| 2014-06-11 11:41:29 | PERMIT 14050111, WEST PALM BEACH CONVENTION CENTER |
| | HILTON HOTEL |
| | THE FIRST ELECTRICAL REVIEW FAILED AS LISTED BELOW: |
| | THE FOLLOWING IS A LIST OF THE CHANGEMARKS, NOTES AND |
| | CORRECTIONS ENTERED AS RESULT OF THE ELECTRICAL REVIEW |
| | ON THE ABOVE MENTIONED PERMIT. THE DIGITAL SET HAS BEEN |
| | MARKED WITH EVERY NOTE AND COMMENT THAT APPEARS BELOW. |
| | FOR EASE OF CORRECTING, PLEASE NOTE THAT THE COMMENTS |
| | ARE ARRANGED WITH PAGE NUMBERS AND THE RESPECTIVE |
| | CHANGEMARK NUMBER PER PAGE. |
| | PAGE E0.00 |
| | 1. THE ADOPTED VERSION OF THE NEC AT THE TIME OF THIS |
| | REVIEW IS THE 2008 EDITION, WHICH IS THE ONE THAT SHALL |
| | APPLY. |
| | 2. NEED MORE SPECIFICS ON THE WIND LOAD CRITERIA. IS |
| | THE REFERENCE TO ULTIMATE OR NOMINAL? |
| | 3. CORRECT THIS QUOTE/REFERRAL TO NEC SECTION 368.6 AS |
| | IT DOES NOT EXIST IN THE 2008 EDITION OF THE NEC. |
| | 4. A SEPARATE PERMIT AND SHOP DRAWINGS ARE REQUIRED FOR |
| | THE FIRE ALARM INSTALLATION. |
| | PAGE E1.01 |
| | 1. LIGHTING CONTROL TO BE IN ACCORDANCE WITH THE |
| | REQUIREMENTS OF 2010 FLORIDA BLDG. CODE - ENERGY |
| | CONSERVATION, SEC. 505. |
| | PAGE E1.06, E1.07 |
| | 1. LIGHTING CONTROL TO BE IN ACCORDANCE WITH THE |
| | REQUIREMENTS OF 2010 FLORIDA BLDG. CODE - ENERGY |
| | CONSERVATION, SEC. 505. |
| | PAGE E1.22 |
| | 1. PER NEC 406.8, ALL 15 AND 20 AMPERE, 125 AND 250 |
| | VOLT NON-LOCKING RECEPTACLES SHALL BE LISTED |
| | WEATHER-RESISTANT TYPE. |
| | PAGE E2.00, E2.01, E2.03, E2.04 |
| | 1. THE 2010 EDITION OF THE FLORIDA BUILDING CODE - |
| | ENERGY CONSERVATION SECTION 505.2.1.3(3) SLEEPING UNIT |
| | CONTROLS HAS SPECIFIC LIGHTING CONTROL REQUIREMENTS FOR |
| | HOTEL GUEST SUITES WHICH HAVE TO BE COMPLIED WITH. SEE |
| | CLOUDED AREAS ON PLANS. |
| | 2. AS PER 2008 NEC 210.60, RECEPTACLE PLACEMENT IN |
| | HOTEL ROOMS SHALL COMPLY WITH NEC SECTIONS 210.52(A) & |
| | (D) |
| | 3. PAGE E2.04, E2.05 CIRCUIT ?L? IS NOT IDENTIFIED. |
| | THIS CIRCUIT APPEARS TO BE IN A KITCHEN AREA. THOUGH |
| | NOT INDICATED, IF PERMANENT COOKING FACILITIES ARE |
| | INSTALLED, OUTLET PLACEMENT SHALL BE AS PER NEC 210.52 |
| | PAGE E3.09 |
| | 1. ADDED NOTE: EVERY GENERAL PURPOSE OUTLET INSTALLED |
| | WITHIN 6' OF A SINK SHALL BE GFI PROTECTED, AS PER NEC |
| | 210.8(B)(5) |
| | 2. REFERRAL TO AN OUTLET IN A PORTABLE POOL BAR IS |
| | MADE. ELABORATE FURTHER ON THIS. IF THE POOL BAR IS |
| | PORTABLE WHAT OUTLET ARE YOU REFERRING TO? |
| | PAGE E4.01 |
| | REFERENCE TO THE ARC-FLASH LABEL REQUIREMENTS OF NEC |
| | 110.16 IS MADE. |
| | 1. ACCORDING TO THE PANEL SCHEDULE FOR MDP "M1", THIS |
| | GOES TO CKT 12 |
| | 2. NOT USED |
| | 3. MISSING OCPD FOR PANEL "1LB", FROM PANEL "1L" ON |
| | RISER PAGE 501 PANEL "1L" |
| | 4. THERE ARE INCONSISTENCIES WITH THE REFERENCES TO "G" |
| | PANEL. AT TIMES IT IS REFERRED TO "2G" OTHERS TIMES |
| | "GL" AND YET ANOTHER "GLN" ARE THESE ALL ONE AND THE |
| | SAME? IF SO, CORRECT TO MATCH |
| | 5. THIS PANEL IS LABELED "GL" IN THE PANEL SCHEDULE FOR |
| | "BRH". |
| | 6. THE MAINS FOR THESE TWO PANELS ARE INVERTED |
| | ACCORDING TO THE PANEL SCHEDULE FOR "M2" ON PAGE E5.05. |
| | 7. THIS DISCONNECT & TRANSFORMER ARE MISSING FROM THE |
| | RISER DIAGRAM |
| | 8. SAME AS NOTE 7, THIS DISCONNECT AND TRANSFORMER DO |
| | NOT APPEAR ON THE PANEL SCHEDULE. |
| | 9. THE PANEL SCHEDULE OF PANEL "12NLA" HAS CKTS FOR |
| | THIS PANEL RATHER THAN FROM PANEL "12NL" AS INDICATED |
| | HERE. CORRECT TO MATCH. |
| | 10. THIS PANEL APPEARS TO BE LABELED "ILDE" ON THE |
| | PANEL SCHEDULE PAGE E4.03 |
| | PAGE E4.02 |
| | ALL WIRE SHALL BE LISTED FOR THE APPLICATION |
| | 1. AS INDICATED HEREIN THAT 120V FOR LIGHTING CONTROL |
| | PROVIDED BY OTHER. UNLESS THIS WORK IS INITIATED & |
| | COMPLETED BY THE ELECTRICAL CONTRACTOR OF RECORD, A |
| | SEPARATE PERMIT SHALL BE REQUIRED FOR THE LOW VOLTAGE |
| | CONTROL WORK. |
| | PAGE E4.03 |
| | 1. ON THE RISER DIAGRAM OF PAGE E4.01, THIS PANEL |
| | APPEARS TO BE LABELED "1LDE" RATHER THAN "ILDE". |
| | CORRECT TO MATCH. |
| | PAGE E5.01 |
| | 1. REFERENCE MADE ON PANEL ?L?, ?2L? OF GFCI |
| | REQUIREMENTS OF NEC 422.52 |
| | 2. MISSING OCPD FOR PANEL "1LB", PER RISER ON PG. E4.01 |
| | PAGE E5.02 |
| | 1. REFERENCE NOTE TO THE NEC 210.8 GFCI REQUIREMENT FOR |
| | OUTLETS ON ROOFS. |
| | 2. SOURCE REFERENCE FOR PANELS ?2LS? & ?2LSA? |
| | 3. THERE ARE INCONSISTENCIES WITH THE REFERENCES TO "G" |
| | PANEL. AT TIMES IT IS REFERRED TO "2G" OTHERS TIMES |
| | "GL" AND YET ANOTHER "GLN" ARE THESE ALL ONE AND THE |
| | SAME? IF SO, CORRECT TO MATCH |
| | PAGE E5.04 |
| | 1. ACCORDING TO THE RISER DIAGRAM OF PAGE E4.01 THE |
| | SOURCE FOR PANEL "2CH" IS "M2". HERE IT INDICATES "M1" |
| | CORRECT ACCORDINGLY. |
| | 2. NEC 422.52 REQUIRES ELECTRIC DRINKING FOUNTAINS TO |
| | BE ON A GFCI CKT. |
| | 3. NEC 422.51 HAS SPECIFIC REQUIREMENTS FOR VENDING |
| | MACHINE CKTS. |
| | 4. THERE ARE NUMEROUS GFI REQUIREMENTS NOT ADDRESSED |
| | WITH RESPECT TO THE POOL AS WELL AS THE ELECTRIC |
| | DRINKING FOUNTAIN. |
| | PAGE E5.05 |
| | 1. CLARIFY IF THE INTENTION OF THIS IS MAIN 3, "M3" |
| | WHICH IS NON-EXISTENT. CORRECT TO MATCH WITH MDP "M2" |
| | PAGE E5.06 |
| | 1. CLARIFY IF THE INTENTION OF THIS IS MAIN 3, "M3" |
| | WHICH IS NON-EXISTENT. CORRECT TO MATCH WITH MDP "M2" |
| | PAGE E5.07 |
| | 1. THE RISER DIAGRAM OF PAGE E4.01 SHOWS PANEL "PSLD" |
| | AS BEING FED FROM PANEL "12NL" NOT "12NLA" CORRECT TO |
| | MATCH. |
| | PAGE E5.08 |
| | 1. INDICATE THAT THIS PANEL ("KEQL") IS FED THROUGH |
| | TRANSFORMER "T75", TO MATCH RISER DIAGRAM |
| | 2. INDICATE THAT THIS PANEL "("3EQL") IS FED THROUGH |
| | THE DISCONNECT VIA TRANSFORMER "T45". |
| | PAGE E5.09 |
| | 1. PER NFPA REQUIREMENTS, THESE CKT/BKRS SHALL BE RED |
| | AND MECHANICALLY PROTECTED AS REQUIRED. |
| | PAGE FA0.00 |
| | SEPARATE PERMIT & SHOP DRAWINGS REQUIRED FOR THE FIRE |
| | ALARM |
| | |
| | THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL |
| | PLANS EXAMINER |
| | YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE |
| | FOLLOWING LINK: |
| | |
| | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT |
| | US.ASPX |
| | |
| | ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS |
| | EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER, |
| | AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB |
| | ABOVE THE SECOND PERMIT INFORMATION). |
| | AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR |
| | COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER |
| | PERMIT CONDITIONS. |
| | FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME. |
| | I CAN BE REACHED AT 561-805-6718 OR [email protected] |
| | |