| 2014-05-07 08:31:54 | 600 OKEECHOBEE BOULEVARD - HIGH RISE HOTEL |
| | PERMIT #14050111 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | NOTE: ALL FIRE REVIEW COMMENTS REFERENCE NFPA 101 REFER |
| | TO NFPA 101-THE LIFE SAFETY CODE (2009 EDITION WITH |
| | FLORIDA AMENDMENTS). |
| | |
| | |
| | SHEET A2.02: FITNESS (#104) IS USING AN OCCUPANT LOAD |
| | FACTOR OF 100 SQUARE FEET PER PERSON. EXERCISE ROOMS |
| | WITH EQUIPMENT OR WITHOUT EQUIPMENT SHALL USE AN |
| | OCCUPANT LOAD FACTOR OF 15 SQUARE FEET PERSON OR 50 |
| | SQUARE FEET PERSON RESPECTIVELY PER TABLE 7.3.1.2. |
| | PROVIDE AN EQUIPMENT LAYOUT. |
| | |
| | SHEET A2.02: A DELUGE SPRINKLER SYSTEM IS INDICATED TO |
| | PROTECT THE CONNECTOR AND ACHIEVE AN EQUIVALENT 2-HOUR |
| | FIRE RATED ENCLOSURE. TO MY KNOWLEDGE, THERE IS NOT A |
| | LISTED DELUGE SYSTEM CAPABLE OF ACHIEVING THIS FIRE |
| | RESISTANCE RATING. A MORE APPROPRIATE DESIGN MAY |
| | INCLUDE THE USE OF THE TYCO WIINDOW SPRINKLERS. IF THE |
| | DESIGN INTENT IS TO USE TYCO WINDOW SPRINKLERS TO |
| | ACHIEVE UP TO A TWO-HOUR FIRE RATED SEPARATION, THE |
| | SPRINKLERS MUST BE INSTALLED ACCORDING TO THE UL |
| | LISTING DATA AND SHALL WET THE ENTIRE GLAZING SURFACE. |
| | SPRINKLERS CANNOT BE USED TO PROTECT OPERABLE DOORS OR |
| | WINDOWS. THE WINDOW SPRINKLERS DO NOT ALLOW HORIZONTAL |
| | WINDOW MULLIONS AND REQUIRE THE GLASS CURTAIN WALL TO |
| | BE ATTACHED TO A THREE FOOT HIGH PONY WALL TO KEEP |
| | COMBUSTIBLE MATERIALS AT LEAST TWO INCHES AWAY FROM THE |
| | GLAZING. PAY SPECIAL ATTENTION TO THE GLAZING ASSEMBLY |
| | AS THE SPRINKLER POSITIONING VARIES FOR BUTT-GLAZED |
| | INSTALLATIONS COMPARED TO VERTICAL MULLION |
| | INSTALLATIONS. VERTICAL MULLIONS SHALL BE OF A DEPTH |
| | THAT PREVENTS COLD SOLDERING OF ADJACENT SPRINKLERS. |
| | THE SPRINKLER DESIGN SHOULD INDICATE WHICH WINDOW |
| | SPRINKLER MODEL WILL BE USED (HORIZONTAL SIDEWALL OR |
| | PENDENT VERTICAL SIDEWALL). |
| | |
| | SHEET A2.03: THE TWO STORY OPENING (PRE-FUNCTION #221) |
| | SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 8.6 FOR |
| | VERTICAL OPENINGS AS EITHER A "COMMUNICATING SPACE", |
| | "ATRIUM" OR " CONVENIENCE OPENING." FOR EXAMPLE, A |
| | COMMUNICATING SPACE REQUIRES THE ENTIRE FLOOR AREA TO |
| | BE OPEN AND UNOBSTRUCTED SUCH THAT A FIRE IN ANY PART |
| | OF THE SPACE WILL BE READILY OBVIOUS TO THE OCCUPANTS |
| | OF THE SPACE PRIOR TO THE TIME A FIRE BECOMES A HAZARD. |
| | ANOTHER EXAMPLE, A CONVENIENCE OPENING REQUIRES THAT |
| | THE FLOOR OPENING BE SEPARATED FROM EXIT ACCESS |
| | CORRIDORS. |
| | |
| | SHEET A2.03: THE PLAN SHOWS THE 1-HOUR FIRE RATING |
| | CROSSING THE CORRIDOR AT DOOR #221A; HOWEVER, THERE IS |
| | NO 1-HOUR FIRE RATING INDICATED FOR THE WALL CROSSING |
| | THE CORRIDOR AT DOOR #221B. ALSO THE DOOR SCHEDULE |
| | (SHEET A14.01) DOES NOT INDICATE A FIRE RATING FOR |
| | EITHER SET OF DOORS. |
| | |
| | SHEET A3.0: PROVIDE DIRECT ACCESS INTO THE FIRE PUMP |
| | ROOM (B003) FROM THE CORRIDOR WITHOUT HAVING TO TRAVEL |
| | THROUGH THE DOMESTIC PUMP ROOM (B002) FIRST. |
| | |
| | SHEET A3.01: STAIR #2 TERMINATES INSIDE THE BUILDING |
| | WHICH IS PERMITTED BY SECTION 28.2.7.2; HOWEVER, THE |
| | TRAVEL DISTANCE FROM THE TERMINATION OF THE EXIT |
| | ENCLOSURE TO AN EXTERIOR EXIT DOOR LEADING TO A PUBLIC |
| | WAY SHALL NOT EXCEED 100 FEET. |
| | |
| | SHEET A4.01: CONNECTOR DOORS (#156-#156F & 118A) |
| | INDICATE THE USE OF TEMPERED GLASS. DOOR GLAZING WILL |
| | NEED TO BE FIRE RATED AS SPRINKLERS ARE NOT LISTED TO |
| | PROTECT OPERABLE DOOR/WINDOW GLAZING AND PROVIDE AN |
| | EQUIVALENT FIRE RATING. |
| | |
| | SHEET A4.01: THE LIFE SAFETY PLAN (SHEET A2.02) |
| | INDICATES A TWO-HOUR WALL RATING AROUND STAIR #6; |
| | HOWEVER, THE DOOR SCHEDULE (SHEET A14.00) DOES NOT |
| | INDICATE A DOOR FIRE RATING OR CLOSER. |
| | |
| | SHEET A4.01: THE LIFE SAFETY PLAN (SHEET A2.02) |
| | INDICATES A ONE-HOUR WALL RATING AROUND POOL STORAGE |
| | #126; HOWEVER, THE DOOR SCHEDULE (SHEET A14.00) DOES |
| | NOT INDICATE A DOOR FIRE RATING OR CLOSER. |
| | |
| | SHEET A4.01: THE LIFE SAFETY PLAN (SHEET A2.02) |
| | INDICATES A ONE-HOUR WALL RATING AROUND PARTITION |
| | STORAGE #121N; HOWEVER, THE DOOR SCHEDULE (SHEET |
| | A14.00) DOES NOT INDICATE A DOOR FIRE RATING OR CLOSER |
| | FOR DOORS #121N AND #121O. |
| | |
| | SHEET A4.01: THE LIFE SAFETY PLAN (SHEET A2.02) |
| | INDICATES A ONE-HOUR WALL RATING AROUND PARTITION |
| | STORAGE #121L; HOWEVER, THE DOOR SCHEDULE (SHEET |
| | A14.00) DOES NOT INDICATE A DOOR FIRE RATING OR CLOSER |
| | FOR DOORS #121L. |
| | |
| | SHEET A4.04: DOOR #103C IN CORRIDOR #103C IS MISSING |
| | PANIC HARDWARE IN DOOR SCHEDULE (SHEET A14.00). |
| | |
| | SHEET A4.04: DOOR #104 IN FITNESS #104 IS MISSING PANIC |
| | HARDWARE IN THE DOOR SCHEDULE (SHEET A14.00). OCCUPANT |
| | LOAD WILL EXCEED 100 PERSONS IN THE FITNESS ROOM ONCE |
| | THE APPROPRIATE OCCUPANT LOAD FACTOR IS APPLIED. |
| | EXITING STAIR #2 AND THEN TRAVELING THROUGH THE HOTEL |
| | LOBBY EXCEEDS 100 FEET. ADDITIONALLY THIS PATH OF |
| | TRAVEL IS NOT OBVIOUS AND DIRECT. |
| | |
| | LEVEL 100: THE OVERALL LIFE SAFETY EXITING CONCEPT |
| | NEEDS TO BE COORDINATED WITH THE ELECTRICAL DRAWINGS |
| | REGARDING THE PLACEMENT OF EXIT SIGNAGE. FOR EXAMPLE, |
| | SHEET E1-09 SHOWS EXIT SIGNS AT DOORS #100E AND #106B |
| | LEADING TO THE BAR TERRACE. HOW ARE OCCUPANTS BEING |
| | DIRECTED TO THE PUBLIC WAY ONCE THEY ENTER THE BAR |
| | TERRACE AREA? DOOR #100E IS NOT EQUIPPED WITH PANIC |
| | HARDWARE. ADDITIONALLY AN EXIT SIGN HAS BEEN PLACED AT |
| | DOOR #105A LEADING BAR OCCUPANTS THROUGH THE KITCHEN |
| | AREA TO REACH AN EXIT. |
| | |
| | SHEET A4.06 (STAIR #3/BOILER ROOM #229/ELECTRICAL |
| | #224): PER SECTION 28.3.2.1 ALL ROOMS CONTAINING |
| | HIGH-PRESSURE BOILERS, TRANSFORMERS OR OTHER SERVICE |
| | EQUIPMENT SUBJECT TO POSSIBLE EXPLOSION SHALL NOT BE |
| | LOCATED DIRECTLY ADJACENT TO EXITS. |
| | |
| | SHEET A4.07: LEVEL 200 HAS ASSEMBLY USE ROOMS WITH |
| | OCCUPANT LOADS EXCEEDING 100 PERSONS. THE EXIT ACCESS |
| | DOORS FROM THESE ROOMS ARE EQUIPPED WITH PANIC/FIRE |
| | EXIT HARDWARE; HOWEVER, THE OTHER EXIT ACCESS DOORS ON |
| | THE FLOOR ARE NOT EQUIPPED WITH PANIC/FIRE EXIT |
| | HARDWARE SUCH AS DOOR T08, 219, 219A, 221A, 221B, & |
| | 223. PER SECTION 6.1.14.1.2, WHERE EXIT ACCESS FROM AN |
| | OCCUPANCY TRAVERSES ANOTHER OCCUPANCY, THE MULTIPLE |
| | OCCUPANCY SHALL BE TREATED AS A MIXED OCCUPANCY AND THE |
| | MOST STRINGENT FIRE AND LIFE SAFETY REQUIREMENTS OF |
| | EACH OCCUPANCY SHALL APPLY TO THE BUILDING. |
| | |
| | SHEET A4.07: THE SERVICE ELEVATOR LOBBY (ALL FLOORS) |
| | INDICATES AN EXIT ACCESS DOOR (#219) WITH A CARD |
| | READER. A CARD READER ON THE EGRESS SIDE IS NOT |
| | PERMITTED AS THIS REQUIRES SPECIAL KNOWLEDGE AND A TOOL |
| | TO GAIN ACCESS TO AN EXIT. |
| | |
| | SHEET A4.07 - DOOR T12 (SUITES #204 & #205): PER |
| | SECTION 28.3.7.2, IN BUILDINGS PROTECTED THROUGHOUT BY |
| | AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM, |
| | EACH HOTEL GUEST ROOM, INCLUDING GUEST SUITES SHALL BE |
| | SEPARATED FROM OTHER GUEST ROOMS BY WALLS AND FLOORS |
| | CONSTRUCTED AS FIRE BARRIERS HAVING A MINIMUM 1/2-HOUR |
| | FIRE RESISTANCE RATING. DOORS IN THE FIRE BARRIERS |
| | SHALL HAVE A FIRE RESISTANCE RATING OF NOT LESS THAN |
| | 20-MINUTES AND SHALL NOT BE REQUIRED TO BE |
| | SELF-CLOSING. |
| | |
| | SHEET A4.08: PER SECTION 28.3.7.2, IN BUILDINGS |
| | PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED |
| | AUTOMATIC SPRINKLER SYSTEM, EACH HOTEL GUEST ROOM, |
| | INCLUDING GUEST SUITES SHALL BE SEPARATED FROM OTHER |
| | GUEST ROOMS BY WALLS AND FLOORS CONSTRUCTED AS FIRE |
| | BARRIERS HAVING A MINIMUM 1/2-HOUR FIRE RESISTANCE |
| | RATING. DOORS IN THE FIRE BARRIERS SHALL HAVE A FIRE |
| | RESISTANCE RATING OF NOT LESS THAN 20-MINUTES AND SHALL |
| | NOT BE REQUIRED TO BE SELF-CLOSING. APPLIES TO SEVERAL |
| | SUITES INCLUDING SUITES, #235, #240, #247 ETC. CHECK |
| | OTHER FLOORS AS WELL. ALSO NO DOOR TAGS PROVIDED FOR |
| | DOORS COMMUNICATING BETWEEN TWO ROOMS SUCH AS SUITE |
| | #240 AND SUITE #247. |
| | |
| | SHEET A4.19: EXECUTIVE LOUNGE #1136 APPEARS TO BE AN |
| | ASSEMBLY USE ROOM; HOWEVER, NO PANIC HARDWARE IS SHOWN |
| | ON DOORS #1136 OR #1136D. |
| | |
| | GENERAL: PROVIDE ADDITIONAL INFORMATION ON THE PROPOSED |
| | GAS FIRED PIT LOCATED NEAR THE OPEN SKY TERRACE/BAR. |
| | SHEET E1-05 REFERENCES A GAS FIRED PIT CONTROLLER, BUT |
| | NO OTHER DESIGN INFORMATION WAS FOUND. |
| | |
| | SHEET M1-00: COULD NOT OPEN DRAWING. FILE CONSISTENTLY |
| | CRASHES COMPUTER. |
| | |
| | SHEET M1-04: KITCHEN #105 EXHAUST LOUVER FROM EXHAUST |
| | FAN #3 (WALL TERMINATION) APPEARS TO BE WITHIN 10 FEET |
| | OF OPERABLE DOORS #100F, #104A AND #105C (REFERENCE |
| | SHEET A4.04). PER NFPA 96, SECTION 7.8.3 WALL |
| | TERMINATIONS. WALL TERMINATIONS SHALL BE ARRANGED WITH |
| | OR PROVIDED WITH THE FOLLOWING PROPERTIES: (1) THROUGH |
| | A NONCOMBUSTIBLE WALL WITH A MINIMUM OF 10 FEET OF |
| | CLEARANCE FROM THE OUTLET TO ADJACENT BUILDINGS, |
| | PROPERTY LINES, GRADE LEVEL, COMBUSTIBLE CONSTRUCTION, |
| | ELECTRICAL EQUIPMENT OR LINES, AND THE CLOSEST POINT OF |
| | ANY AIR INTAKE OR OPERABLE DOOR OR WINDOW AT OR BELOW |
| | THE PLANE OF THE EXHAUST TERMINATION. |
| | |
| | SHEET M1-04: VERIFY THERE ARE NO OPERABLE WINDOWS ABOVE |
| | KIITCHEN #105 EXHAUST LOUVER FROM FAN #3 (WALL |
| | TERMINATION). PER NFPA 96 SECTION 7.8.3, THE CLOSEST |
| | POINT OF ANY AIR INTAKE OR OPERABLE DOOR OR WINDOW |
| | ABOVE THE PLANE OF THE EXHAUST TERMINATION SHALL BE A |
| | MINIMUM OF 10 FEET IN DISTANCE, PLUS 3-INCHES FOR EACH |
| | 1 DEGREE FROM HORIZONTAL, THE ANGLE OF DEGREE BEING |
| | MEASURED FROM THE CENTER OF THE EXHAUST TERMINATION TO |
| | THE CENTER OF THE AIR INTAKE OR OPERABLE DOOR OR |
| | WINDOW, AS INDICATED IN FIGURE 7.8.3. |
| | |
| | SHEET E1-06: SOUTH DIRECTION INDICATING CHEVRONS ARE |
| | NEEDED AT THE EXIT SIGN PLACED AT THE CONNECTOR (HOTEL |
| | TO CONVENTION CENTER). OCCUPANTS WILL NOT BE ABLE TO |
| | EXIT THROUGH THE CONNECTOR (FROM HOTEL) IF THE FIRE |
| | SHUTTER ACTIVATES. |
| | |
| | SHEET E1-06: NO EXTERIOR EXIT SIGNS DIRECTING POOL |
| | OCCUPANTS TO EGRESS THROUGH THE CONNECTOR. |
| | |
| | SHEET E1-08: ONLY ONE EXIT SIGN PROVIDED IN MAIN |
| | KITCHEN. ALSO, EXIT SIGNS LOCATED CORRIDOR |
| | INTERSECTIONS SUCH AS SERVICE CORRIDOR #127 MAY NEED TO |
| | HAVE TWO EXIT SIGNS IN LIEU OF ONLY ONE SIGN. THE |
| | CURRENT SIGN PLACEMENT WILL ALLOW OCCUPANTS TRAVELING |
| | NORTH/SOUTH TO VIEW THE SIGN; HOWEVER, OCCUPANTS |
| | TRAVELING EAST/WEST WILL NOT BE ABLE TO VIEW THE SIGN. |
| | |
| | SHEET E1-09: EXIT SIGN IS ROUTING OCCUPANTS THROUGH THE |
| | KITCHEN AREA. |
| | |
| | SHEET E1-09: NO EXIT SIGNS PROVIDED IN MEETING ROOM |
| | #101. |
| | |
| | SHEET E1-09: EXIT SIGN NOT VIEWABLE FROM LONG PORTION |
| | OF CORRIDOR #103A. |
| | |
| | SHEET E1-16 & E1-17: NO EXIT SIGNS PROVIDED IN ASSEMBLY |
| | ROOMS. EXIT SIGNS IN THE CORRIDOR ADJACENT TO THE |
| | ASSEMBLY ROOMS ONLY DIRECT OCCUPANTS TO USE THE CENTER |
| | EXIT STAIR. ADDITIONAL EXIT SIGNAGE IS NEEDED NOTIFYING |
| | OCCUPANTS THEY CAN ALSO USE THE SOUTH OR WEST STAIRS AS |
| | WELL. |
| | |
| | SHEET E1-17: EXIT SIGN ALSO NEEDED ON SOUTHEAST SIDE OF |
| | CORRIDOR DOORS. |
| | |
| | SHEET E1-20: NO EXIT SIGNS IN EXECUTIVE LOUNGE #1136. |
| | |
| | SHEET E3.00: COULD NOT LOCATE FIREFIGHTERS' SMOKE |
| | CONTROL PANEL (KEY NOTE 9) IN THE FIRE COMMAND ROOM. |
| | |
| | SHEET E4.01: CONFIRM SMOKE CONTROL SYSTEM IS CONNECTED |
| | TO THE EMERGENCY GENERATOR AND THE LOAD IS ACCOUNTED |
| | FOR. |
| | |
| | SHEET FA0.00: PER LOCAL AHJ POLICY, DUCT SMOKE |
| | DETECTORS SHALL INITIATE AN ALARM CONDITION IN LIEU OF |
| | A SUPERVISORY ALARM. |
| | |
| | SHEET FA1-01: NO NOTIFICATION APPLIANCES LOCATED IN |
| | CORRIDOR JUST EAST OF JUNIOR BALLROOM #121. |
| | |
| | SHEET FA1-09: ADD FIRE ALARM DEVICE (POSSIBLY TACTILE |
| | WARNING DEVICES) SHOWN IN GUESTROOM #305 TO THE FIRE |
| | ALARM LEGEND (B SYMBOLS). |
| | |
| | FIRE ALARM: INDICATE ALL GUESTROOMS THAT WILL BE ADA |
| | COMPLIANT. APPEARS ONLY ROOM #305 HAS BEEN SETUP FOR |
| | ADA REQUIREMENTS ON ALL FLOORS. |
| | |
| | SHEET FA1-12: PLAN NOTE INDICATES TO PROVIDE A FIRE |
| | ALARM INTERFACE WITH BI-DIRECTIONAL ANTENNA SYSTEM. ARE |
| | BOTH WIRED FIREFIGHTER PHONE JACKS AND BI-DIRECTIONAL |
| | AMPLIFIER BEING PROVIDED? IF BOTH ARE NOT INTENDED, |
| | PROVIDE BI-DIRECTIONAL RADIO AMPLIFIER SYSTEM IN LIEU |
| | OF WIRED COMMUNICATION SYSTEM (FIREFIGHTER PHONE/JACKS) |
| | PER FBC SECTION 907.2.13.2. |
| | |
| | SHEET FA1-13: CONFIRM SMOKE DETECTORS LOCATED AT THE |
| | TOP OF THE ELEVATOR SHAFTS ARE TO BE INSTALLED TO |
| | ACTIVATE THE ELEVATOR HOISTWAY SMOKE RELIEF EQUIPMENT; |
| | OTHERWISE, NFPA 72 SECTION 21.3.6 PROHIBITS SMOKE |
| | DETECTORS FROM BEING INSTALLED IN THESE LOCATIONS. |
| | |
| | SHEET FP0-01: FIRE SPRINKLER NOTE #15 - PER NFPA 13 |
| | SECTION 24.2.1.2 PORTIONS OF THE SYSTEM NORMALLY |
| | SUBJECTED TO SYSTEM WORKING PRESSURES IN EXCESS OF 150 |
| | PSI SHALL BE TESTEDAT A PRESSURE OF 50 PSI IN EXCESS OF |
| | SYSTEM WORKING PRESSURE. |
| | |
| | FIRE PROTECTION LEVEL 1: DUE TO THE SIZE OF THE FLOOR |
| | PLATE, PLEASE PROVIDE 2-1/2" FIRE DEPARTMENT HOSE |
| | VALVES THROUGHOUT THE CORRIDORS. |
| | |
| | SHEET FP1-08: COULD NOT LOCATE SPRINKLER PROTECTION FOR |
| | LARGE OPEN AREA (COMMUNICATING SPACE). SPRINKLERS |
| | PROTECTING HIGH CEILING OF COMMUNICATING SPACE WILL |
| | NEED TO BE SUPPLIED AND ZONED FROM THE FIRST FLOOR |
| | SYSTEM. |
| | |
| | SHEET FP1-13: THE SPRINKLERS PROTECTING THE SPACES ON |
| | THE ROOF LEVEL WILL NEED TO BE SUPPLIED BY A SEPARATE |
| | SUPERVISED CONTROL VALVE AND FLOW SWITCH SO |
| | FIREFIGHTERS CAN DISTINGUISH A FIRE ON THE 12TH FLOOR |
| | FROM A FIRE ON THE ROOF LEVEL. |
| | |
| | FIRE PROTECTION: COULD NOT LOCATE ANY HYDRANT FLOW TEST |
| | DATA. |
| | |