| 2014-08-08 11:26:07 | 600 OKEECHOBEE BOULEVARD - HIGH RISE HOTEL |
| | PERMIT #14050111 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | NOTE: ALL FIRE REVIEW COMMENTS REFERENCE NFPA 101 REFER |
| | TO NFPA 101-THE LIFE SAFETY CODE (2009 EDITION WITH |
| | FLORIDA AMENDMENTS). |
| | |
| | |
| | NEW COMMENT - SHEETS A3.00 - A3.14: DRAWING SERIES WILL |
| | NEED TO BE UPDATED TO INCORPORATE THE NEW FLOOR PLANS |
| | REPRESENTED ON THE OTHER SHEETS. |
| | |
| | NEW COMMENT - SHEET A4.03: FIRE COMMAND #150 HAS BEEN |
| | RECONFIGURED RESULTING IN A MINIMUM ROOM DIMENSION OF |
| | LESS THAN 10'-0" (FBC 911.1.3). |
| | |
| | NEW COMMENT - SHEET A4.04: FITNESS (#104) FREE-WEIGHTS |
| | STORAGE RACK IS OBSTRUCTING EXIT DOOR #104A. |
| | |
| | RESPONSE COMMENT: FIRE PIT (SKY TERRACE) HAS NOT BEEN |
| | ACCEPTED OR REJECTED AT THIS TIME. PRODUCT DATA AND |
| | SHOP DRAWINGS TO BE SUBMITTED BY CONTRACTOR. OPEN |
| | FLAMES WILL NEED TO BE GUARDED AGAINST ACCIDENTAL OR |
| | INTENTIONAL CONTACT BY OCCUPANTS. |
| | ORIGINAL COMMENT - GENERAL: PROVIDE ADDITIONAL |
| | INFORMATION ON THE PROPOSED GAS FIRED PIT LOCATED NEAR |
| | THE OPEN SKY TERRACE/BAR. SHEET E1-05 REFERENCES A GAS |
| | FIRED PIT CONTROLLER, BUT NO OTHER DESIGN INFORMATION |
| | WAS FOUND. |
| | |
| | RESPONSE COMMENT: ONLY ONE EXIT SIGN PROVIDED. THIS ONE |
| | FIXTURE WILL BE INSUFFICIENT TO CLEARLY AND OBVIOUSLY |
| | DIRECT OCCUPANTS TO THE EXITS. |
| | ORIGINAL COMMENT - SHEET E1-06: NO EXTERIOR EXIT SIGNS |
| | DIRECTING POOL OCCUPANTS TO EGRESS THROUGH THE |
| | CONNECTOR. |
| | |
| | NEW COMMENT - SHEET E3.04: PROVIDE EMERGENCY LIGHTING |
| | IN UNDERGROUND POOL EQUIPMENT ROOM IF NOT ALREADY |
| | PROVIDED. |
| | |
| | RESPONSE COMMENT: PORTIONS OF THE SYSTEM UPSTREAM OF |
| | ANY PRVS WILL BE SUBJECT TO PRESSURES EXCEEDING 150 PSI |
| | DUE TO THE FIRE PUMP CHURN PRESSURE (+140 PSI) PLUS AN |
| | ADDITIONAL +70 PSI FROM THE CITY SUPPLY SIDE. |
| | ORIGINAL COMMENT - SHEET FP0-01: FIRE SPRINKLER NOTE |
| | #15 - PER NFPA 13 SECTION 24.2.1.2 PORTIONS OF THE |
| | SYSTEM NORMALLY SUBJECTED TO SYSTEM WORKING PRESSURES |
| | IN EXCESS OF 150 PSI SHALL BE TESTED AT A PRESSURE OF |
| | 50 PSI IN EXCESS OF SYSTEM WORKING PRESSURE. |
| | |
| | MODIFIED COMMENT: SHEET FP1-04, PROVIDE AN ADDITIONAL |
| | 2-1/2" FIRE DEPARTMENT HOSE VALVE IN HOTEL LOBBY #100 |
| | CORRIDOR. |
| | ORIGINAL COMMENT - FIRE PROTECTION LEVEL 1: DUE TO THE |
| | SIZE OF THE FLOOR PLATE, PLEASE PROVIDE 2-1/2" FIRE |
| | DEPARTMENT HOSE VALVES THROUGHOUT THE CORRIDORS. |
| | |
| | NEW COMMENT: SHEET FP1-04, VERIFY AND CONFIRM ANY |
| | EXTERIOR ROOFS, CANOPIES AND PORTE-COCHERES COMPLY WITH |
| | NFPA 13 SECTION 8.15.7. |
| | |
| | RESPONSE COMMENT: DRAWINGS HAVE NOT BEEN MODIFIED TO |
| | ADDRESS THE ORIGINAL COMMENT. |
| | ORIGINAL COMMENT - SHEET FP1-13: THE SPRINKLERS |
| | PROTECTING THE SPACES ON THE ROOF LEVEL WILL NEED TO BE |
| | SUPPLIED BY A SEPARATE SUPERVISED CONTROL VALVE AND |
| | FLOW SWITCH SO FIREFIGHTERS CAN DISTINGUISH A FIRE ON |
| | THE 12TH FLOOR FROM A FIRE ON THE ROOF LEVEL. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |