| 2014-06-27 09:30:12 | PLAN DENIED | | | 1) REFER TO SECTION 506.3.12.2 TERMINATION THROUGH AN | | | EXTERIOR WALL. | | | 2010 FBC (M) (FOR HOOD EXHAUST) | | | 2) REFER TO SECTION 607 DUCT AND TRANSFER OPENING. WHAT | | | TYPE OF | | | PROTECTION OF DUCT PENETRATION ARE USED FOR MEETING | | | ROOMS AND SUITES | | | 2ED LEVEL AND UP 2010 FBC (M) | | | 3) PROVIDEE DRYER MANUFACTURERS INSTRUCTIONS WITH THE | | | PLANS PER | | | SECTION 504.7 COMMERCIAL CLOTHES DRYER. 2010 FBC (M) | | | REFER TO DRYER BOOSTER FAN DETAIL. | | | 4) PLEASE MOVE THE DIESEL FUEL PIPING ISOMETRIC TO THE | | | MECHANICAL PLAN | | | PER SECTION 1301 FBC (M) | | | 5) PROVIDE AN ISOMETRIC OF THE GENERATOR EXHAUST ON THE | | | MECHANICAL PLAN. | | | PER SECTION 510 FBC (M) | | | 6) PROVIDE STATIC PRESSURE OF AIR CONDITIONING SYSTEMS | | | ON THE PLAN. | | | PROVID A DETAIL ON THE TYPE OF DUCT REINFORCEMENT | | | REQUIRED ON THE PLAN. | | | CHAPTER 2 SMACNA | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | | | | |
|