Plan Review Notes
Plan Review Notes For Permit 14050111
Permit Number 14050111
Review Stop E
Sequence Number 1
Notes
Date Text
2014-06-11 11:41:29PERMIT 14050111, WEST PALM BEACH CONVENTION CENTER
 HILTON HOTEL
 THE FIRST ELECTRICAL REVIEW FAILED AS LISTED BELOW:
 THE FOLLOWING IS A LIST OF THE CHANGEMARKS, NOTES AND
 CORRECTIONS ENTERED AS RESULT OF THE ELECTRICAL REVIEW
 ON THE ABOVE MENTIONED PERMIT. THE DIGITAL SET HAS BEEN
 MARKED WITH EVERY NOTE AND COMMENT THAT APPEARS BELOW.
 FOR EASE OF CORRECTING, PLEASE NOTE THAT THE COMMENTS
 ARE ARRANGED WITH PAGE NUMBERS AND THE RESPECTIVE
 CHANGEMARK NUMBER PER PAGE.
 PAGE E0.00
 1. THE ADOPTED VERSION OF THE NEC AT THE TIME OF THIS
 REVIEW IS THE 2008 EDITION, WHICH IS THE ONE THAT SHALL
 APPLY.
 2. NEED MORE SPECIFICS ON THE WIND LOAD CRITERIA. IS
 THE REFERENCE TO ULTIMATE OR NOMINAL?
 3. CORRECT THIS QUOTE/REFERRAL TO NEC SECTION 368.6 AS
 IT DOES NOT EXIST IN THE 2008 EDITION OF THE NEC.
 4. A SEPARATE PERMIT AND SHOP DRAWINGS ARE REQUIRED FOR
 THE FIRE ALARM INSTALLATION.
 PAGE E1.01
 1. LIGHTING CONTROL TO BE IN ACCORDANCE WITH THE
 REQUIREMENTS OF 2010 FLORIDA BLDG. CODE - ENERGY
 CONSERVATION, SEC. 505.
 PAGE E1.06, E1.07
 1. LIGHTING CONTROL TO BE IN ACCORDANCE WITH THE
 REQUIREMENTS OF 2010 FLORIDA BLDG. CODE - ENERGY
 CONSERVATION, SEC. 505.
 PAGE E1.22
 1. PER NEC 406.8, ALL 15 AND 20 AMPERE, 125 AND 250
 VOLT NON-LOCKING RECEPTACLES SHALL BE LISTED
 WEATHER-RESISTANT TYPE.
 PAGE E2.00, E2.01, E2.03, E2.04
 1. THE 2010 EDITION OF THE FLORIDA BUILDING CODE -
 ENERGY CONSERVATION SECTION 505.2.1.3(3) SLEEPING UNIT
 CONTROLS HAS SPECIFIC LIGHTING CONTROL REQUIREMENTS FOR
 HOTEL GUEST SUITES WHICH HAVE TO BE COMPLIED WITH. SEE
 CLOUDED AREAS ON PLANS.
 2. AS PER 2008 NEC 210.60, RECEPTACLE PLACEMENT IN
 HOTEL ROOMS SHALL COMPLY WITH NEC SECTIONS 210.52(A) &
 (D)
 3. PAGE E2.04, E2.05 CIRCUIT ?L? IS NOT IDENTIFIED.
 THIS CIRCUIT APPEARS TO BE IN A KITCHEN AREA. THOUGH
 NOT INDICATED, IF PERMANENT COOKING FACILITIES ARE
 INSTALLED, OUTLET PLACEMENT SHALL BE AS PER NEC 210.52
 PAGE E3.09
 1. ADDED NOTE: EVERY GENERAL PURPOSE OUTLET INSTALLED
 WITHIN 6' OF A SINK SHALL BE GFI PROTECTED, AS PER NEC
 210.8(B)(5)
 2. REFERRAL TO AN OUTLET IN A PORTABLE POOL BAR IS
 MADE. ELABORATE FURTHER ON THIS. IF THE POOL BAR IS
 PORTABLE WHAT OUTLET ARE YOU REFERRING TO?
 PAGE E4.01
  REFERENCE TO THE ARC-FLASH LABEL REQUIREMENTS OF NEC
 110.16 IS MADE.
 1. ACCORDING TO THE PANEL SCHEDULE FOR MDP "M1", THIS
 GOES TO CKT 12
 2. NOT USED
 3. MISSING OCPD FOR PANEL "1LB", FROM PANEL "1L" ON
 RISER PAGE 501 PANEL "1L"
 4. THERE ARE INCONSISTENCIES WITH THE REFERENCES TO "G"
 PANEL. AT TIMES IT IS REFERRED TO "2G" OTHERS TIMES
 "GL" AND YET ANOTHER "GLN" ARE THESE ALL ONE AND THE
 SAME? IF SO, CORRECT TO MATCH
 5. THIS PANEL IS LABELED "GL" IN THE PANEL SCHEDULE FOR
 "BRH".
 6. THE MAINS FOR THESE TWO PANELS ARE INVERTED
 ACCORDING TO THE PANEL SCHEDULE FOR "M2" ON PAGE E5.05.
 7. THIS DISCONNECT & TRANSFORMER ARE MISSING FROM THE
 RISER DIAGRAM
 8. SAME AS NOTE 7, THIS DISCONNECT AND TRANSFORMER DO
 NOT APPEAR ON THE PANEL SCHEDULE.
 9. THE PANEL SCHEDULE OF PANEL "12NLA" HAS CKTS FOR
 THIS PANEL RATHER THAN FROM PANEL "12NL" AS INDICATED
 HERE. CORRECT TO MATCH.
 10. THIS PANEL APPEARS TO BE LABELED "ILDE" ON THE
 PANEL SCHEDULE PAGE E4.03
 PAGE E4.02
  ALL WIRE SHALL BE LISTED FOR THE APPLICATION
 1. AS INDICATED HEREIN THAT 120V FOR LIGHTING CONTROL
 PROVIDED BY OTHER. UNLESS THIS WORK IS INITIATED &
 COMPLETED BY THE ELECTRICAL CONTRACTOR OF RECORD, A
 SEPARATE PERMIT SHALL BE REQUIRED FOR THE LOW VOLTAGE
 CONTROL WORK.
 PAGE E4.03
 1. ON THE RISER DIAGRAM OF PAGE E4.01, THIS PANEL
 APPEARS TO BE LABELED "1LDE" RATHER THAN "ILDE".
 CORRECT TO MATCH.
 PAGE E5.01
 1. REFERENCE MADE ON PANEL ?L?, ?2L? OF GFCI
 REQUIREMENTS OF NEC 422.52
 2. MISSING OCPD FOR PANEL "1LB", PER RISER ON PG. E4.01
 PAGE E5.02
 1. REFERENCE NOTE TO THE NEC 210.8 GFCI REQUIREMENT FOR
 OUTLETS ON ROOFS.
 2. SOURCE REFERENCE FOR PANELS ?2LS? & ?2LSA?
 3. THERE ARE INCONSISTENCIES WITH THE REFERENCES TO "G"
 PANEL. AT TIMES IT IS REFERRED TO "2G" OTHERS TIMES
 "GL" AND YET ANOTHER "GLN" ARE THESE ALL ONE AND THE
 SAME? IF SO, CORRECT TO MATCH
 PAGE E5.04
 1. ACCORDING TO THE RISER DIAGRAM OF PAGE E4.01 THE
 SOURCE FOR PANEL "2CH" IS "M2". HERE IT INDICATES "M1"
 CORRECT ACCORDINGLY.
 2. NEC 422.52 REQUIRES ELECTRIC DRINKING FOUNTAINS TO
 BE ON A GFCI CKT.
 3. NEC 422.51 HAS SPECIFIC REQUIREMENTS FOR VENDING
 MACHINE CKTS.
 4. THERE ARE NUMEROUS GFI REQUIREMENTS NOT ADDRESSED
 WITH RESPECT TO THE POOL AS WELL AS THE ELECTRIC
 DRINKING FOUNTAIN.
 PAGE E5.05
 1. CLARIFY IF THE INTENTION OF THIS IS MAIN 3, "M3"
 WHICH IS NON-EXISTENT. CORRECT TO MATCH WITH MDP "M2"
 PAGE E5.06
 1. CLARIFY IF THE INTENTION OF THIS IS MAIN 3, "M3"
 WHICH IS NON-EXISTENT. CORRECT TO MATCH WITH MDP "M2"
 PAGE E5.07
 1. THE RISER DIAGRAM OF PAGE E4.01 SHOWS PANEL "PSLD"
 AS BEING FED FROM PANEL "12NL" NOT "12NLA" CORRECT TO
 MATCH.
 PAGE E5.08
 1. INDICATE THAT THIS PANEL ("KEQL") IS FED THROUGH
 TRANSFORMER "T75", TO MATCH RISER DIAGRAM
 2. INDICATE THAT THIS PANEL "("3EQL") IS FED THROUGH
 THE DISCONNECT VIA TRANSFORMER "T45".
 PAGE E5.09
 1. PER NFPA REQUIREMENTS, THESE CKT/BKRS SHALL BE RED
 AND MECHANICALLY PROTECTED AS REQUIRED.
 PAGE FA0.00
  SEPARATE PERMIT & SHOP DRAWINGS REQUIRED FOR THE FIRE
 ALARM
  
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
  
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.