| 2014-08-15 12:48:02 | DATE: 8/15/2014 |
| | PROJECT: WPB HILTON CONVENTION CENTER HOTEL |
| | PERMIT#: 14050111 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: PROVISO |
| | |
| | 1) SHEET E1-01 |
| | A. ELECTRICAL RM, FIRE PUMP RM, ELEVATOR EQUIPMENT ROOM |
| | MECHANICAL RM AND SIMILAR ROOMS, SHOULD NOT HAVE AN OS |
| | SWITCH DUE TO FBC 505.2.2 EXCEPTION #4 SPACES WHERE AN |
| | AUTOMATIC SHUTOFF WOULD ENDANGER OCCUPANT SAFETY OR |
| | SECURITY. |
| | |
| | 2) SHEET E1.09 |
| | A. 680.10 UNDERGROUND WIRING LOCATION. UNDERGROUND |
| | WIRING SHALL NOT BE PERMITTED UNDER THE POOL OR WITHIN |
| | THE AREA EXTENDING 1.5 M (5 FT) HORIZONTALLY FROM THE |
| | INSIDE WALL OF THE POOL UNLESS THIS WIRING IS NECESSARY |
| | TO SUPPLY POOL EQUIPMENT PERMITTED BY THIS ARTICLE. |
| | WHERE SPACE LIMITATIONS PREVENT WIRING FROM BEING |
| | ROUTED A DISTANCE 1.5 M (5 FT) OR MORE FROM THE POOL, |
| | SUCH WIRING SHALL BE PERMITTED WHERE INSTALLED IN |
| | COMPLETE RACEWAY SYSTEMS OF RIGID METAL CONDUIT, |
| | INTERMEDIATE METAL CONDUIT, OR A NONMETALLIC RACEWAY |
| | SYSTEM. ALL METAL CONDUIT SHALL BE CORROSION RESISTANT |
| | AND SUITABLE FOR THE LOCATION. THE MINIMUM COVER DEPTH |
| | SHALL BE AS GIVEN IN TABLE 680.10. |
| | B. 680.22 (5)(C)(1) MEASUREMENTS. IN DETERMINING THE |
| | DIMENSIONS IN THIS SECTION ADDRESSING RECEPTACLE |
| | SPACING THE DISTANCE TO BE MEASURED SHALL BE THE |
| | SHORTEST PATH THE SUPPLY CORD OF AN APPLIANCE CONNECTED |
| | TO THE RECEPTACLE WOULD FOLLOW WITHOUT PIERCING A |
| | FLOOR, WALL, CEILING, DOORWAY WITH HINGED OR SLIDING |
| | DOOR, WINDOW OPENING, OR OTHER EFFECTIVE PERMANENT |
| | BARRIER. |
| | (C) LUMINAIRES, LIGHTING OUTLETS, AND CEILING-SUSPENDED |
| | (PADDLE) FANS. |
| | (1) NEW OUTDOOR INSTALLATION CLEARANCES. IN OUTDOOR |
| | POOL AREAS, LUMINAIRES, LIGHTING OUTLETS, AND CEILING |
| | SUSPENDED (PADDLE) FANS INSTALLED ABOVE THE POOL OR THE |
| | AREA EXTENDING 1.5 M (5 FT) HORIZONTALLY FROM THE |
| | INSIDE WALLS OF THE POOL SHALL BE INSTALLED AT A HEIGHT |
| | NOT LESS THAN 3.7 M (12 FT) ABOVE THE MAXIMUM WATER |
| | LEVEL OF THE POOL. |
| | |
| | 3) SHEET E4.01 |
| | A. PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| | 110.16, 110.22 |
| | B. IDENTIFY ALL SWITCHGEAR. SEE NEC 110.22 |
| | IDENTIFICATION OF DISCONNECTING MEANS. AND 240.86(A) |
| | (A) GENERAL. EACH DISCONNECTING MEANS SHALL BE LEGIBLY |
| | MARKED TO INDICATE ITS PURPOSE UNLESS LOCATED AND |
| | ARRANGED SO THE PURPOSE IS EVIDENT. THE MARKING SHALL |
| | BE OF SUFFICIENT DURABILITY TO WITHSTAND THE |
| | ENVIRONMENT INVOLVED. |
| | (B) NEC 230.95 GROUNDFAULT PROTECTION OF EQUIPMENT |
| | SHALL BE PROVIDED FOR SOLIDLY GROUNDED WYE ELECTRIC |
| | SERVICES OF MORE THAN 150 VOLTS TO GROUND BUT NOT |
| | EXCEEDING 600 VOLTS PHASE-TO-PHASE FOR EACH SERVICE |
| | DISCONNECT RATED 1000 AMPERES OR MORE. |
| | (C) NEC 230.95 (C) THE GROUND-FAULT PROTECTION SYSTEM |
| | SHALL BE PERFORMANCE TESTED WHEN FIRST INSTALLED ON |
| | SITE. THE TEST SHALL BE CONDUCTED IN ACCORDANCE WITH |
| | INSTRUCTIONS THAT SHALL BE PROVIDED WITH THE EQUIPMENT. |
| | A WRITTEN RECORD OF THIS TEST SHALL BE MADE AND SHALL |
| | BE AVAILABLE TO THE AUTHORITY HAVING JURISDICTION. |
| | (D) ENGINEERED SERIES COMBINATION SYSTEMS. |
| | NEC 240.86 SERIES RATINGS. WHERE A CIRCUIT BREAKER IS |
| | USED ON A CIRCUIT HAVING AN AVAILABLE FAULT CURRENT |
| | HIGHER THAN THE MARKED INTERRUPTING RATING BY BEING |
| | CONNECTED ON THE LOAD SIDE OF AN ACCEPTABLE OVERCURRENT |
| | PROTECTIVE DEVICE HAVING A HIGHER RATING, THE CIRCUIT |
| | BREAKER SHALL MEET THE REQUIREMENTS SPECIFIED IN (A) OR |
| | (B), AND (C) |
| | C. PROVIDE VERIFICATION ON THE PLANS THAT THE FIRE PUMP |
| | FEEDERS, CIRCUIT CONDUCTORS, GENERATOR CONTROL WIRING |
| | AND PUMP WIRING ARE APPROPRIATELY FIRE PROTECTED. |
| | INDICATE THE FIRE RATING AND MATERIAL REQUIRED. NEC |
| | 695.6, 695.14 |
| | D. VERIFY THE FIRE PUMP FEEDERS ARE SIZED WITH A RATING |
| | NOT LESS THAN 125% OF THE SUM OF THE FIRE PUMP MOTOR, |
| | PRESSURE MAINTENANCE MOTORS AND 100 PERCENT OF THE |
| | ACCESSORIES. VERIFY THE MAXIMUM VOLTAGE DROP IS NOT |
| | MORE THAN 15 % BELOW NORMAL STARTING AND 5% BELOW WHEN |
| | THE MOTOR IS OPERATING AT 115% OF THE FULL ?LOAD |
| | CURRENT RATING. NEC 695.6, 695.7 |
| | INDICATE THAT ALL WIRING FOR EMERGENCY LOADS WILL BE |
| | IDENTIFIED WITH PERMANENT MARKINGS AND KEPT ENTIRELY |
| | INDEPENDENT OF ALL OTHER WIRING AND EQUIPMENT. NEC |
| | 700.9 |
| | E. PROVIDE SIGNS AT THE SERVICE INDICATING THE TYPE AND |
| | LOCATION OF THE ON SITE EMERGENCY POWER SOURCE. NEC |
| | 700.8 |
| | |
| | 4) SHEET E5.01, E5.04 |
| | PANEL 2CH, PANEL M1, AND POSSIBLY OTHERS NOT NOTED IN |
| | THIS REVIEW INDICATE MORE CIRCUITS THAN THE PANEL BOARD |
| | IS RATED FOR. 2, AND 3 POLE CIRCUITS SHALL BE |
| | CONSIDERED 2 OR 3 POLE DEVICES. IDENTIFY ALL |
| | PANELBOARDS ACCORDINGLY NEC 408.54. REVISE PANEL |
| | SCHEDULES TO COMPLY. |
| | |
| | 5) GENERAL NOTES: |
| | A. PROVIDE MANUFACTURER DATA SHEETS FOR FLOOR BOXES, |
| | B. A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR GENERATOR, SWIMMING POOL, FIRE ALARM, |
| | SECURITY, CCTV, DATA/COM, NETWORK, STRUCTURED CABLING, |
| | AUDIO/VIDEO, AND SIGNAGE. |
| | |