Plan Review Notes
Plan Review Notes For Permit 14050111
Permit Number 14050111
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2014-08-08 11:26:07600 OKEECHOBEE BOULEVARD - HIGH RISE HOTEL
 PERMIT #14050111
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: ALL FIRE REVIEW COMMENTS REFERENCE NFPA 101 REFER
 TO NFPA 101-THE LIFE SAFETY CODE (2009 EDITION WITH
 FLORIDA AMENDMENTS).
  
  
 NEW COMMENT - SHEETS A3.00 - A3.14: DRAWING SERIES WILL
 NEED TO BE UPDATED TO INCORPORATE THE NEW FLOOR PLANS
 REPRESENTED ON THE OTHER SHEETS.
  
 NEW COMMENT - SHEET A4.03: FIRE COMMAND #150 HAS BEEN
 RECONFIGURED RESULTING IN A MINIMUM ROOM DIMENSION OF
 LESS THAN 10'-0" (FBC 911.1.3).
  
 NEW COMMENT - SHEET A4.04: FITNESS (#104) FREE-WEIGHTS
 STORAGE RACK IS OBSTRUCTING EXIT DOOR #104A.
  
 RESPONSE COMMENT: FIRE PIT (SKY TERRACE) HAS NOT BEEN
 ACCEPTED OR REJECTED AT THIS TIME. PRODUCT DATA AND
 SHOP DRAWINGS TO BE SUBMITTED BY CONTRACTOR. OPEN
 FLAMES WILL NEED TO BE GUARDED AGAINST ACCIDENTAL OR
 INTENTIONAL CONTACT BY OCCUPANTS.
 ORIGINAL COMMENT - GENERAL: PROVIDE ADDITIONAL
 INFORMATION ON THE PROPOSED GAS FIRED PIT LOCATED NEAR
 THE OPEN SKY TERRACE/BAR. SHEET E1-05 REFERENCES A GAS
 FIRED PIT CONTROLLER, BUT NO OTHER DESIGN INFORMATION
 WAS FOUND.
  
 RESPONSE COMMENT: ONLY ONE EXIT SIGN PROVIDED. THIS ONE
 FIXTURE WILL BE INSUFFICIENT TO CLEARLY AND OBVIOUSLY
 DIRECT OCCUPANTS TO THE EXITS.
 ORIGINAL COMMENT - SHEET E1-06: NO EXTERIOR EXIT SIGNS
 DIRECTING POOL OCCUPANTS TO EGRESS THROUGH THE
 CONNECTOR.
  
 NEW COMMENT - SHEET E3.04: PROVIDE EMERGENCY LIGHTING
 IN UNDERGROUND POOL EQUIPMENT ROOM IF NOT ALREADY
 PROVIDED.
  
 RESPONSE COMMENT: PORTIONS OF THE SYSTEM UPSTREAM OF
 ANY PRVS WILL BE SUBJECT TO PRESSURES EXCEEDING 150 PSI
 DUE TO THE FIRE PUMP CHURN PRESSURE (+140 PSI) PLUS AN
 ADDITIONAL +70 PSI FROM THE CITY SUPPLY SIDE.
 ORIGINAL COMMENT - SHEET FP0-01: FIRE SPRINKLER NOTE
 #15 - PER NFPA 13 SECTION 24.2.1.2 PORTIONS OF THE
 SYSTEM NORMALLY SUBJECTED TO SYSTEM WORKING PRESSURES
 IN EXCESS OF 150 PSI SHALL BE TESTED AT A PRESSURE OF
 50 PSI IN EXCESS OF SYSTEM WORKING PRESSURE.
  
 MODIFIED COMMENT: SHEET FP1-04, PROVIDE AN ADDITIONAL
 2-1/2" FIRE DEPARTMENT HOSE VALVE IN HOTEL LOBBY #100
 CORRIDOR.
 ORIGINAL COMMENT - FIRE PROTECTION LEVEL 1: DUE TO THE
 SIZE OF THE FLOOR PLATE, PLEASE PROVIDE 2-1/2" FIRE
 DEPARTMENT HOSE VALVES THROUGHOUT THE CORRIDORS.
  
 NEW COMMENT: SHEET FP1-04, VERIFY AND CONFIRM ANY
 EXTERIOR ROOFS, CANOPIES AND PORTE-COCHERES COMPLY WITH
 NFPA 13 SECTION 8.15.7.
  
 RESPONSE COMMENT: DRAWINGS HAVE NOT BEEN MODIFIED TO
 ADDRESS THE ORIGINAL COMMENT.
 ORIGINAL COMMENT - SHEET FP1-13: THE SPRINKLERS
 PROTECTING THE SPACES ON THE ROOF LEVEL WILL NEED TO BE
 SUPPLIED BY A SEPARATE SUPERVISED CONTROL VALVE AND
 FLOW SWITCH SO FIREFIGHTERS CAN DISTINGUISH A FIRE ON
 THE 12TH FLOOR FROM A FIRE ON THE ROOF LEVEL.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730