| 2014-08-02 14:06:53 | BUILDING PLAN REVIEW |
| | PERMIT:14050111 |
| | ADD: 600 OKEECHOBEE BLVD |
| | CONT: COASTAL CONSTRUCTION |
| | TEL: (561) 630-3770 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | THE PALM BEACH CONVENTION CENTER HILTON HOTEL |
| | CONSTRUCTION OF NEW 400 ROOM HOTEL INCLUDING BALLROOMS, |
| | RESTAURANT(S), MEETING SPACE, POOL DECK AND AMENITIES |
| | |
| | 2ND REVIEW |
| | DATE: SAT. AUGUST 02/ 2014 |
| | |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT DESCRIPTION LISTED ABOVE TO BUILD THE |
| | HOTEL, POOL, POOL DECK & AMENITIES IS A INCLUSIVE |
| | PACKAGE WITHIN THE SUBMITTED PLANS. THERE ARE CIVIL, |
| | SITE, LANDSCAPING, IRRIGATION, GREASE INTERCEPTORS, |
| | FUEL GAS, GENERATOR, FIRE SPRINKLER, FIRE ALARM, |
| | LOWVOLTAGE, AWNINGS AND SIGNAGE PLANS WITHIN THE |
| | SUBMITTED DOCUMENTS. |
| | THESE TYPE OF ACTIVITIES REQUIRE A SEPARATE PERMIT |
| | APPLICATION, REVIEW AND ASSOCIATED FEES. PLEASE BACK |
| | OUT THE VALUE OF WORK TO BE COMPLETED UNDER EACH OF |
| | THESE PERMITS SO THE BUILDING DEPARTMENT DOES NOT |
| | CHARGE YOU TWICE FOR THESE SERVICES. 2010 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION 105.1 PERMITS |
| | |
| | 2) UNDER CONSIDERATION BY THE BUILDING OFFICIAL. THE |
| | APPLIED VALUE OF THE HOTEL IS VALUED AT $35,000,000.00. |
| | THE CALCULATED VALUE OF THE PROJECT IS $55,930,374.00 |
| | (312,216 SQ FT X $179.14 BUILDING ONLY, NO SITE |
| | DEVELOPMENT) USING THE ICC BUILDING VALUATION DATA FOR |
| | BOTH AUGUST 2013 & FEB, 2014. W P B ADMINISTRTIVE CODE |
| | 108.2 SCHEDULE OF PERMIT FEES. ON BUILDINGS, |
| | STRUCTURES, ELECTRICAL, GAS, MECHANICAL, AND PLUMBING |
| | SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A FEE FOR |
| | EACH PERMIT SHALL BE PAID AS REQUIRED, IN ACCORDANCE |
| | WITH THE SCHEDULE ESTABLISHED BY THE APPLICABLE |
| | GOVERNING AUTHORITY. |
| | IF A BUILDING BREAK OUT OF SQUARE FOOTAGE UNDER EACH |
| | OCCUPANCY CLASSIFICATION THIS NUMBER WOUD DROP SOME |
| | WHAT, THIS WAS UNOT COMPLETED UNDER THE OCCUPANCY |
| | CLASSIFICATION, PROBANLY BECAUSE OF UNLIMITED AREA FOR |
| | A TYPE 1A BUILDING TYPE. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 3) 0210-A2.00: |
| | |
| | 3) COMPLIED. |
| | 4) 0211-A2.01/ BASEMENT LEVEL: |
| | |
| | 4A) 2ND REQUEST, THE FIRST COMMENT ASKED WHY THER WAS |
| | STORAGE BINS IN THE CORRIDOR, THE RESPONSE INDICATES |
| | THESE ARE SOILED LAUNDRY BINS. |
| | SOILED LAUNDRY IS CONSIDERED AN INCIDENTIAL ACCESSORY |
| | OCCUPANY IN ITSELF, AND IS TO BE SEPARATE WITHIN A |
| | ROOM, NOT IN A EXIT ACCESS COORIDOR, |
| | SEE THE 2010 FBC-B TABLE 508.2.5. IT STATES THAT |
| | LAUNDRY ROOMS ARE TO BE SEPARATED BY 1 HR ROOM OR |
| | PROVIDE FIRE SPRINKLERS. PLEASE REVIEW 508.2.5.2 |
| | NONFIRE-RESISTANCE-RATED SEPARATION AND PROTECTION. |
| | WHERE TABLE 508.2.5 PERMITS AN AUTOMATIC |
| | FIRE-EXTINGUISHING SYSTEM WITHOUT A FIRE BARRIER, THE |
| | INCIDENTAL ACCESSORY OCCUPANCIES SHALL BE SEPARATED |
| | FROM THE REMAINDER OF THE BUILDING BY CONSTRUCTION |
| | CAPABLE OF RESISTING THE PASSAGE OF SMOKE. THE WALLS |
| | SHALL EXTEND FROM THE TOP OF THE FOUNDATION OR FLOOR |
| | ASSEMBLY BELOW TO THE UNDERSIDE OF THE CEILING THAT IS |
| | A COMPONENT OF A FIRE-RESISTANCE-RATED FLOOR ASSEMBLY |
| | OR ROOF ASSEMBLY ABOVE OR TO THE UNDERSIDE OF THE FLOOR |
| | OR ROOF SHEATHING, DECK OR SLAB ABOVE. DOORS SHALL BE |
| | SELF- OR AUTOMATIC-CLOSING UPON DETECTION OF SMOKE IN |
| | ACCORDANCE WITH SECTION 715.4.8.3. DOORS SHALL NOT HAVE |
| | AIR TRANSFER OPENINGS AND SHALL NOT BE UNDERCUT IN |
| | EXCESS OF THE CLEARANCE PERMITTED IN ACCORDANCE WITH |
| | NFPA 80. WALLS SURROUNDING THE INCIDENTAL ACCESSORY |
| | OCCUPANCY SHALL NOT HAVE AIR TRANSFER OPENINGS UNLESS |
| | PROVIDED WITH SMOKE DAMPERS IN ACCORDANCE WITH SECTION |
| | 711.7. |
| | |
| | 1ST REVIEW COMMENT. THE SERVICE COORIDOR B000 IN FRONT |
| | OF THE HOUSEMANS STORAGE AND HOUSE KEEPING LAUNDRY IT |
| | APPEARS THERE IS STORAGE CABINETS BEING STORED WITHIN |
| | THE CORRIDOR? PLEASE EXPLAIN THE USAGE OF THIS AREA? |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 4B) COMPLIED. |
| | |
| | 5) 0212-A2.02/ LEVEL 0100 |
| | |
| | 5A-B) COMPLIED. |
| | |
| | 5C) 2ND REQUEST. THE RESPONCE INDICATES THE LULA LIFT |
| | IS TO BE ON STANDBY POWER. THE NOTE ABOVE THE LULA LIFT |
| | INDICATES THAT IT IS GOING TO BE HOOKED UP TO JRH-31 |
| | WHICH IS FOR THE JUNIOR BALL ROOM, ISN'T THE LIFT ON |
| | THE CONNVENTION CENTER SIDE OF THE PROPERTY LINE, AND |
| | SHOULDN'T ALL THE POWER FOR THIS SIDE OF THE PROPERTY |
| | BE COMING FROM THE CONVENTION CENTER? |
| | NOTE THE PERMIT FOR THE HOTEL STOPS AT THE PROPERTY |
| | LINE, A SECOND PERMIT WILL BE NEEDED FOR THE |
| | CONSTRUCTION ACTIVITIES ON THE CONVENTION CENTER |
| | PROPERTY. AGAIN THE LULA LIFT IS CONSIDERED AN ELEVATOR |
| | AND TREATED AS SUCH. FBC-B 403.4.7.2 (3) DOES NOT SAY |
| | ANYTHING ABOUT LIFTS. |
| | [F] 403.4.7.2 STANDBY POWER LOADS. |
| | THE FOLLOWING ARE CLASSIFIED AS STANDBY POWER LOADS: 3. |
| | STANDBY POWER SHALL BE PROVIDED FOR ELEVATORS IN |
| | ACCORDANCE WITH SECTIONS 1006.2.4, 3003, 3007 AND 3008. |
| | |
| | 5D-F COMPLIED. |
| | |
| | 5G) 2ND REQUEST, NOT SHOWN ON THIS SHEET BUT A4.04 DOES |
| | SHOW THE WEST PROPERTY LINE GOING THROUGH THE CABANAS |
| | AND POOL ON THE WEST OF THE PROPERTY. |
| | UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE |
| | TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS |
| | WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE' |
| | SHALL BE |
| | RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE |
| | RECORDED 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE |
| | 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| | NOT APPLICABLE. |
| | SEE WEBSITE FOR APPLICATION: |
| | HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP |
| | "APPLICATION FOR UNITY OF TITLE" |
| | HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45 |
| | -38-UNITYOFTITLE3.PDF |
| | |
| | 6A-B) COMPLIED. |
| | |
| | 6C) NEW COMMENT/ SEMI NEW, NEW LOCATION, THE EXECUTIVE |
| | LOUNGE HAS BEEN MOVED TO ROOM # 207 THE COMMENTS STILL |
| | EXIST. THE EXECUTIVE LOUNGE HAS A OCCUPANT LOAD OF 73 |
| | THIS IS AN ASSEMBLY OCCUPANCY PLEASE PROVIDE A |
| | FURNATURE LATOUT. SHEET A3.00 DOES NOT INCLUDE THIS |
| | ROOM IN THE PLUMBING FIXTURE COUNT. DEPENDING ON THE |
| | USAGE THIS MAY BE CONSIDERED EIHER AN A2 OR A3, IF |
| | CONSIDERED MORE AS A LOUNGE A-2 THE WATER CLOSET RATIO |
| | WILL BE 1/40 REQUIRING ADDITIONAL FIXTURES. |
| | |
| | 6D) ROOM 207 THE EXECUTIVE LOUNGE, THERE IS A SMALL |
| | ROOM THAT NO INFORMATION HAS BEEN PROVIDED, IS THIS FOR |
| | STORAGE, BAR OR KITCHEN TO BE USED IN CONJUNCTION WITH |
| | THE LOUNGE? FBC-B 302.1. NOTE FBC-B 1014.2 EGRESS |
| | THROUGH INTERVENING SPACES. 4. EGRESS SHALL NOT PASS |
| | THROUGH KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES USED |
| | FOR SIMILAR PURPOSES. |
| | |
| | 7-15) COMPLIED. |
| | |
| | 16) SHEET A4.20 SECTION THRU BUILDING A12.10 : 2010 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION |
| | SHOW COMPLIANCE NOTES ON PLANS QUATING CODE DOES NOT |
| | MEAN COMPLIED. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS SUCH INFORMATION SHALL BE SPECIFIC, AND THE |
| | TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN |
| | PART, NOR SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE |
| | USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION. |
| | 16A NOTES ON THE PLANS INDICATES THE USE OF ALUMINUM |
| | COMPOSITE WALL PANELS, PLEASE PROVIDE DOCUMENTATION FOR |
| | CODE COMPLIANCE WITH: 2010 FBC-B 1407.2 EXTERIOR WALL |
| | FINISH. |
| | MCM USED AS EXTERIOR WALL FINISH OR AS ELEMENTS OF |
| | BALCONIES AND SIMILAR PROJECTIONS AND BAY AND ORIEL |
| | WINDOWS TO PROVIDE CLADDING OR WEATHER RESISTANCE SHALL |
| | COMPLY WITH SECTIONS 1407.4 THROUGH 1407.14. |
| | |
| | 16B) A12.10 DETAILS 1 & 8 BOTH INDICATE THE PERIMETER |
| | SUN SCREEN , DETAIL 3 A12.09 ALSO A CLOSE UP OF THE |
| | PERIMETER SUNSCREEN INDICATE THE USE OF STEEL EMBEDS W/ |
| | NELSON BOLTS PER THE MANUFACTURERS REQUIREMENTS. PLEASE |
| | PROVIDE ENGINEERING FOR THIS SYSTEM THAT THE DESIGN AND |
| | ATTACHMENTS WILL MEET THE WINDLOADS AND HEIGHT |
| | ADJUSTMENT FACTORS FOR THIS ELEVATION, TO BE DESIGNED |
| | TO ASCE 7-10 .1609.1.1 DETERMINATION OF WIND LOADS. |
| | WIND LOADS ON EVERY BUILDING OR STRUCTURE SHALL BE |
| | DETERMINED IN ACCORDANCE WITH CHAPTERS 26 THROUGH 30 OF |
| | ASCE 7 OR THE PROVISIONS OF THE ALTERNATE ALL HEIGHTS |
| | METHOD IN SECTION 1609.6. L |
| | |
| | 17-21) COMPLIED. |
| | |
| | 22A-C) COMPLIED. |
| | |
| | 22D) THE FPL VAULT REQUIRES 3 HR WALLS 2008 NEC THE |
| | DOORS ALSO REQUIRE A 3 HR RATING PER 2008 NEC 450.43(A) |
| | & 2010 FBC-B TABLE 715.4. |
| | |
| | |
| | 23) A5.18: |
| | WALL IDENTIFICATION TAGS ARE MISSING AND IDENTIFICATION |
| | OF FIRE RATED WALLS. ADDITIONAL INFORMATION IS |
| | REQUIRED. SEE LIFE SAFETY PLAN FOR WALL FIRE RATING |
| | DISCREPANCY IN PLANS. 107.2.1.3. |
| | |
| | 24-25) COMPLIED. |
| | |
| | 26) 2ND REQUEST. THE RESPONSE INDICATES THAT THE LINEN |
| | CHUTE DOOR IS IDENTIFIED AS T26. PLEASE REVIEW THE DOOR |
| | SCHEDULE ON A14.01, T26 IS FOR THE ICE ROOM NEXT TO THE |
| | LAUNDRY CHUTE, THAT DOES NOT HAVE ANY DOOR, NOR IS THE |
| | ARK OF A DOOR INDICATED ON THE PLANS. |
| | |
| | SHEET A2.10 SHOWS THE LAUNDRY CHUTE LOCATED ON THE GRID |
| | LINES X.1 JUST NORTH & Y.2 CENTERED ON THE GRID LINE |
| | WHICH IS LOCATED IN THE MAIDS ROOM.FLOORS 10-12 SEE |
| | SHEET A2.11 THE LAUBDRY CHUTE IS OFFSET TO THE |
| | NORTHEAST OR TO THE EAST OF GRID LINE Y.2 . THE PLANS |
| | SHOW THE ACCESS TO THE ACCESS CHUTE DOOR LOCATED WITH |
| | THE CORRADOR. PLEASE CONFORM WITH: |
| | |
| | 2010 FBC-B 708.13.3 REFUSE AND LAUNDRY CHUTE ACCESS |
| | ROOMS. |
| | ACCESS OPENINGS FOR REFUSE AND LAUNDRY CHUTES SHALL BE |
| | LOCATED IN ROOMS OR COMPARTMENTS ENCLOSED BY NOT LESS |
| | THAN 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE |
| | WITH SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED |
| | IN ACCORDANCE WITH SECTION 712, OR BOTH. OPENINGS INTO |
| | THE ACCESS ROOMS SHALL BE PROTECTED BY OPENING |
| | PROTECTIVES HAVING A FIRE PROTECTION RATING OF NOT LESS |
| | THAN 3/4 HOUR. DOORS SHALL BE SELF- OR |
| | AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE IN |
| | ACCORDANCE WITH SECTION 715.4.8.3. |
| | |
| | 27) 2ND REQUEST. SHEET A12.16 SHOWS A NEW DETAIL WITH A |
| | FIRE RISER WITHIN THE 2 HR FIRE RATED CHASE BUT THE |
| | SPRINKLER HEAD DOES NOT PENETRATE INTO THE THE LINEN |
| | CHUTE NOR DOES THERE SHOW HOW THE SPRINKLER HEAD HAS |
| | ACCESSIBILITY FOR MAINTENANCE. |
| | SHEET A7.15 THE LINEN CHUTE DETAILS DO NOT MENTION THE |
| | REQUIREMENT OR ANY ALLOWANCES FOR FIRE SPRINKLERS IN |
| | THE LINEN CHUTE. THE FIRE SPRINKLER SHEETS ONLY PROVIDE |
| | A DEAIL ON FP0.01 INDICATING SERVICE CHUTE DETAIL. |
| | 708.13.6 AUTOMATIC SPRINKLER SYSTEM. |
| | AN APPROVED AUTOMATIC SPRINKLER SYSTEM SHALL BE |
| | INSTALLED IN ACCORDANCE WITH SECTION 903.2.11.2 F] |
| | 903.2.11.2 RUBBISH AND LINEN CHUTES. |
| | AN AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED AT THE |
| | TOP OF RUBBISH AND LINEN CHUTES AND IN THEIR TERMINAL |
| | ROOMS. CHUTES EXTENDING THROUGH THREE OR MORE FLOORS |
| | SHALL HAVE ADDITIONAL SPRINKLER HEADS INSTALLED WITHIN |
| | SUCH CHUTES AT ALTERNATE FLOORS. CHUTE SPRINKLERS SHALL |
| | BE ACCESSIBLE FOR SERVICING. |
| | |
| | THE LAUNDRY CHUTE DETAIL SHEET ALSO DOESN'T MAKE |
| | REFERANCE TO THE REQUIREMENT FOR CHUTE SPRINKLERS SHALL |
| | BE ACCESSIBLE FOR SERVICING. |
| | |
| | 28-32) COMPLIED. |
| | |
| | 33) COMPLIED. 8/07/2014 SIGNED & SEALED ORIGINAL |
| | SUBMITTED BY APPLICANT. |
| | |
| | A DRAFT COPY OF A WIND TUNNEL TEST WAS PROVIDED, THIS |
| | COMMENT WILL STAY UNTIL THEWIND TUNNEL TEST IS A FINAL |
| | VERSION. SHEET S0.00 THE WIND DESIGN CRITERIA IS SHOWN |
| | IN VULT, PLEASE PROVIDE THE PRESSURES IN VASD SINCE ALL |
| | PRODUCT APPROVALS ARE PRINTED IN VASD. |
| | TABLE 1609.3. IS THIS PROJECT GOING TO DO WIND TUNNEL |
| | TESTING TO REDUCE PRESSURES? |
| | |
| | 34) 2ND REQUEST, NOTE UPON WRITTEN REQUEST THIS CODE |
| | ISSUE CAN BE A DEFERRED SUBMITTAL UNDER 107.3.4.2 BUT |
| | THE PRESSURES HAVE TO BE INALLIZED BEFORE PERMIT |
| | ISSUANCE. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 35) 2ND REQUEST, NOTE UPON WRITTEN REQUEST THIS CODE |
| | ISSUE CAN BE A DEFERRED SUBMITTAL UNDER 107.3.4.2 BUT |
| | THE PRESSURES HAVE TO BE INALLIZED BEFORE PERMIT |
| | ISSUANCE. |
| | 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 36) THE SMOKE CONTROL NARRATIVE APPEARS TO HAVE BEEN |
| | PREPARED EARLY ON IN THE DEVELOPMENT OF THE PROJECT. |
| | THERE ARE STATEMENTS WITHIN THE NARRATIVE THAT DO NOT |
| | REFLECT THE ACTUAL CONFIGURATION OF THE BUILDING: |
| | |
| | 36A) PAGE 7 HEADING PRESSURE DIFFERENCES FLOOR TO |
| | FLOOR. THE NARRATIVE STATE THE BASEMENT AND 1ST FLOOR |
| | WILL NOT BE PRESSURIZED DASED ON THE BUILDING |
| | CONFIGURATION THAT ALL STAIRS DISCHARGE TO THE |
| | EXTERIOR. STAIR WELL # 2 BY THE LOBBY DOES NOT LEAD |
| | DIRECTLY TO THE EXTERIOR OF THE BUILDING. |
| | |
| | 36B) PAGE 7 HEADING PRESSURE DIFFERENCES FLOOR TO |
| | FLOOR. THE NARRATIVE STATE THE BASEMENT AND 1ST FLOOR |
| | WILL NOT BE PRESSURIZED DASED ON THE BUILDING |
| | CONFIGURATION THAT ALL STAIRS DISCHARGE TO THE |
| | EXTERIOR. THE NARRATIVE INDICATES TO REVIEW THE NATURAL |
| | METHODS OF POST FIRE SALVAGE OPERATION. PLEASE DIRECT |
| | WHERE THE CODE ALLOWS FOR NATURAL METHODS OF POST FIRE |
| | SALVAGE OPERATION IN LUE OF A ACTIVE SMOKE CONTROL |
| | SYSTEM. |
| | 909.20.3 909.20.3 NATURAL VENTILATION ALTERNATIVE DEALS |
| | STRICTLY WITH THE STAIRWELLS NOT WHOLE FLOORS. |
| | |
| | THE SECOND ISSUE IS WITH THE BASEMENT NOT HAVING |
| | NATURAL VENTILATION AND ALSO USING THE EXIT ACCESS |
| | CORRIDOR TO STORE 25 + SOILED LAUNDRY CARTS WITHIN THE |
| | EXIT ACCESS COORIDOR. SEE EARLIER COMMENT 4A). |
| | |
| | 36C) THIS IS A HIGH RISE BUILDING AND THIS STUDY HAS |
| | NOT SHOWN HOW SMOKE WILL BE REMOVED FROM THE BASEMENT, |
| | 1ST FLOOR, BALLROOMS WITH HIGH CEILINGS AS WELL AS THE |
| | 2 STORY ATRIUM. 909.2 GENERAL DESIGN REQUIREMENTS. |
| | BUILDINGS, STRUCTURES OR PARTS THEREOF REQUIRED BY THIS |
| | CODE TO HAVE A SMOKE CONTROL SYSTEM OR SYSTEMS SHALL |
| | HAVE SUCH SYSTEMS DESIGNED IN ACCORDANCE WITH THE |
| | APPLICABLE REQUIREMENTS OF SECTION 909 AND THE |
| | GENERALLY ACCEPTED AND WELL-ESTABLISHED PRINCIPLES OF |
| | ENGINEERING RELEVANT TO THE DESIGN. THE CONSTRUCTION |
| | DOCUMENTS SHALL INCLUDE SUFFICIENT INFORMATION AND |
| | DETAIL TO ADEQUATELY DESCRIBE THE ELEMENTS OF THE |
| | DESIGN NECESSARY FOR THE PROPER IMPLEMENTATION OF THE |
| | SMOKE CONTROL SYSTEMS. THESE DOCUMENTS SHALL BE |
| | ACCOMPANIED BY SUFFICIENT INFORMATION AND ANALYSIS TO |
| | DEMONSTRATE COMPLIANCE WITH THESE PROVISIONS. |
| | |
| | 36D ) PAGE 12 DEALS WITH THE STAIRWELL SHAFTS THAT WILL |
| | BE PRESSURIZED BY A FANS CONTROLLED BY A VARIABLE SPEED |
| | DRIVE WITH RELIEF VENTS. WILL BE REQUIRED TO BE TESTED |
| | IN ACCORDANCE WITH FBC-B 909.6.2./ 1008.1.2. |
| | |
| | 37) PLEASE PROVIDE CODE COMPLIANCE WITH: 2010 FBC-B [F] |
| | 914.2 EQUIPMENT ROOM IDENTIFICATION. |
| | FIRE PROTECTION EQUIPMENT SHALL BE IDENTIFIED IN AN |
| | APPROVED MANNER. ROOMS CONTAINING CONTROLS FOR |
| | AIR-CONDITIONING SYSTEMS, SPRINKLER RISERS AND VALVES |
| | OR OTHER FIRE DETECTION, SUPPRESSION OR CONTROL |
| | ELEMENTS SHALL BE IDENTIFIED FOR THE USE OF THE FIRE |
| | DEPARTMENT. APPROVED SIGNS REQUIRED TO IDENTIFY FIRE |
| | PROTECTION EQUIPMENT AND EQUIPMENT LOCATION SHALL BE |
| | CONSTRUCTED OF DURABLE MATERIALS, PERMANENTLY INSTALLED |
| | AND READILY VISIBLE. |
| | |
| | 38) EMERGENCY RESPONDER RADIO COVERAGE SHALL BE |
| | PROVIDED IN ALL NEW BUILDINGS IN ACCORDANCE THE FLORIDA |
| | FIRE PREVENTION CODE. |
| | |
| | 39) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B [F] |
| | 911.1.5 REQUIRED FEATURES. THE FIRE COMMAND CENTER |
| | SHALL COMPLY WITH NFPA 72 AND SHALL CONTAIN THE |
| | FOLLOWING FEATURES: 1-17. |
| | |
| | 40) THE SUBMITTED DOCUMENTS FOR 1ST REVIEW DID NOT |
| | PROVIDE DOCUMENTS FOR THE ENERGY CODE FOR COMPLIANCE. |
| | SEE 2010 FBC-ENERGY 103.2.1 & 103.2.3.1.2. |
| | |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |