | |
| | 2ND REVIEW |
| | DATE: TUESDAY AUGUST 05/ 2014 |
| | |
| | ACTION: DENIED |
| | |
| | FUEL GAS: THIS REVIEW IS UNDER A SEPARATE PLAN REVIEW |
| | STOP, SEE FOR STATUS AND COMMENTS. |
| | |
| | 1-2) COMPLIED. |
| | 3) SHEET P0.01 BASEMENT LEVEL: |
| | |
| | 3A) 2ND REQUEST: THE ASSOCIATES CAFETERIA PLUMBING PLAN |
| | LIST EQUIPMENT AND PLUMBING FIXTURES WITH A C-LABEL. |
| | THE PLUMBING INDEX LIST SHEET P2.01 AS THE BANQUET |
| | KITCHEN & ASSO. CAFE SCHEDULE, THERE ARE NO C EQUIPMENT |
| | ON SHEET P2.01, THIS LIST ALL FIXTURES & EQUIPMENT ON |
| | THIS SHEET ARE LISTED WITH A Q. I CAN'T IDENTIFY THE |
| | TYPE OF EQUIPMENT FOR THE TYPE OR WASTE REQUIRED. NOTE |
| | # 10 REFERS TO GREASY WASTE FOR THIS SHEET BUT NOT |
| | IDENTIFIED ON THE PLAN. |
| | |
| | 3B)(1)(2)(3)(4) COMPLIED. |
| | |
| | 3C) COMPLIED. |
| | |
| | 3D) COMPLIED. |
| | |
| | 3E) COMPLIED. |
| | |
| | 3F) FOUND, NO COMMENT. |
| | |
| | 3G) 2ND REQUEST, RESPONSE INDICATES SEE SHEET P4.02. |
| | SHEET P0.01 THE BASEMENT LEVEL/ POOL EQUIPMENT ROOM |
| | NOTE #10 INDICATES THE USE OF A SUMP PUMP TO PUMP THE |
| | POOL BACK WASH TO SANITARY, THERE IS NO PIT SHOWN ON |
| | THE PLANS, NOR IS THERE A NOTE PROVIDING DETAILS SIZE |
| | OF PUMP OR DISCHARGE REQUIRED. SUMPS ARE TO COMPLY WITH |
| | 2010 FBC-P 712. |
| | |
| | 3H) COMPLIED. |
| | |
| | 4 ) COMPLIED. |
| | |
| | 5) SHEET P1.02 LEVEL 1 AREA Q2: |
| | |
| | 5A) COMPLIED. |
| | |
| | 5B) 2ND REQUEST. SHEET P1.02 LEVEL 1 AREA Q2, NOTE# 21 |
| | INDICATES A NEW 750 GALLON CONCRETE VAULT TYPE GREASE |
| | INTERCEPTOR, NOTE 36 SEE SHEET P3.01D FOR THE |
| | CONTINUATION OF GREASY WASTE. PLEASE PROVIDE THE SIZING |
| | CALCULATIONS FOR THE CONCRETE VAULT TYPE GREASE |
| | INTERCEPTOR, |
| | SIZING IS TO BE IN ACCORDANCE WITH 2010 FBC-P SECTION |
| | 1003.5.1 AND TABLE 1003.5.1. |
| | |
| | 5C) REVIEWED BY MECHANICAL PLAN REVIEW.NO ACTION |
| | REQUIRED. SHEET P1.02 LEVEL 1 AREA Q2, NOTES 22-25 |
| | DEALS WITH FUEL LINES, PLEASE NOTE DIRECTLY ABOVE THE |
| | NEXT STORY IS THE DIESEL EMERGENCY GENERATOR. DIESEL, |
| | FUEL TANKS AND ASSOCIATED LINES WILL BE REVIEWED BY THE |
| | MECHANICAL REVIEWER AND INSPECTED BY THE MECHANICAL |
| | INSPECTOR. DETAIL P4.04. |
| | |
| | 6) 2ND REQUEST. SHEET P1.03 LEVEL 1 AREA Q3. SHEET |
| | P1.03 LEVEL 1 AREA Q3, NOTE# 01 INDICATES A NEW 1,250 |
| | GALLON CONCRETE VAULT TYPE GREASE INTERCEPTOR, NOTE |
| | REFERS TO SHEET P4.03 THE GREASE INTERCEPTOR DETAIL. |
| | SHEET P3.00 INDICATES 132 FU DRAINING INTO THE GREASE |
| | INTERCEPTOR. IF SIZING USING TABLE 1003.3.4.1 THIS |
| | TABLE IS TO BE USED WHEN THE DESIGN IS FOR HYDRO |
| | MECHANICAL GREASE INTERCEPTORS. |
| | PLEASE PROVIDE THE SIZING CALCULATIONS FOR THE CONCRETE |
| | VAULT TYPE GREASE INTERCEPTOR, SIZING IS TO BE IN |
| | ACCORDANCE WITH 2010 FBC-P SECTION 1003.5.1 AND TABLE |
| | 1003.5.1. |
| | |
| | THE CITY FOG INSPECTORS (FATS, OILS & GREASE) MONITOR |
| | ALL GREASE INTERCEPTORS TO VERIFY COMPLIANCE WITH THE |
| | CITY?S MUNI CODE SEC. 90-126. PROHIBITIONS AND |
| | LIMITATIONS OF DISCHARGE.(7) MINERAL OIL IN EXCESS OF |
| | 50 MG/L OR ANIMAL/VEGETABLE FATS, WAX, GREASE, OR OILS |
| | IN EXCESS OF 100 MG/L, WHETHER EMULSIFIED OR NOT; OR |
| | SUBSTANCES WHICH MAY SOLIDIFY OR BECOME VISCOUS AT |
| | TEMPERATURES LOWER THAN OR EQUAL TO 150 DEGREES |
| | FAHRENHEIT (65.56 DEGREES CELSIUS). |
| | |
| | 7) 2ND REQUEST, RESPONSE INDICATES SEE SHEET P2.01 FOR |
| | THIS AREA. SHEET P1.04 LEVEL 1 AREA Q4. KITCHEN 105 , |
| | NO GREASY WASTE IS SHOWN ON THE PLANS, NOTE # 15 |
| | INDICATES SEE P2.04 FOR CONTINUATION. THIS SHEET IS A |
| | EQUIPMENT SCHEDULE, PLEASE PROVIDE A GREASY WASTE |
| | ISOMETRIC OR WHERE TO LOCATE SUCH PLANS. PLEASE PROVIDE |
| | THE SIZING CALCULATIONS FOR THE CONCRETE VAULT TYPE |
| | GREASE INTERCEPTOR, SIZING IS TO BE IN ACCORDANCE WITH |
| | 2010 FBC-P SECTION 1003.5.1 AND TABLE 1003.5.1. |
| | |
| | 8) COMPLIED. |
| | |
| | 9) COMPLIED. |
| | |
| | 10) COMPLIED |
| | |
| | 11) COMPLIED. |
| | |
| | 12) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |