2014-05-07 08:31:54600 OKEECHOBEE BOULEVARD - HIGH RISE HOTEL
 PERMIT #14050111
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: ALL FIRE REVIEW COMMENTS REFERENCE NFPA 101 REFER
 TO NFPA 101-THE LIFE SAFETY CODE (2009 EDITION WITH
 FLORIDA AMENDMENTS).
  
  
 SHEET A2.02: FITNESS (#104) IS USING AN OCCUPANT LOAD
 FACTOR OF 100 SQUARE FEET PER PERSON. EXERCISE ROOMS
 WITH EQUIPMENT OR WITHOUT EQUIPMENT SHALL USE AN
 OCCUPANT LOAD FACTOR OF 15 SQUARE FEET PERSON OR 50
 SQUARE FEET PERSON RESPECTIVELY PER TABLE 7.3.1.2.
 PROVIDE AN EQUIPMENT LAYOUT.
  
 SHEET A2.02: A DELUGE SPRINKLER SYSTEM IS INDICATED TO
 PROTECT THE CONNECTOR AND ACHIEVE AN EQUIVALENT 2-HOUR
 FIRE RATED ENCLOSURE. TO MY KNOWLEDGE, THERE IS NOT A
 LISTED DELUGE SYSTEM CAPABLE OF ACHIEVING THIS FIRE
 RESISTANCE RATING. A MORE APPROPRIATE DESIGN MAY
 INCLUDE THE USE OF THE TYCO WIINDOW SPRINKLERS. IF THE
 DESIGN INTENT IS TO USE TYCO WINDOW SPRINKLERS TO
 ACHIEVE UP TO A TWO-HOUR FIRE RATED SEPARATION, THE
 SPRINKLERS MUST BE INSTALLED ACCORDING TO THE UL
 LISTING DATA AND SHALL WET THE ENTIRE GLAZING SURFACE.
 SPRINKLERS CANNOT BE USED TO PROTECT OPERABLE DOORS OR
 WINDOWS. THE WINDOW SPRINKLERS DO NOT ALLOW HORIZONTAL
 WINDOW MULLIONS AND REQUIRE THE GLASS CURTAIN WALL TO
 BE ATTACHED TO A THREE FOOT HIGH PONY WALL TO KEEP
 COMBUSTIBLE MATERIALS AT LEAST TWO INCHES AWAY FROM THE
 GLAZING. PAY SPECIAL ATTENTION TO THE GLAZING ASSEMBLY
 AS THE SPRINKLER POSITIONING VARIES FOR BUTT-GLAZED
 INSTALLATIONS COMPARED TO VERTICAL MULLION
 INSTALLATIONS. VERTICAL MULLIONS SHALL BE OF A DEPTH
 THAT PREVENTS COLD SOLDERING OF ADJACENT SPRINKLERS.
 THE SPRINKLER DESIGN SHOULD INDICATE WHICH WINDOW
 SPRINKLER MODEL WILL BE USED (HORIZONTAL SIDEWALL OR
 PENDENT VERTICAL SIDEWALL).
  
 SHEET A2.03: THE TWO STORY OPENING (PRE-FUNCTION #221)
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 8.6 FOR
 VERTICAL OPENINGS AS EITHER A "COMMUNICATING SPACE",
 "ATRIUM" OR " CONVENIENCE OPENING." FOR EXAMPLE, A
 COMMUNICATING SPACE REQUIRES THE ENTIRE FLOOR AREA TO
 BE OPEN AND UNOBSTRUCTED SUCH THAT A FIRE IN ANY PART
 OF THE SPACE WILL BE READILY OBVIOUS TO THE OCCUPANTS
 OF THE SPACE PRIOR TO THE TIME A FIRE BECOMES A HAZARD.
 ANOTHER EXAMPLE, A CONVENIENCE OPENING REQUIRES THAT
 THE FLOOR OPENING BE SEPARATED FROM EXIT ACCESS
 CORRIDORS.
  
 SHEET A2.03: THE PLAN SHOWS THE 1-HOUR FIRE RATING
 CROSSING THE CORRIDOR AT DOOR #221A; HOWEVER, THERE IS
 NO 1-HOUR FIRE RATING INDICATED FOR THE WALL CROSSING
 THE CORRIDOR AT DOOR #221B. ALSO THE DOOR SCHEDULE
 (SHEET A14.01) DOES NOT INDICATE A FIRE RATING FOR
 EITHER SET OF DOORS.
  
 SHEET A3.0: PROVIDE DIRECT ACCESS INTO THE FIRE PUMP
 ROOM (B003) FROM THE CORRIDOR WITHOUT HAVING TO TRAVEL
 THROUGH THE DOMESTIC PUMP ROOM (B002) FIRST.
  
 SHEET A3.01: STAIR #2 TERMINATES INSIDE THE BUILDING
 WHICH IS PERMITTED BY SECTION 28.2.7.2; HOWEVER, THE
 TRAVEL DISTANCE FROM THE TERMINATION OF THE EXIT
 ENCLOSURE TO AN EXTERIOR EXIT DOOR LEADING TO A PUBLIC
 WAY SHALL NOT EXCEED 100 FEET.
  
 SHEET A4.01: CONNECTOR DOORS (#156-#156F & 118A)
 INDICATE THE USE OF TEMPERED GLASS. DOOR GLAZING WILL
 NEED TO BE FIRE RATED AS SPRINKLERS ARE NOT LISTED TO
 PROTECT OPERABLE DOOR/WINDOW GLAZING AND PROVIDE AN
 EQUIVALENT FIRE RATING.
  
 SHEET A4.01: THE LIFE SAFETY PLAN (SHEET A2.02)
 INDICATES A TWO-HOUR WALL RATING AROUND STAIR #6;
 HOWEVER, THE DOOR SCHEDULE (SHEET A14.00) DOES NOT
 INDICATE A DOOR FIRE RATING OR CLOSER.
  
 SHEET A4.01: THE LIFE SAFETY PLAN (SHEET A2.02)
 INDICATES A ONE-HOUR WALL RATING AROUND POOL STORAGE
 #126; HOWEVER, THE DOOR SCHEDULE (SHEET A14.00) DOES
 NOT INDICATE A DOOR FIRE RATING OR CLOSER.
  
 SHEET A4.01: THE LIFE SAFETY PLAN (SHEET A2.02)
 INDICATES A ONE-HOUR WALL RATING AROUND PARTITION
 STORAGE #121N; HOWEVER, THE DOOR SCHEDULE (SHEET
 A14.00) DOES NOT INDICATE A DOOR FIRE RATING OR CLOSER
 FOR DOORS #121N AND #121O.
  
 SHEET A4.01: THE LIFE SAFETY PLAN (SHEET A2.02)
 INDICATES A ONE-HOUR WALL RATING AROUND PARTITION
 STORAGE #121L; HOWEVER, THE DOOR SCHEDULE (SHEET
 A14.00) DOES NOT INDICATE A DOOR FIRE RATING OR CLOSER
 FOR DOORS #121L.
  
 SHEET A4.04: DOOR #103C IN CORRIDOR #103C IS MISSING
 PANIC HARDWARE IN DOOR SCHEDULE (SHEET A14.00).
  
 SHEET A4.04: DOOR #104 IN FITNESS #104 IS MISSING PANIC
 HARDWARE IN THE DOOR SCHEDULE (SHEET A14.00). OCCUPANT
 LOAD WILL EXCEED 100 PERSONS IN THE FITNESS ROOM ONCE
 THE APPROPRIATE OCCUPANT LOAD FACTOR IS APPLIED.
 EXITING STAIR #2 AND THEN TRAVELING THROUGH THE HOTEL
 LOBBY EXCEEDS 100 FEET. ADDITIONALLY THIS PATH OF
 TRAVEL IS NOT OBVIOUS AND DIRECT.
  
 LEVEL 100: THE OVERALL LIFE SAFETY EXITING CONCEPT
 NEEDS TO BE COORDINATED WITH THE ELECTRICAL DRAWINGS
 REGARDING THE PLACEMENT OF EXIT SIGNAGE. FOR EXAMPLE,
 SHEET E1-09 SHOWS EXIT SIGNS AT DOORS #100E AND #106B
 LEADING TO THE BAR TERRACE. HOW ARE OCCUPANTS BEING
 DIRECTED TO THE PUBLIC WAY ONCE THEY ENTER THE BAR
 TERRACE AREA? DOOR #100E IS NOT EQUIPPED WITH PANIC
 HARDWARE. ADDITIONALLY AN EXIT SIGN HAS BEEN PLACED AT
 DOOR #105A LEADING BAR OCCUPANTS THROUGH THE KITCHEN
 AREA TO REACH AN EXIT.
  
 SHEET A4.06 (STAIR #3/BOILER ROOM #229/ELECTRICAL
 #224): PER SECTION 28.3.2.1 ALL ROOMS CONTAINING
 HIGH-PRESSURE BOILERS, TRANSFORMERS OR OTHER SERVICE
 EQUIPMENT SUBJECT TO POSSIBLE EXPLOSION SHALL NOT BE
 LOCATED DIRECTLY ADJACENT TO EXITS.
  
 SHEET A4.07: LEVEL 200 HAS ASSEMBLY USE ROOMS WITH
 OCCUPANT LOADS EXCEEDING 100 PERSONS. THE EXIT ACCESS
 DOORS FROM THESE ROOMS ARE EQUIPPED WITH PANIC/FIRE
 EXIT HARDWARE; HOWEVER, THE OTHER EXIT ACCESS DOORS ON
 THE FLOOR ARE NOT EQUIPPED WITH PANIC/FIRE EXIT
 HARDWARE SUCH AS DOOR T08, 219, 219A, 221A, 221B, &
 223. PER SECTION 6.1.14.1.2, WHERE EXIT ACCESS FROM AN
 OCCUPANCY TRAVERSES ANOTHER OCCUPANCY, THE MULTIPLE
 OCCUPANCY SHALL BE TREATED AS A MIXED OCCUPANCY AND THE
 MOST STRINGENT FIRE AND LIFE SAFETY REQUIREMENTS OF
 EACH OCCUPANCY SHALL APPLY TO THE BUILDING.
  
 SHEET A4.07: THE SERVICE ELEVATOR LOBBY (ALL FLOORS)
 INDICATES AN EXIT ACCESS DOOR (#219) WITH A CARD
 READER. A CARD READER ON THE EGRESS SIDE IS NOT
 PERMITTED AS THIS REQUIRES SPECIAL KNOWLEDGE AND A TOOL
 TO GAIN ACCESS TO AN EXIT.
  
 SHEET A4.07 - DOOR T12 (SUITES #204 & #205): PER
 SECTION 28.3.7.2, IN BUILDINGS PROTECTED THROUGHOUT BY
 AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM,
 EACH HOTEL GUEST ROOM, INCLUDING GUEST SUITES SHALL BE
 SEPARATED FROM OTHER GUEST ROOMS BY WALLS AND FLOORS
 CONSTRUCTED AS FIRE BARRIERS HAVING A MINIMUM 1/2-HOUR
 FIRE RESISTANCE RATING. DOORS IN THE FIRE BARRIERS
 SHALL HAVE A FIRE RESISTANCE RATING OF NOT LESS THAN
 20-MINUTES AND SHALL NOT BE REQUIRED TO BE
 SELF-CLOSING.
  
 SHEET A4.08: PER SECTION 28.3.7.2, IN BUILDINGS
 PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM, EACH HOTEL GUEST ROOM,
 INCLUDING GUEST SUITES SHALL BE SEPARATED FROM OTHER
 GUEST ROOMS BY WALLS AND FLOORS CONSTRUCTED AS FIRE
 BARRIERS HAVING A MINIMUM 1/2-HOUR FIRE RESISTANCE
 RATING. DOORS IN THE FIRE BARRIERS SHALL HAVE A FIRE
 RESISTANCE RATING OF NOT LESS THAN 20-MINUTES AND SHALL
 NOT BE REQUIRED TO BE SELF-CLOSING. APPLIES TO SEVERAL
 SUITES INCLUDING SUITES, #235, #240, #247 ETC. CHECK
 OTHER FLOORS AS WELL. ALSO NO DOOR TAGS PROVIDED FOR
 DOORS COMMUNICATING BETWEEN TWO ROOMS SUCH AS SUITE
 #240 AND SUITE #247.
  
 SHEET A4.19: EXECUTIVE LOUNGE #1136 APPEARS TO BE AN
 ASSEMBLY USE ROOM; HOWEVER, NO PANIC HARDWARE IS SHOWN
 ON DOORS #1136 OR #1136D.
  
 GENERAL: PROVIDE ADDITIONAL INFORMATION ON THE PROPOSED
 GAS FIRED PIT LOCATED NEAR THE OPEN SKY TERRACE/BAR.
 SHEET E1-05 REFERENCES A GAS FIRED PIT CONTROLLER, BUT
 NO OTHER DESIGN INFORMATION WAS FOUND.
  
 SHEET M1-00: COULD NOT OPEN DRAWING. FILE CONSISTENTLY
 CRASHES COMPUTER.
  
 SHEET M1-04: KITCHEN #105 EXHAUST LOUVER FROM EXHAUST
 FAN #3 (WALL TERMINATION) APPEARS TO BE WITHIN 10 FEET
 OF OPERABLE DOORS #100F, #104A AND #105C (REFERENCE
 SHEET A4.04). PER NFPA 96, SECTION 7.8.3 WALL
 TERMINATIONS. WALL TERMINATIONS SHALL BE ARRANGED WITH
 OR PROVIDED WITH THE FOLLOWING PROPERTIES: (1) THROUGH
 A NONCOMBUSTIBLE WALL WITH A MINIMUM OF 10 FEET OF
 CLEARANCE FROM THE OUTLET TO ADJACENT BUILDINGS,
 PROPERTY LINES, GRADE LEVEL, COMBUSTIBLE CONSTRUCTION,
 ELECTRICAL EQUIPMENT OR LINES, AND THE CLOSEST POINT OF
 ANY AIR INTAKE OR OPERABLE DOOR OR WINDOW AT OR BELOW
 THE PLANE OF THE EXHAUST TERMINATION.
  
 SHEET M1-04: VERIFY THERE ARE NO OPERABLE WINDOWS ABOVE
 KIITCHEN #105 EXHAUST LOUVER FROM FAN #3 (WALL
 TERMINATION). PER NFPA 96 SECTION 7.8.3, THE CLOSEST
 POINT OF ANY AIR INTAKE OR OPERABLE DOOR OR WINDOW
 ABOVE THE PLANE OF THE EXHAUST TERMINATION SHALL BE A
 MINIMUM OF 10 FEET IN DISTANCE, PLUS 3-INCHES FOR EACH
 1 DEGREE FROM HORIZONTAL, THE ANGLE OF DEGREE BEING
 MEASURED FROM THE CENTER OF THE EXHAUST TERMINATION TO
 THE CENTER OF THE AIR INTAKE OR OPERABLE DOOR OR
 WINDOW, AS INDICATED IN FIGURE 7.8.3.
  
 SHEET E1-06: SOUTH DIRECTION INDICATING CHEVRONS ARE
 NEEDED AT THE EXIT SIGN PLACED AT THE CONNECTOR (HOTEL
 TO CONVENTION CENTER). OCCUPANTS WILL NOT BE ABLE TO
 EXIT THROUGH THE CONNECTOR (FROM HOTEL) IF THE FIRE
 SHUTTER ACTIVATES.
  
 SHEET E1-06: NO EXTERIOR EXIT SIGNS DIRECTING POOL
 OCCUPANTS TO EGRESS THROUGH THE CONNECTOR.
  
 SHEET E1-08: ONLY ONE EXIT SIGN PROVIDED IN MAIN
 KITCHEN. ALSO, EXIT SIGNS LOCATED CORRIDOR
 INTERSECTIONS SUCH AS SERVICE CORRIDOR #127 MAY NEED TO
 HAVE TWO EXIT SIGNS IN LIEU OF ONLY ONE SIGN. THE
 CURRENT SIGN PLACEMENT WILL ALLOW OCCUPANTS TRAVELING
 NORTH/SOUTH TO VIEW THE SIGN; HOWEVER, OCCUPANTS
 TRAVELING EAST/WEST WILL NOT BE ABLE TO VIEW THE SIGN.
  
 SHEET E1-09: EXIT SIGN IS ROUTING OCCUPANTS THROUGH THE
 KITCHEN AREA.
  
 SHEET E1-09: NO EXIT SIGNS PROVIDED IN MEETING ROOM
 #101.
  
 SHEET E1-09: EXIT SIGN NOT VIEWABLE FROM LONG PORTION
 OF CORRIDOR #103A.
  
 SHEET E1-16 & E1-17: NO EXIT SIGNS PROVIDED IN ASSEMBLY
 ROOMS. EXIT SIGNS IN THE CORRIDOR ADJACENT TO THE
 ASSEMBLY ROOMS ONLY DIRECT OCCUPANTS TO USE THE CENTER
 EXIT STAIR. ADDITIONAL EXIT SIGNAGE IS NEEDED NOTIFYING
 OCCUPANTS THEY CAN ALSO USE THE SOUTH OR WEST STAIRS AS
 WELL.
  
 SHEET E1-17: EXIT SIGN ALSO NEEDED ON SOUTHEAST SIDE OF
 CORRIDOR DOORS.
  
 SHEET E1-20: NO EXIT SIGNS IN EXECUTIVE LOUNGE #1136.
  
 SHEET E3.00: COULD NOT LOCATE FIREFIGHTERS' SMOKE
 CONTROL PANEL (KEY NOTE 9) IN THE FIRE COMMAND ROOM.
  
 SHEET E4.01: CONFIRM SMOKE CONTROL SYSTEM IS CONNECTED
 TO THE EMERGENCY GENERATOR AND THE LOAD IS ACCOUNTED
 FOR.
  
 SHEET FA0.00: PER LOCAL AHJ POLICY, DUCT SMOKE
 DETECTORS SHALL INITIATE AN ALARM CONDITION IN LIEU OF
 A SUPERVISORY ALARM.
  
 SHEET FA1-01: NO NOTIFICATION APPLIANCES LOCATED IN
 CORRIDOR JUST EAST OF JUNIOR BALLROOM #121.
  
 SHEET FA1-09: ADD FIRE ALARM DEVICE (POSSIBLY TACTILE
 WARNING DEVICES) SHOWN IN GUESTROOM #305 TO THE FIRE
 ALARM LEGEND (B SYMBOLS).
  
 FIRE ALARM: INDICATE ALL GUESTROOMS THAT WILL BE ADA
 COMPLIANT. APPEARS ONLY ROOM #305 HAS BEEN SETUP FOR
 ADA REQUIREMENTS ON ALL FLOORS.
  
 SHEET FA1-12: PLAN NOTE INDICATES TO PROVIDE A FIRE
 ALARM INTERFACE WITH BI-DIRECTIONAL ANTENNA SYSTEM. ARE
 BOTH WIRED FIREFIGHTER PHONE JACKS AND BI-DIRECTIONAL
 AMPLIFIER BEING PROVIDED? IF BOTH ARE NOT INTENDED,
 PROVIDE BI-DIRECTIONAL RADIO AMPLIFIER SYSTEM IN LIEU
 OF WIRED COMMUNICATION SYSTEM (FIREFIGHTER PHONE/JACKS)
 PER FBC SECTION 907.2.13.2.
  
 SHEET FA1-13: CONFIRM SMOKE DETECTORS LOCATED AT THE
 TOP OF THE ELEVATOR SHAFTS ARE TO BE INSTALLED TO
 ACTIVATE THE ELEVATOR HOISTWAY SMOKE RELIEF EQUIPMENT;
 OTHERWISE, NFPA 72 SECTION 21.3.6 PROHIBITS SMOKE
 DETECTORS FROM BEING INSTALLED IN THESE LOCATIONS.
  
 SHEET FP0-01: FIRE SPRINKLER NOTE #15 - PER NFPA 13
 SECTION 24.2.1.2 PORTIONS OF THE SYSTEM NORMALLY
 SUBJECTED TO SYSTEM WORKING PRESSURES IN EXCESS OF 150
 PSI SHALL BE TESTEDAT A PRESSURE OF 50 PSI IN EXCESS OF
 SYSTEM WORKING PRESSURE.
  
 FIRE PROTECTION LEVEL 1: DUE TO THE SIZE OF THE FLOOR
 PLATE, PLEASE PROVIDE 2-1/2" FIRE DEPARTMENT HOSE
 VALVES THROUGHOUT THE CORRIDORS.
  
 SHEET FP1-08: COULD NOT LOCATE SPRINKLER PROTECTION FOR
 LARGE OPEN AREA (COMMUNICATING SPACE). SPRINKLERS
 PROTECTING HIGH CEILING OF COMMUNICATING SPACE WILL
 NEED TO BE SUPPLIED AND ZONED FROM THE FIRST FLOOR
 SYSTEM.
  
 SHEET FP1-13: THE SPRINKLERS PROTECTING THE SPACES ON
 THE ROOF LEVEL WILL NEED TO BE SUPPLIED BY A SEPARATE
 SUPERVISED CONTROL VALVE AND FLOW SWITCH SO
 FIREFIGHTERS CAN DISTINGUISH A FIRE ON THE 12TH FLOOR
 FROM A FIRE ON THE ROOF LEVEL.
  
 FIRE PROTECTION: COULD NOT LOCATE ANY HYDRANT FLOW TEST
 DATA.
  