2014-06-17 17:59:22P B CONVENTION CENTER HILTON HOTEL 1ST PLUMBING REVIEW
 PLUMBING PLAN REVIEW
 PERMIT:14050111
 ADD: 600 OKEECHOBEE BLVD
 CONT: COASTAL CONSTRUCTION
 TEL: (561) 630-3770
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 THE PALM BEACH CONVENTION CENTER HILTON HOTEL
 CONSTRUCTION OF NEW 400 ROOM HOTEL INCLUDING BALLROOMS,
 RESTAURANT(S), MEETING SPACE, POOL DECK AND AMENITIES
  
 1ST REVIEW
 DATE: TUESDAY JUNE 17TH/ 2014
  
 ACTION: DENIED
  
 FUEL GAS: THIS REVIEW IS UNDER A SEPARATE PLAN REVIEW
 STOP, SEE FOR STATUS AND COMMENTS.
  
 1) THE PERMIT DESCRIPTION LISTED ABOVE TO BUILD THE
 HOTEL, POOL, POOL DECK & AMENITIES IS A INCLUSIVE
 PACKAGE WITHIN THE SUBMITTED PLANS. THERE ARE CIVIL,
 SITE, LANDSCAPING, IRRIGATION, GREASE INTERCEPTORS,
 FUEL GAS, GENERATOR, FIRE SPRINKLER, FIRE ALARM,
 LOW-VOLTAGE, AWNINGS AND SIGNAGE PLANS WITHIN THE
 SUBMITTED DOCUMENTS.
 THESE TYPE OF ACTIVITIES REQUIRE A SEPARATE PERMIT
 APPLICATION, REVIEW AND ASSOCIATED FEES. PLEASE BACK
 OUT THE VALUE OF WORK TO BE COMPLETED UNDER EACH OF
 THESE PERMITS SO THE BUILDING DEPARTMENT DOES NOT
 CHARGE YOU TWICE FOR THESE SERVICES. 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 105.1 PERMITS
  
 2) SHEET A3.00 MINIMUM NUMBER OF REQUIRED PLUMBING
 FIXTURES:
  
 2A) HEADING: A-2 OCCUPANCY (BANQUET HALL) GRAND BALL
 ROOM, JR. BALLROOM & MEETING ROOMS ARE FIGURED AT 1/75
 FOR WATER CLOSETS & 1/200 FOR LAVS.
 THE USE OF THESE ROOMS WILL VARY DEPENDING ON THE
 EVENT, EVEN THOUGH THE OCCUPANT LOAD WILL STAY THE SAME
 THE MINIMUM NUMBER OF REQUIRED FIXTURES WILL CHANGE. IF
 IT IS TO BE CONSIDERED A DANCE HALL THE MINIMUM NUMBER
 OF REQUIRED FIXTURES (W.C.) WOULD BE CONSIDERED AT 1/40
 OR IF A EXHIBITION HALL THE WOMEN?S (W. C.) WOULD DROP
 TO 1/65. THE VARIOUS BALLROOMS AND MEETING ROOMS MAY BE
 RENTED OUT BY VARIOUS ORGANIZATIONS WITH DIFFERENT
 EVENT TYPES THIS LOADING FACTOR NEEDS TO BE REFIGURED.
  
 2B) HEADING: POOL AN A4 OCCUPANCY. WITHIN THE CHART THE
 CELL FOR REQUIRED DRINKING FOUNTAIN & SERVICE SINK IS
 STRUCK THROUGH. TABLE 403.1 UNDER THE ASSEMBLY HEADING
 A4 POOLS UNDER THE REQUIRED MINIMUM FIXTURES LIST
 DRINKING FOUNTAINS AND SERVICE SINKS.
  
 2C) HEADING SPORTS BAR & TERRACE A-2 OCCUPANCY
 INDICATES THE LAVS FIGURED AT 1/200, THAT IS FOR
 RESTAURANTS, PLEASE SEE TABLE 403.2 LAVS ARE TO BE
 FIGURED AT 1/40 FOR BARS AND SIMILAR PURPOSES.
  
 2D) HEADING FOR THE FITNESS CENTER IS A BUSINESS
 OCCUPANCY THIS WOULD BE ACCEPTABLE IF THERE IS TO BE A
 INSTRUCTOR THERE ALL THE TIME FOR PERSONAL TRAINING AND
 FITNESS OTHERWISE THIS HEADING SHOULD BE AN A3
 OCCUPANCY FOR A GYM THE OCCUPANT LOAD WOULD CHANGE.
  
 3) SHEET P0.01 BASEMENT LEVEL:
 3A) THE ASSOCIATES CAFETERIA PLUMBING PLAN LIST
 EQUIPMENT AND PLUMBING FIXTURES WITH A C-LABEL. THE
 PLUMBING INDEX LIST SHEET P2.01 AS THE BANQUET KITCHEN
 & ASSO. CAFE SCHEDULE, THERE ARE NO C EQUIPMENT ON THIS
 LIST ALL FIXTURES & EQUIPMENT ON THIS SHEET ARE LISTED
 WITH A Q. I CAN'T IDENTIFY THE TYPE OF EQUIPMENT FOR
 THE TYPE OR WASTE REQUIRED. NOTE # 10 REFERS TO GREASY
 WASTE FOR THIS SHEET BUT NOT IDENTIFIED ON THE PLAN.
  
 3B)(1) SHEET P0.01 THE BASEMENT LEVEL WITHIN THE ACTIVE
 LINEN STORAGE ROOM THERE IS A SUMP PIT, NOTE # 1
 INDICATES SEE DETAIL SHEET P4.01 FOR SANITARY LIFT
 STATION. THE DETAIL SHOWS THE 2" DISCHARGE PIPE
 VERTICALLY THEN MAKING A 90 DEGREE TURN BENEATH THE
 SLAB, THERE INSTALLED A FLANGED CHECK VALVE FOR EACH
 PUMP AND A FLANGED GATE VALVE (1) FOR EACH PUMP. PLEASE
 SEE SECTION FBC-P 712.2 FOR REQUIRED COMPLIANCE.
 2010 FBC-PLUMBING 712.2 VALVES REQUIRED.
 A CHECK VALVE AND A FULL OPEN VALVE LOCATED ON THE
 DISCHARGE SIDE OF THE CHECK VALVE SHALL BE INSTALLED IN
 THE PUMP OR EJECTOR DISCHARGE PIPING BETWEEN THE PUMP
 OR EJECTOR AND THE GRAVITY DRAINAGE SYSTEM. ACCESS
 SHALL BE PROVIDED TO SUCH VALVES. SUCH VALVES SHALL BE
 LOCATED ABOVE THE SUMP COVER REQUIRED BY SECTION 712.1
 OR, WHERE THE DISCHARGE PIPE FROM THE EJECTOR IS BELOW
 GRADE, THE VALVES SHALL BE ACCESSIBLY LOCATED OUTSIDE
 THE SUMP BELOW GRADE IN AN ACCESS PIT WITH A REMOVABLE
 ACCESS COVER.
  
 3B)(2) SHEET P0.01 THE BASEMENT LEVEL WITHIN THE ACTIVE
 LINEN STORAGE ROOM THERE IS A SUMP PIT, NOTE # 1
 INDICATES SEE DETAIL SHEET P4.01 FOR SANITARY LIFT
 STATION. THE DETAIL OF THE LIFT STATION ALSO DOES NOT
 PROVIDE ANY DETAILS ON THE ACCESS COVER, SIZE,
 THICKNESS OF COVER, TYPE OF MATERIAL OR HOW ACCESS
 COVER WILL BE ATTACHED TO THE FLOOR, OR HOW THE COVER
 WILL BE ACCESSIBLE FOR MAINTENANCE.
 2010 FBC-P 712.3.2 SUMP PIT.
 THE SUMP PIT SHALL BE NOT LESS THAN 18 INCHES (457 MM)
 IN DIAMETER AND 24 INCHES (610 MM) DEEP, UNLESS
 OTHERWISE APPROVED. THE PIT SHALL BE ACCESSIBLE AND
 LOCATED SUCH THAT ALL DRAINAGE FLOWS INTO THE PIT BY
 GRAVITY. THE SUMP PIT SHALL BE CONSTRUCTED OF TILE,
 CONCRETE, STEEL, PLASTIC OR OTHER APPROVED MATERIALS.
 THE PIT BOTTOM SHALL BE SOLID AND PROVIDE PERMANENT
 SUPPORT FOR THE PUMP. THE SUMP PIT SHALL BE FITTED WITH
 A GAS-TIGHT REMOVABLE COVER ADEQUATE TO SUPPORT
 ANTICIPATED LOADS IN THE AREA OF USE.
  
 3B)(3) SHEET P0.01 THE BASEMENT LEVEL WITHIN THE ACTIVE
 LINEN STORAGE ROOM THERE IS A SUMP PIT, NOTE # 1
 INDICATES SEE DETAIL SHEET P4.01 FOR SANITARY LIFT
 STATION. THE PLUMBING SHEET P0.01 NOR HAS THIS DETAIL
 P4.01 PROVIDED THE TOTAL DRAINAGE FIXTURE UNITS/
 GALLONS PER MINUTE OF WASTE THAT IS TO DRAIN INTO THE
 SANITARY LIFT STATION. PLEASE PROVIDE THIS DATA TO SEE
 THAT THE SPECKED PUMPS WILL MEET THE DEMAND AND PROVIDE
 COMPLIANCE WITH 2010 FBC-P 712.4.2 CAPACITY.
 712.4.2 CAPACITY.
 A SEWAGE PUMP OR SEWAGE EJECTOR SHALL HAVE THE CAPACITY
 AND HEAD FOR THE APPLICATION REQUIREMENTS. PUMPS OR
 EJECTORS THAT RECEIVE THE DISCHARGE OF WATER CLOSETS
 SHALL BE CAPABLE OF HANDLING SPHERICAL SOLIDS WITH A
 DIAMETER OF UP TO AND INCLUDING 2 INCHES (51 MM). OTHER
 PUMPS OR EJECTORS SHALL BE CAPABLE OF HANDLING
 SPHERICAL SOLIDS WITH A DIAMETER OF UP TO AND INCLUDING
 1 INCH (25.4 MM). THE MINIMUM CAPACITY OF A PUMP OR
 EJECTOR BASED ON THE DIAMETER OF THE DISCHARGE PIPE
 SHALL BE IN ACCORDANCE WITH TABLE 712.4.2.
  
 3B)(4) SHEET P1.03 LEVEL 1 AREA Q3 IS WHERE THE LIFT
 STATION TIES INTO THE BUILDING DRAIN, NOTE # 29
 IDENTIFIES THE WASTE LINE. HERE THERE IS 2 ISSUES, THE
 CONNECTION OF THE DISCHARGE PIPING IS TO OCCUR EITHER
 TO THE BUILDING SEWER OR TO A WYE FITTING IN THE
 BUILDING DRAIN. THE CONNECTION TO THE BUILDING DRAIN,
 WYE FITTING MUST BE A MINIMUM OF 10 FEET AWAY FROM
 OTHER PIPE CONNECTIONS OR FIXTURES TO REDUCE THE
 LIKELIHOOD THAT DISCHARGE FROM THE PUMP/ EJECTOR WILL
 INTERFERE WITH THE GRAVITY FLOW IN THE DRAINAGE SYSTEM.
  
 THERE IS A 2 INCH HUB DRAIN CONNECTION WITHIN THE 2"
 DISCHARGE LINE OF THE SUMP/ EJECTOR PIPING SYSTEM, THIS
 2 INCH HUB DRAIN WILL NEED TO TIE INTO BUILDING DRAIN
 LINE DIRECTLY.
  
 THE 2ND ISSUE IS THERE IS ANOTHER 2 INCH HUB DRAIN LINE
 THAT TIES INTO THE BUILDING DRAIN LINE WITHIN THE 10
 FEET WHERE THE SUMP/ EJECTOR PUMP IS TYING INTO THE
 BUILDING DRAIN LINE. WHEN VIEWING WHERE AND HOW THE
 SUMP/ EJECTOR PUMP DISCHARGE INTO THE BUILDING DRAIN IT
 IS DEPICTED AS THE WYE ON ITS SIDE. SEE 2010 FBC-P
 712.3.5 EJECTOR CONNECTION TO THE DRAINAGE SYSTEM.
 PUMPS CONNECTED TO THE DRAINAGE SYSTEM SHALL CONNECT TO
 THE BUILDING SEWER OR SHALL CONNECT TO A WYE FITTING IN
 THE BUILDING DRAIN A MINIMUM OF 10 FEET (3048 MM) FROM
 THE BASE OF ANY SOIL STACK, WASTE STACK OR FIXTURE
 DRAIN. WHERE THE DISCHARGE LINE CONNECTS INTO
 HORIZONTAL DRAINAGE PIPING, THE CONNECTOR SHALL BE MADE
 THROUGH A WYE FITTING INTO THE TOP OF THE DRAINAGE
 PIPING.
  
 3C) SHEET P0.01 THE BASEMENT LEVEL WITHIN THE ACTIVE
 LINEN STORAGE ROOM AT THE THREE COMMERCIAL WASHING
 MACHINES THERE IS NO DRAINAGE, NO TRENCH DRAIN, ONLY A
 3 INCH FLOOR DRAIN. PLEASE PROVIDE THE MANUFACTURERS
 SPECS ON THE COMMERCIAL CLOTHES WASHERS, WILL THEY BE A
 GRAVITY DRAIN OR PUMP, IF PUMP WHAT WILL THE GPM FLOW
 BE? WILL THESE UNITS BE USING A TRENCH DRAIN? SHOW
 COMPLIANCE WITH
 2010 FBC-PLUMBING 406.3 WASTE CONNECTION. TABLE 709.1
 COMMERCIAL FOOTNOTES (A & G).
  
 3D) SHEET P0.01 THE BASEMENT LEVEL WITHIN THE SERVICE
 ELEVATOR B016 THE PLANS DO NOT SHOW A SUMP PUMP DETAIL
 AS DOES THE SERVICE ELEVATOR ST4B NOTE # 9 PROVIDES
 DETAILS ON P4.01.
 2010 FBC-P 1003.4 OIL SEPARATORS REQUIRED. AT REPAIR
 GARAGES, CAR-WASHING FACILITIES, AT FACTORIES WHERE
 OILY AND FLAMMABLE LIQUID WASTES ARE PRODUCED AND IN
 HYDRAULIC ELEVATOR PITS, SEPARATORS SHALL BE INSTALLED
 INTO WHICH ALL OIL-BEARING, GREASE-BEARING OR FLAMMABLE
 WASTES SHALL BE DISCHARGED BEFORE EMPTYING INTO THE
 BUILDING DRAINAGE SYSTEM OR OTHER POINT OF DISPOSAL.
  
 3E) SHEET P0.01 THE BASEMENT LEVEL NOTE # 2 A/C
 CONDENSATE DRAIN PIPE TO RUN BELOW BASEMENT SLAB, SIZE
 IS NOT PROVIDED, NOTE THIS PIPE IS SHOWN ON THE FLOOR
 PLANS TO DRAIN INTO THE SUMP PIT WHERE AS IT IS NOT
 SHOWN ON THE DETAIL OF THE SUMP PIT, NOTE SURE AT WHAT
 LEVEL IT WILL DISCHARGE INTO THE SUMP PIT.
 THE OTHER ISSUE IS A/C CONDENSATE DUMPING INTO THE CITY
 SEWER. WEST PALM BCH MUNI CODE SEC. 90-126
 PROHIBITIONS & LIMITATIONS OF DISCHARGE (A)GENERALLY.
 USERS SHALL NOT DISCHARGE POLLUTANTS INTO THE WWF
 UNLESS IN ACCORDANCE WITH THIS ARTICLE.
 (5)STORM WATER, SURFACE WATER, GROUNDWATER, ARTESIAN
 WELL WATER, ROOF RUNOFF, SUBSURFACE DRAINAGE, SWIMMING
 POOL DISCHARGES, UNCONTAMINATED COOLING WATER,
 UNPOLLUTED INDUSTRIAL PROCESS WATERS, AIR CONDITIONING
 CONDENSATE, UNLESS SPECIFICALLY AUTHORIZED BY THE CITY
 IN WRITING.
  
 3F) FOUND, NO COMMENT.
  
 3G) SHEET P0.01 THE BASEMENT LEVEL/ POOL EQUIPMENT ROOM
 NOTE #10 INDICATES THE USE OF A SUMP PUMP TO PUMP THE
 POOL BACK WASH TO SANITARY, THERE IS NO PIT SHOWN ON
 THE PLANS, NOR IS THERE A NOTE PROVIDING DETAILS SIZE
 OF PUMP OR DISCHARGE REQUIRED. SUMPS ARE TO COMPLY WITH
 2010 FBC-P 712.
  
 3H) NOTE THE POOL EQUIPMENT ROOM IS MISSING A HOSE BIBB
 PER SECTION 2010 FBC-B 424.1.5.9.
  
 4) SHEET P1.01 LEVEL 1 AREA Q1: NOTE OUTSIDE OF THE
 POOL STORAGE EQUIPMENT ROOM THERE IS DEPICTED HOSE BIBB
 PLEASE INDICATE WHERE COMPLIANCE WITH SECTION 2010
 FBC-B 424.1.6.2 RINSE SHOWER CAN BE FOUND?
  
 5) SHEET P1.02 LEVEL 1 AREA Q2:
  
 5A) SHEET P1.02 LEVEL 1 AREA Q2, NOTE# 35 INDICATES CAN
 WASH SEE P4.01 CAN WASH DETAIL:
 5A) (1) THE SIDE ELEVATION SECTION AND FRONT ELEVATION,
 THERE ARE QUESTIONS, NOTE # 5 INDICATES THE HOT WATER
 TO THE CAN WASH WILL BE 180 DEGREES BUT NOTE 4
 INDICATES HOSE BIBB NIBCO- SCOTT 760 (W/ CREST WASHER -
 100 DEGREES. THE SIDE VIEW OF THE HOSE BIBBS AND FRONT
 VIEW IT APPEARS THERE WILL BE TO INDEPENDENT HOSE BIBBS
 WHERE WATER CANNOT MIX AS IF IT WERE GOING THROUGH A
 MIXING VALVE, WATER HOTTER THAN 140 DEGREES WILL NEED
 TO COMPLY WITH:
 2010 FBC-P 701.7 CONNECTIONS.
 DIRECT CONNECTION OF A STEAM EXHAUST, BLOWOFF OR DRIP
 PIPE SHALL NOT BE MADE WITH THE BUILDING DRAINAGE
 SYSTEM. WASTEWATER WHEN DISCHARGED INTO THE BUILDING
 DRAINAGE SYSTEM SHALL BE AT A TEMPERATURE NOT HIGHER
 THAN 140?F (60?C). WHEN HIGHER TEMPERATURES EXIST,
 APPROVED COOLING METHODS SHALL BE PROVIDED.
  
 5B) SHEET P1.02 LEVEL 1 AREA Q2, NOTE# 21 INDICATES A
 NEW 750 GALLON CONCRETE VAULT TYPE GREASE INTERCEPTOR,
 NOTE 36 SEE SHEET P3.01D FOR THE CONTINUATION OF GREASY
 WASTE. PLEASE PROVIDE THE SIZING CALCULATIONS FOR THE
 CONCRETE VAULT TYPE GREASE INTERCEPTOR,
 SIZING IS TO BE IN ACCORDANCE WITH 2010 FBC-P SECTION
 1003.5.1 AND TABLE 1003.5.1.
  
 5C) SHEET P1.02 LEVEL 1 AREA Q2, NOTES 22-25 DEALS WITH
 FUEL LINES, PLEASE NOTE DIRECTLY ABOVE THE NEXT STORY
 IS THE DIESEL EMERGENCY GENERATOR. DIESEL, FUEL TANKS
 AND ASSOCIATED LINES WILL BE REVIEWED BY THE MECHANICAL
 REVIEWER AND INSPECTED BY THE MECHANICAL INSPECTOR.
 DETAIL P4.04.
  
 6) SHEET P1.03 LEVEL 1 AREA Q3. SHEET P1.03 LEVEL 1
 AREA Q3, NOTE# 01 INDICATES A NEW 1,250 GALLON CONCRETE
 VAULT TYPE GREASE INTERCEPTOR, NOTE REFERS TO SHEET
 P4.03 THE GREASE INTERCEPTOR DETAIL. SHEET P3.00
 INDICATES 132 FU DRAINING INTO THE GREASE INTERCEPTOR.
 IF SIZING USING TABLE 1003.3.4.1 THIS TABLE IS TO BE
 USED WHEN THE DESIGN IS FOR HYDRO MECHANICAL GREASE
 INTERCEPTORS.
 PLEASE PROVIDE THE SIZING CALCULATIONS FOR THE CONCRETE
 VAULT TYPE GREASE INTERCEPTOR, SIZING IS TO BE IN
 ACCORDANCE WITH 2010 FBC-P SECTION 1003.5.1 AND TABLE
 1003.5.1.
  
 7) SHEET P1.04 LEVEL 1 AREA Q4. KITCHEN 105 , NO GREASY
 WASTE IS SHOWN ON THE PLANS, NOTE # 15 INDICATES SEE
 P2.04 FOR CONTINUATION. THIS SHEET IS A EQUIPMENT
 SCHEDULE, PLEASE PROVIDE A GREASY WASTE ISOMETRIC OR
 WHERE TO LOCATE SUCH PLANS. PLEASE PROVIDE THE SIZING
 CALCULATIONS FOR THE CONCRETE VAULT TYPE GREASE
 INTERCEPTOR, SIZING IS TO BE IN ACCORDANCE WITH 2010
 FBC-P SECTION 1003.5.1 AND TABLE 1003.5.1.
  
 8) SHEET P1.06 NOTE # 15 INDICATES 3 ELECTRIC WATER
 HEATERS FOR USE IN THE KITCHEN THIS IS REVISION 4.5 IS
 THIS PART OF A REVISION FOUND IN THE GAS PLAN REVISION
 3.5 WHERE THERE IS A DISCREPANCY IN THE AMOUNT OF
 BOILERS FOR THE KITCHEN AND BTU'S.
  
 9) SHEET P3.04 RWL # 2. WITH THE 4 " ROOF DRAIN 1106 S.
 F. BEING ADDED TO THE HORIZONTAL LOAD OF2597 SQ FT
 TABLE 1106.3/ 1 % SLOPE . WILL REQUIRE 5 " HORIZONTAL
 DRAIN PIPE. WHEN 4 " RD 739 S F IS ADDED, THE LOAD IS
 3336 S F / 1 % SLOPE, A 6 IN HORIZONTAL PIPE WILL BE
 REQUIRED.
  
 10) SHEET P3.05:
 10A) SHEET P3.05 (MARK UP # 1) THE COMBINED SQUARE
 FOOTAGE OF RWL 15 & 16 = 1748 OVER THE 1652 SQ FT @ 4.5
 IN/ 100 YR RAIN OF 1652 IF USING 1% SLOPE? SLOPE NOT
 INDICATED. 2010 FBC-P TABLE 1106.3.
  
 10B) SHEET P3.05 (MARK UP # 2) THE COMBINED SQUARE
 FOOTAGE OF RWL UNKNOWN NOT MARKED & 17 = 2254 OVER THE
 1652 SQ FT @ 4.5 IN/ 100 YR RAIN OF 1652 IF USING 1%
 SLOPE? SLOPE NOT INDICATED. 2010 FBC-P TABLE 1106.3.
  
 11) SHEET P3.09 (MARK UP # 1) THE 2 X 770 S F= 1540 S F
 + 603 S F+2143 SQ FT, OVER THE ALLOWED 1652 SQ FT @ 4.5
 IN/ 100 YR RAIN OF 1652 IF USING 1% SLOPE? SLOPE NOT
 INDICATED. 2010 FBC-P TABLE 1106.3.
  
 12) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  