Plan Review Notes
Plan Review Notes For Permit 14050111
Permit Number 14050111
Review Stop M
Sequence Number 1
Notes
Date Text
2014-06-27 09:30:12PLAN DENIED
 1) REFER TO SECTION 506.3.12.2 TERMINATION THROUGH AN
 EXTERIOR WALL.
 2010 FBC (M) (FOR HOOD EXHAUST)
 2) REFER TO SECTION 607 DUCT AND TRANSFER OPENING. WHAT
 TYPE OF
 PROTECTION OF DUCT PENETRATION ARE USED FOR MEETING
 ROOMS AND SUITES
 2ED LEVEL AND UP 2010 FBC (M)
 3) PROVIDEE DRYER MANUFACTURERS INSTRUCTIONS WITH THE
 PLANS PER
 SECTION 504.7 COMMERCIAL CLOTHES DRYER. 2010 FBC (M)
 REFER TO DRYER BOOSTER FAN DETAIL.
 4) PLEASE MOVE THE DIESEL FUEL PIPING ISOMETRIC TO THE
 MECHANICAL PLAN
 PER SECTION 1301 FBC (M)
 5) PROVIDE AN ISOMETRIC OF THE GENERATOR EXHAUST ON THE
 MECHANICAL PLAN.
 PER SECTION 510 FBC (M)
 6) PROVIDE STATIC PRESSURE OF AIR CONDITIONING SYSTEMS
 ON THE PLAN.
 PROVID A DETAIL ON THE TYPE OF DUCT REINFORCEMENT
 REQUIRED ON THE PLAN.
 CHAPTER 2 SMACNA
  