2014-06-05 06:31:33BUILDING PLAN REVIEW
 PERMIT:14050111
 ADD: 600 OKEECHOBEE BLVD
 CONT: COASTAL CONSTRUCTION
 TEL: (561) 630-3770
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 THE PALM BEACH CONVENTION CENTER HILTON HOTEL
 CONSTRUCTION OF NEW 400 ROOM HOTEL INCLUDING BALLROOMS,
 RESTAURANT(S), MEETING SPACE, POOL DECK AND AMENITIES
  
 1ST REVIEW
 DATE: TUESDAY JUNE 17TH/ 2014
  
 ACTION: DENIED
  
 1) THE PERMIT DESCRIPTION LISTED ABOVE TO BUILD THE
 HOTEL, POOL, POOL DECK & AMENITIES IS A INCLUSIVE
 PACKAGE WITHIN THE SUBMITTED PLANS. THERE ARE CIVIL,
 SITE, LANDSCAPING, IRRIGATION, GREASE INTERCEPTORS,
 FUEL GAS, GENERATOR, FIRE SPRINKLER, FIRE ALARM,
 LOWVOLTAGE, AWNINGS AND SIGNAGE PLANS WITHIN THE
 SUBMITTED DOCUMENTS.
 THESE TYPE OF ACTIVITIES REQUIRE A SEPARATE PERMIT
 APPLICATION, REVIEW AND ASSOCIATED FEES. PLEASE BACK
 OUT THE VALUE OF WORK TO BE COMPLETED UNDER EACH OF
 THESE PERMITS SO THE BUILDING DEPARTMENT DOES NOT
 CHARGE YOU TWICE FOR THESE SERVICES. 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 105.1 PERMITS
  
 2) THE APPLIED VALUE OF THE HOTEL IS VALUED AT
 $35,000,000.00. THE CALCULATED VALUE OF THE PROJECT IS
 $55,930,374.00 (312,216 SQ FT X $179.14 BUILDING ONLY,
 NO SITE DEVELOPMENT) USING THE ICC BUILDING VALUATION
 DATA FOR BOTH AUGUST 2013 & FEB, 2014. W P B
 ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. ON
 BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, AND
 PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A
 FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
 IF A BUILDING BREAK OUT OF SQUARE FOOTAGE UNDER EACH
 OCCUPANCY CLASSIFICATION THIS NUMBER WOUD DROP SOME
 WHAT, THIS WAS UNOT COMPLETED UNDER THE OCCUPANCY
 CLASSIFICATION, PROBANLY BECAUSE OF UNLIMITED AREA FOR
 A TYPE 1A BUILDING TYPE.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 3) 0210-A2.00:
  
 3A) HEADING: PROJECT NAME LIST THE ADDRESS FORTHIS
 PROJECT AS 901 FLORIDA AVENUE, PLEASE UPDATE THE
 ADDRESS FOR THIS SITE TO 600 OKEECHOBEE BLVD. WEST PALM
 BEACH, FL. (PALM BEACH COUNTY).
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.2.1. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. 2010 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW
 AND EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS NUMBERS OR LETTERS.
  
 3B) HEADING: APPLICABLE CODES LIST THE (4) FLORIDA
 BUILDING CODE-TEST PROTOCOLS FOR HIGH VELOCITY
 HURRICANE ZONES- 2010 EDITION PLEASE NOTE THIS PORTION
 OF THE CODE IS FOR BROWARD AND MIAMI-DADE COUNTIES. THE
 ONLY REASON WE MAY LOOK AT THIS CODE IS IF A MIAMI-DADE
 NOA NOTICE OF ACCEPTANCE REPORT IS SUBMITTED, THE
 PRESCRIPTIVE REQUIREMENTS OF THIS CODE HAVE NOT AND CAN
 NOT BE USED IN THIS JURISDICTION.
  
 3C) HEADING CONSTRUCTION TYPE: LIST THE CODE SECTION
 FOR OPEN PARIKNG GARAGES FBC 406.3.5 OPEN PARKING
 GARAGES, PLEASE NOTE THE OPEN PARKING GARAGE IS ON
 ANOTHER PROPERTY, WITH A SEPARATE ADDRESS. THIS
 STRUCTURE WILL REQUIRE A SEPARATE PERMIT, REVIEW AND
 ASSOCIATED FEES, FOR RECORD RECORDING PURPOSES. 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 105.1 PERMIT REQUIRED.
  
 3D) THE FIRE RESISTANCE REQUIREMENTS- WALLS DOES NOT
 PROVIDE THE RATING OF THE R-1 TENANT WALLS FOUND IN
 SECTION 2010 FBC-B 439.2 FIRE PARTITIONS.
  
 PLEASE PROVIDE THE ACTUAL SQUARE FOOTAGE OF THE
 BUILDING FOOT PRINT AS WELL AS THE SQUARE FOOTAGE FOR
 THE TOWER AND THE TOTAL OVER ALL SQUARE FOOTAGE UNDER
 ROOF, THESE ARE REQUIREMENTS FOR RECORD KEEPING AND
 PRINTING OF CERTIFICATE OF OCCUPANCY. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3E) SHEET A2.00 WHILE THIS SHEET PROVIDES TABLES FOR
 OCCUPANCY CLASSIFICATION & OCCUPANT LOAD FACTORS THE
 LIFR SAFETY SHEET DOES NOT PROVIDE OCCUPANT LOADS PER
 FLOOR OR FOR THE TOTAL BUILDING. 2010 FBC-B 1004.1
 DESIGN OCCUPANT LOAD.
  
 4) 0211-A2.01/ BASEMENT LEVEL:
  
 4A) THE SERVICE COORIDOR B000 IN FRONT OF THE HOUSEMANS
 STORAGE AND HOUSE KEEPING LAUNDRY IT APPEARS THERE IS
 STORAGE CABINETS BEING STORED WITHIN THE CORRIDOR?
 PLEASE EXPLAIN THE USAGE OF THIS AREA? 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 4B) THE 2 ROOMS TO THE LEFT OF STORAGE ROOM B005 DO NOT
 PROVIDE IDENTIFICATION, OR USAGE BUT INDICATE A 2 HR
 FIRE RATING PLEASE IDENTIFY ROOMS AND OCCUPANCY. FBC-B
 TABLE 508.4.
  
 5) 0212-A2.02/ LEVEL 0100
  
 5A) IN THE LAST MEETING ALOT OF DISCUSSION TOOK PLACE
 ABOUT THE CONNECTOR BETWEEN THE CONVENTION CENTER AND
 THE HOTEL PROPERTY. ONE TOPIC WAS A DELUGE SYSTEM
 REQUIRED FOR THE GLAZING. 3104.5 REQUIRES A 2 HR
 SEPARATION, WALKWAYS SHALL BE SEPARATED FROM THE
 INTERIOR OF THE BUILDING BY NOT LESS THAN 2 HOURS.
 THERE ARE 4 EXCEPTIONS TO THE CODE. THERE ARE 4
 EXCEPTIONS TO THIS REQUIREMENT.
 WITHIN EXCEPTION # 1 THERE IS 3 COMPONENTS:
 1). THE THE WALL IS CAPABLE OF RESISTING THE PASSAGE OF
 SMOKE OR IS CONSTRUCTED OF A TEMPERED, WIRED OR
 LAMINATED GLASS WALL AND DOORS SUBJECT TO THE
 FOLLOWING:
 1.1. THE WALL OR GLASS SEPARATING THE INTERIOR OF THE
 BUILDING FROM THE PEDESTRIAN WALKWAY SHALL BE PROTECTED
 BY AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 903.3.1.1 AND THE SPRINKLER SYSTEM SHALL
 COMPLETELY WET THE ENTIRE SURFACE OF INTERIOR SIDES OF
 THE WALL OR GLASS WHEN ACTUATED;
 1.2. THE GLASS SHALL BE IN A GASKETED FRAME AND
 INSTALLED IN SUCH A MANNER THAT THE FRAMING SYSTEM WILL
 DEFLECT WITHOUT BREAKING (LOADING) THE GLASS BEFORE THE
 SPRINKLER OPERATES; AND
 1.3. OBSTRUCTIONS SHALL NOT BE INSTALLED BETWEEN THE
 SPRINKLER HEADS AND THE WALL OR GLASS.
  
 THE ISSUE WITH THIS EXCEPTION STATES THE INTERIOR SIDE
 OF THE GLASS SHALL BE PROTECTED WITH A SPRINKLER, WHEN
 THE DOORS ARE OPEN THEY WILL NOT BE PROTECTED.
  
 5B) ON THE EMERGENCY EXITING SIDE OF THE CONNECTOR THE
 PLANS STATE THAT THE DOORWAY WILL ACCEPT 640 OCCUPANTS.
 PLEASE REVIEW THE DOORWAY LEADING FROM THE JR.
 BALLROOMS WITH A OCCUPANT LOAD OF 320 OCCUPANTS, THE
 LEFT HAND DOOR BLOCKS ONE OF THE 4 EXIT DOORWAYS
 REDUCING THE CLEAR WIDTH OF THE OPENING. THE OTHER
 ISSUE WITH THIS CONFIGURATION IS THE SAME DOUBLE DOORS
 LEADING FROM THE JR BALLROOMS, THE RIGHT HAND DOOR IS
 PARTIALLY BLOCKED BY THE LEADING EDGE OF THE INSWING
 DOOR, THERE IS ONLY A FOOT UNTIL THIS DOOR SWING
 BECOMES AN OBSTRUCTION AGAIN DECREASING THE ABILITY TO
 GET THE DECLARED OCCUPANT LOAD OUT THIS EXIT THE ACTUAL
 OCCUPANT ACCESS LOADS ARE SKEWED. 2010 FBC-B 1005.1.,
 1005.2 & FBC-B 1008.1.1.1.
  
 5C) PLEASE PROVIDE IF THE LULA LIFT IS ON STANDBY
 POWER? IF THE 3 HOUR FIRE DOOR IS ACTIVATED BY THE FIRE
 ALARM AND IS CLOSED WILL A OCCUPANT IN THE LULA LIFT IF
 LOCATED ON THE LOWER LEVEL BE ABLE TO OPERATE THE LIFT
 TO THE UPPER LANDING TO BE ABLE TO ESCAPE FROM THE
 BUILDING? FBC-B 403.4.7.2 (3) DOES NOT SAY ANYTHING
 ABOUT LIFTS.
 [F] 403.4.7.2 STANDBY POWER LOADS.
 THE FOLLOWING ARE CLASSIFIED AS STANDBY POWER LOADS: 3.
 STANDBY POWER SHALL BE PROVIDED FOR ELEVATORS IN
 ACCORDANCE WITH SECTIONS 1006.2.4, 3003, 3007 AND 3008.
  
 5D) WHAT APPEARS TO BE THE MENS RESTROOM, NOT LABELED,
 BY THE WOMENS RESTROOM # 116 THIS RESTROOM HAS 4
 QUESTION MARKS WITHIN THE RESTROOM.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 5E) THE LAST MEETING THERE WAS DISCUSSION ABOUT THE
 RATING OF THE COORIDOR IN FRONT OF THE RESTARAUNT 115.
 THE CODE ALLOWS FOR 250 FEET (FBC-B TABLE 1016.1)
 BEFORE HAVING TO REACH EITHER A PROTECTED EXIT FRONT
 THE ENTRANCE OF THE BALL ROOM TO THE FRONT ENTRY THE
 TRAVEL DISTANCE IS APPROXIMATELY 237 FEET. THE OTHER
 ISSUE IS REQUIED EXIT ACCESS CORRIDORS, FBC-B 1018.1
 FOR AN ASSEMBLY OCCUPANCY IN A FIRE SPRINKLERED
 BUILDING THERE IS NO FIRE RATING REQUIRED FOR THIS
 CORRIDOR, YOU SEE THIS IN CONFIGURATION IN MALLS &
 AIRPORT CONCOURSES AND TERMINAL.
  
 5F) MEETING ROOM 2 & 3 WHEN COMBINED THE DIAGONAL
 DISTANCE FROM CORNER TO CORNER APPEARS TO BE 57.2 FEET
 ON THE DIAGONAL AND THE TO ENTRY DOORS ONLY BEING
 13'-0" APART CENTERLINE TO CENTER LINE NOT THE 18'-7 "
 AS INDICATED ON THE PLANS. 2010 FBC-B 1015.2.1 EXCEP #
 2.
  
 5G) NOT SHOWN ON THIS SHEET BUT A4.04 DOES SHOW THE
 WEST PROPERTY LINE GOING THROUGH THE CABANAS AND POOL
 ON THE WEST OF THE PROPERTY.
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE'
 SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
  
 6) 0213-A-2.03 0200 LEVEL:
  
 6A) SERVICE ELEVATOR LOBBY TO MAKE CHANGES AS PER THE
 LAST MEETING AS DISCUSSED.
  
 6B) THE MEETING ROOM # 1, BOARDROOM & MEETING ROOM # 2
 ARE TO BE REWORKED AS THE LAST MEETING ALLOWING EACH OF
 THE ADJACENT ROOMS TO BE CONSIDERED INTERVENING ROOMS
 AS PER FBC-B 1014.2 AND THE CORRIDOR DOORS THAT
 SEPARATE THE 2 STORY ATRIUM BE MOVED CLOSER IN TO THE
 ATRIUM AREA ALLOWING EGRESS FROM MEETING ROOM 1 & 2
 INTO THE RATED PORTION OF THE CORRIDOR ACCHIEVING CODE
 COMPLIANCE WITH A HYBRID TYPE OF ATRIM WALL RATED 1 HR
 AND ACHIEVING EXITING WITHOUT HAVING TO TRAVEL THROUGH
 A UNPROTECTED ATRIUM.
  
 7) 0214-A-2.04 / 0300 LEVEL. PLEASE REVIEW GUEST ROOM #
 346 IT APPEARS TO BE MISSING A LAVATORY. SEE DEFITITION
 OF SLEEPING ROOM.
  
 8)0221-A2.11 0100 LEVEL: GUEST ROOM #1046 IS A SHELL
 ROOM, PLEASE PROVIDE A OCCUPANCY TYPE AND OCCUPANCY
 LOAD FOR THIS UNIT, AS DEPICTED THIS MAY BE A ASSMBLY
 OCCUPANCY, PLEASE PROVIDE ADDITIONAL DETAILS THIS ROOM
 IS AN ADJOINING ROOM WITH SUITE # 1044 WHAT IS THE FIRE
 RATING OF THE 2 COMMUNICATING DOORS. FBC-B 302.1, TABLE
 508.4 & TABLE 715.4.
  
 9A) 0222-A2.12/ 1200 LEVEL ROOM 1136 THE EXECUTIVE
 LOUNGE HAS A OCCUPANT LOAD OF 96 THIS IS AN ASSEMBLY
 OCCUPANCY PLEASE PROVIDE A FURNATURE LATOUT. SHEET
 A3.00 DOES NOT INCLUDE THIS ROOM IN THE PLUMBING
 FIXTURE COUNT. DEPENDING ON THE USAGE THIS MAY BE
 CONSIDERED EIHER AN A2 OR A3, IF CONSIDERED MORE AS A
 LOUNGE A-2 THE WATER CLOSET RATIO WILL BE 1/40
 REQUIRING ADDITIONAL FIXTURES.
  
 9B) 0222-A2.12/ 1200 LEVEL ROOM 1136 THE EXECUTIVE
 LOUNGE, THERE IS A SMALL ROOM THAT NO INFORMATION HAS
 BEEN PROVIDED, IS THIS FOR STORAGE, BAR OR KITCHEN TO
 BE USED IN CONJUNCTION WITH THE LOUNGE? FBC-B 302.1.
  
 10) A201 LIFE SAFETY BASEMENT PLAN VERSES A4.00 VERSES
 DOOR SCHEDULE.
  
 10A) THE DOMESTIC PUMP ROOM B002 IS SHOWN TO HAVE 2 HR
 RATED WALLS WHERE AS THE DOOR SCHEDULE INDICATESS THE
 DOOR TO BE A 45 MINUTE DOOR.
 2010 FBC-B TABLE 715.4/ 2HR RATED WALLS REQUIRES 1 1/2
 HR PROTECTIVES.
  
 10B) THE STORE ROOM B005 IS INDICATED TO HAVE 1 HR
 WALLS WHERE AS THE DOOR SCHEDULE INDICATES DOOR B005 TO
 BE 90 MIN. FBC-B TABLE 715.4.
  
 10C) THE LAUNDRY ROOM WALLS ARE SHOWN AS 1 HR RATED
 WALLS WHEREAS THE DOOR SCHEDULE INDICATES B006 TO BE A
 90 MIN. DOOR. FBC-B TABLE 715.4.
  
 10D) ROOM B013 SOILED LINEN ROOM IS ALSO THE
 TERMINATION ROOM FOR THE LAUNDRY CHUTE THE WALLS ARE
 INDICATED TO BE ONE HOUR WHERE AS THE DOORS SHOW AS 90
 MINUTE RATED. SEE 708.11 & 708.13.4. THE LAUNDRY CHUTE
 MUST HAVE A 2 HOUR FIRE RATING AT THE END OF THE CHUTE
 TO KEEP THE 1 HR FIRE RATING OF THE ROOM AND 45 MINUTE
 OPENING PROTECTIVES. FBC-B TABLE 715.4.
  
 10E) STAIR # 2, DOOR # B)16A BLOCKS THE STAIRWAY, 2010
 FBC-B 1008.1.1.1 PROJECTIONS INTO THE CLEAR WIDTH.
 1008.1.6 LANDINGS AT DOORS & 1009.5 STAIRWELL LANDINGS
 BLOCKS THE REQUIRED LANDING LENGHT.
  
 11) A2.02 VERSES A4.01 AND DOOR SCHEDULE:
  
 11A) WALLS SHOWN ON A2.02 TO BE 1 HOUR FIRE RATED,
 DOORS IDENTIFIED ON A4.01 AND DOOR SCHEDULE , DOORS
 MISSING RATING IN THE DOOR SCHEDULE ARE
 DOOR 121L, DOOR 121N & DOOR 121O. FBC-B TABLE 715.4
  
 11B) STAIR # 6 A 2 HOUR FIRE RATING AND DOOR SCHEDULE
 MISSING 1 1/2 HR PROTECTIVE . FBC-B TABLE 715.4.
  
 11C) ROOM POOL STORAGE IS A 1 HR RATING , DOOR SCHEDULE
 MISSING FIRE RATING. FBC-B TABLE 715.4.
  
 12) A2.02 VERSES A4.02 AND DOOR SCHEDULE:
  
 12A) FPL VAULT 3 HR FIRE RATING THE DOOR SCHEDULE IS
 MISSING THE1 1/2 HOUR FIRE RATING PER NEC 450.21.
  
 13) SHEET A2.02 & A4.03, SHEET A4.03 COUNTING ROOM 112N
 TABLE IS BLOCKING THE EGRESS DOOR. 2010 FBC-B
 1008.1.1.1 PROJECTIONS INTO THE CLEAR WIDTH.
  
 14) SHEET A2.03 VS A4.07:
  
 14A) SHEET A2.03 INDICATES A 1HR FIRE RATING BETWEEN
 SLEEPING ROOMS IN ACCORDANCE WITH 709.1, PLEASE NOTE
 709.3 DOES NOT GIVE THE 1/2 HR REDUCTION IN WALL RATINS
 SINCE THIS IS A TYPE IA CONSTRUCTION. THE EXCEPTION IS
 FOR IIB, IIIB & VB CONSTRUCTION. THE COMMUNICATING
 DOORS T12 WILL REQUIRE A 3/4 HR FIRE RATED DOOR. THE
 DOOR SCHEDULE DOES NOT INDICATE ANY FIRE RATING. IF
 TRYING TO USE 2/ 20 MIN DOORS, PLEASE SHOW A TESTED
 ASSEMBLY MEETING THE 3/4 HR FIRE RATING. THIS COMMENT
 WILL STAND FOR ALL FLOORS WITH SLEEPING ROOMS WITH
 INTER-CONNECTING DOORS.
  
 14B) DOOR # 219 NOTE # 20 INDICATES THE USE OF A CARD
 READER TO GAIN ACCESS TO THE VERTICAL EXIT STAIRWAY.
 SHEET A2.00 DOES NOT PROVIDE THE ACTUAL OCCUPANT LOADS
 FOR ANY FLOORS PLEASE PROVIDE A MATRIX WITH OCCUPANT
 LOADS PER FLOOR. FBC-B TABLE 1021.1 ONLY REQUIRES 2
 VERTICAL EXITS IF THE OCCUPANT LOAD IS 500 OR LESS,
 REMOTENESS IS MET WITH STAIRWELL 1 &3 WITH THE
 EXCEPTION OF THE TOP 3 FLOORS THERE THE CARD READER
 WOULD NEED TO BE REMOVED. THE TOP FLOOR IS LESS THAN
 120'-0" IN HEIGHT, A FIRE SERVICE ELEVATOR (403.6.1
 REQUIRED AT 120 FT OCCUPIED FLOOR LEVEL) IS NOT
 REQUIRED, THIS STAIR AND ELEVATOR COULD BE FOR BACK OF
 HOUSE USE ONLY AND LIMITED TO EMPLOYEES ONLY. IF THE
 ELEVATORS ARE TO BE FOR THE FIREMEN THEN THE ACCESS
 CARD READERS WOULD NEED TO BE CONNECTED TO THE FIRE
 COMMAND ROOM FOR THIER USE IN CASE OF EMERGENCY.
  
 14C) THE OTHER ISSUE IS THE WAY THE ATRIUM WALL RATING
 IS BEING CONSIDERED AS THE 1 HOUR WALL AT THE MEETING
 ROOMS & BOARD ROOM. THE LAST MEETING IT WAS DISCUSSED
 THAT THERE WOULD BE FIRE RATED DOOR OPENINGS AT EACH
 SIDE OF THE ATRIUM AREA AND NEW COMMUNACATING DOORS
 WITHIN THE BOARDROOM AND MEETING ROOMS TO CREATE
 INTERVENING ROOMS AND A WAY FOR THE OCCUPANTS WITH THE
 BOARD & MEETING ROOMS TO EXIT INTO A EXIT ACCESS
 CORRIDOR.
 TO DO THIS WILL THERE BE EXIT DIRECTIONAL SIGNS SHOWING
 THIS AS A PART OF THE EGRESS PATH. THE OTHER QUESTION
 IS THE A3 ASSEMBLY BOARD & MEETING ROOMS WILL REQUIRE A
 INTERIOR FINISH FOR THE ROOMS AS A C AND THE CORRIDORS
 AS A B, NOW WILL THE MEETING ROOMS BE CONSIDERED
 CORRIDORS AND A B INTERIOR JUST AS THE CORRIDOR. NOTE
 THE ASSEMBLY OCCUPANCY NOW WILL BE EXITING INTO THE
 PORTION OF THE CORRIDOR FOR THE HOTEL ROOMS BUT WILL
 NEED TO MAINTAIN THE FINISH FOR CORRIDORS AS FOR A3
 OCCUPANCY A B FINISH. TABLE 803.9.
  
 ROOMS 201- 217 HAVE THE TWO MEANS OF EGRESS, ROOMS 235
 THRU 250 WILL BE REQUIRED TO TRAVEL THRU THE MEETING
 ROOMS TO MEET THE REQUIRED 2 MEANS OF EGRESS. FBC-B
 TABLE 1018.1 FINSHES & TABLE 1021.1 MINIMUM EXITS.
  
 14D) PLEASE SEE MEETING ROOM # 2 THE LOCAION OF THE ONE
 HOUR RATED WALLTHE PURPLE LINE REPRESENTING THE RATED
 WALL GOES AROUND THE DUCTWOK THAT COMES UP FROM THE 1ST
 FLOOR 48"X15", THE MECHANICAL SHEET M-1.08 DOES NOT
 SHOW A DAMPER IN IT. IT APPEARS THE FIRE RATING SHOULD
 BE ONLY BEHIND THE DUCTWORK, THEN NO DAMPER WOULD BE
 REQUIRED, 713.1.1 DUCTS AND AIR TRANSFER OPENINGS.
  
 15) SHEET A2.03 VS A4.08:
  
 15A) DETAIL 7/12.05 IS A FIRE EXTINGUISHER CABINET IN A
 FIRE RATED WALL, THE DETAILS ON 12.05 DO NOT INDICATE
 HOW THE FIRE RATINGS ARE TO BE MAINTAINED IN THE FIRE
 RATED WALLS. ON SOME OF THE DETAILS FEC RATING SHOULD
 BE SIMILAR TO WALL RATING. PLEASE PROVIDE HOW THE FIRE
 RATING WILL BE MAINTAINED.
  
 15B) SUITE OF ROOMS 240 & 247 DO HAVE INTERVENING ROOMS
 AND DO MEET THE COMMON PATH OF TRAVEL OF 50 FT. ALL
 SUITES WILL NEED TO MEET THE 50' COMMON PATH OF TRAVEL
 FOR A R1 OCCUPANCY. FBC-B 1014.3 ECP # 6.
  
 16) SHEET A4.20 SECTION THRU BUILDING A12.10 :
  
 16A NOTES ON THE PLANS INDICATES THE USE OF ALUMINUM
 COMPOSITE WALL PANELS, PLEASE PROVIDE DOCUMENTATION FOR
 CODE COMPLIANCE WITH: 2010 FBC-B
 1407.2 EXTERIOR WALL FINISH.
 MCM USED AS EXTERIOR WALL FINISH OR AS ELEMENTS OF
 BALCONIES AND SIMILAR PROJECTIONS AND BAY AND ORIEL
 WINDOWS TO PROVIDE CLADDING OR WEATHER RESISTANCE SHALL
 COMPLY WITH SECTIONS 1407.4 THROUGH 1407.14.
  
 16B) A12.10 DETAILS 1 & 8 BOTH INDICATE THE PERIMETER
 SUN SCREEN , DETAIL 3 A12.09 ALSO A CLOSE UP OF THE
 PERIMETER SUNSCREEN INDICATE THE USE OF
 STEEL EMBEDS W/ NELSON BOLTS PER THE MANUFACTURERS
 REQUIREMENTS. PLEASE PROVIDE ENGINEERING FOR THIS
 SYSTEM THAT THE DESIGN AND ATTACHMENTS WILL MEET THE
 WINDLOADS AND HEIGHT ADJUSTMENT FACTORS FOR THIS
 ELEVATION, TO BE DESIGNED TO ASCE 7-10 .1609.1.1
 DETERMINATION OF WIND LOADS.
 WIND LOADS ON EVERY BUILDING OR STRUCTURE SHALL BE
 DETERMINED IN ACCORDANCE WITH CHAPTERS 26 THROUGH 30 OF
 ASCE 7 OR THE PROVISIONS OF THE ALTERNATE ALL HEIGHTS
 METHOD IN SECTION 1609.6. L
  
 17A) SHEET # A5.00 THIS COMMENT WILL STAND FOR ALL
 FLOORS. TYPICAL STANDARD KING. THE PLANS INDICATE A
 WALL TAG 28C WITHIN THE BATHROOM THAT BACKS UP TO
 ANOTHER SLEEPING UNIT. TENANT SEPARATION WALL NOT
 RATED. FBC-B 709.1(6). THE WALL TAG 28C USES
 ABBREVIATIONS GMGB AND SAFB NOT FOUND IN THE
 ABBRREVIATIONS FOUND ON SHEET A0.02. PLEASE PROVIDE
 WHAT THIS STAND FOR? ALSO SEE COMPLIANCE WITH 2010
 FBC-B 2509.2 BASE FOR TILE.
 GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS,
 DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE
 SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENT
 SUBSTRATE SHEETS IN COMPLIANCE WITH ASTM C 1178, C 1288
 OR C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER
 RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN
 SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS.
 REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR
 WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840.
 2509.3 LIMITATIONS. WATER-RESISTANT GYPSUM BACKING
 BOARD SHALL NOT BE USED IN THE FOLLOWING LOCATIONS:
 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB
 COMPARTMENTS.
 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN
 AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY.
 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES
 (305 MM) O.C. FOR 1/2-INCH-THICK (12.7 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16
 INCHES (406 MM) O.C. FOR 5/8-INCH-THICK (15.9 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD.
  
 17B) TYPICAL STANDARD KING TENANT SEPERATION WALL, WALL
 TAG 5B DETAIL SHEET 11/1200 INDICATES FIRE RATING NOT
 REQUIRED. FBC-B 709.1(6).
  
 18) ) SHEET A5.11:
 A) SHEET A5.11 VERSES A2.02 SEE WALL RATINGS OF 1 HOUR
 WALL TAGS 7, 5C & 13 DO NOT SHOW THE 1 HOUR FIRE RATING
 THAT THE LIFE SAFETY PLANS INDICATE.
  
 B) SHEET A5.11 0100 LEVEL BOH RESTROOM PLANS DOES NOT
 MATCH UP WITH A2.02. WALL TYPE IDENTIFIED AS WALL TAG
 10A IS INDICATED AS A 2 HR WALL THIS WALL IS A COMMON
 WALL TO THE FPL VAULT A 3 HR RATED WALL. WALL TAG 3B IS
 INDICATED AS NOT RATED BY WALL TAG, A2.02 THE LIFE
 SAFETY PLANS INDICATES THIS WALL TO BE A 1 HOUR FIRE
 RATED WALL. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED, DISCREPANCY IN PLANS.
  
 C)SHEET A5.11 0100 LEVEL BOH RESTROOM PLANS DOES NOT
 MATCH UP WITH A2.02. WALL TYPE IDENTIFIED AS WALL TAG
 3B IS INDICATED AS A NON-RATED WALL A2.02 LIFE SAFETY
 SHEET A 1 HOUR RATED WALL. 107.2.1.3 DISCREPANCY IN
 PLANS. ADDITIONAL INFORMATION IS REQUIRED.
  
 19) SHEET A5.12 :
 A) WALL TAGS 5A COMMON TO RESTROOM 124 AND PRE-FUNCTION
 AREA ARE INDICATED NOT TO BE FIRE RATED WHERE AS A2.02
 LIFE SAFETY SHEET INDICATES THEM TO BE A 1 HOUR FIRE
 RATING. 107.2.1.3 DISCREPANCY IN PLANS. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 B) POOL STORAGE ROOM 126, MISSING WALL TAG FOR THE
 COMMON WALL WITH MENS RESTROOM 125, LIFE SAFETY SHOW
 THE BLOCKWALL A 2 HR FIRE RATED WALL. 107.2.1.3
 DISCREPANCY IN PLANS. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 C) ) POOL STORAGE ROOM 126, MISSING WALL TAG FOR THE
 COMMON WALL WITH MENS RESTROOM 125, LIFE SAFETY SHOW
 THE BLOCKWALL A 2 HR FIRE RATED WALL. 107.2.1.3
 DISCREPANCY IN PLANS. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 20) SHEET A5.15:
 A) ADMINISTRATIVE OFFICES WALL IDENTIFICATION TAGS LIFE
 SAFETY SHEET INDICATES THIS TO BE A 1 HOUR FIRE RATING
 WHERE AS THE WALL IDENTIFICATION TAGS INDICATE A 2 HR.
 107.2.1.3.DISCREPANCY. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 B) SHEET A5.15 COMMON WALL OF SERVICE CORRIDOR AND
 PAYMASTER AT WATER FOUNTAINS WALL IDENTIFICATION TAG
 28C. THIS WALL TAG INDICATES THIS A NON-FIRE RATED WALL
 WHERE AS THE LIFE SAFETY PLAN SHOW THE ONE HOUR FIRE
 RATING GOING THROUGH BEHIND THE WATER FOUNTAINS.
 107.2.1.3.DISCREPANCY. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 21) SHEET A5.16 DOCK OFFICE WALL IDENTIFICATION TAGS 4A
 & 2A BOTH INDICATE A 1 HOUR FIRERATING WHERE AS THE
 LIFE SAFETY PLAN INDICATES THESE WALLS AS 2 HR FIRE
 RATING. WINDOW IN A 2 HR RATED WALL 1 1/2 HOUR
 PROTECTIVE. 107.2.1.3.DISCREPANCY. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 22) SHEET A5.17:
 A) THE FPL VAULT SWITH ROOMS DO NOT HAVE WALL
 IDENTIFICATION TAGS, NOR DOES THE 2 SWITCH ROOMS HAVE
 ROOM IDENTIFICATION NUMBERS.
 107.2.1.3.DISCREPANCY. ADDITIONAL INFORMATION IS
 REQUIRED. SEE LIFE SAFETY PLAN FOR WALL FIRE RATING.
  
 B) NEITHER THE LIFE SAFETY PLAN NOR A5.17 PROVIDE
 WHATTHE REQUIRED FIRE RATING OF THE FPL VAULT CEILING
 IS? SEE A2.00 FPL TRANSFORMER VAULT 2008 NEC 450.21.
  
 C) SHEET A5.17 FPL VAULT DOOR # 143 DOOR HARDWARE
 SCHEDULE UPDATE HARDWARE SEE SECTION FBC-B 1008.1.10
 PANIC AND FIRE EXIT HARDWARE. ELECTRICAL ROOMS WITH
 EQUIPMENT RATED 1,200 AMPERES OR MORE AND OVER 6 FEET
 (1829 MM) WIDE THAT CONTAIN OVERCURRENT DEVICES,
 SWITCHING DEVICES OR CONTROL DEVICES WITH EXIT OR EXIT
 ACCESS DOORS SHALL BE EQUIPPED WITH PANIC HARDWARE OR
 FIRE EXIT HARDWARE. THE DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS TRAVEL.
  
 23) A5.18:
 WALL IDENTIFICATION TAGS ARE MISSING AND IDENTIFICATION
 OF FIRE RATED WALLS. ADDITIONAL INFORMATION IS
 REQUIRED. SEE LIFE SAFETY PLAN FOR WALL FIRE RATING
 DISCREPANCY IN PLANS. 107.2.1.3.
  
 24) A7.03, A7.05 & A7.10 THE STAIR FLOOR PLANS DO NOT
 INDICATE THE REQUIRED STANDPIPES 2010 FBC-B 905.3. [F]
 403.3.1.1 RISER LOCATION.
 SPRINKLER RISERS SHALL BE PLACED IN EXIT ENCLOSURES
 THAT ARE REMOTELY LOCATED IN ACCORDANCE WITH SECTION
 1015.2.
  
  
 25) SHEET A7.15 THE LINEN CHUTE DETAIL AT THE 12TH
 FLOOR THE 2 HOUR RATED SHAFT STOPS SHORT OF THE ROOF
 DECK, YET THE LAUNDRY CHUTE CONTINUES THROUGH THE ROOF.
 708.12 ENCLOSURE AT THE TOP. A SHAFT ENCLOSURE THAT
 DOES NOT EXTEND TO THE UNDERSIDE OF THE ROOF SHEATHING,
 DECK OR SLAB OF THE BUILDING SHALL BE ENCLOSED AT THE
 TOP WITH CONSTRUCTION OF THE SAME FIRE-RESISTANCE
 RATING AS THE TOPMOST FLOOR PENETRATED BY THE SHAFT,
 BUT NOT LESS THAN THE FIRE-RESISTANCE RATING REQUIRED
 FOR THE SHAFT ENCLOSURE.
  
 26) SHEET A2.10 SHOWS THE LAUNDRY CHUTE LOCATED ON THE
 GRID LINES X.1 JUST NORTH & Y.2 CENTERED ON THE GRID
 LINE WHICH IS LOCATED IN THE MAIDS ROOM.
 FLOORS 10-12 SEE SHEET A2.11 THE LAUBDRY CHUTE IS
 OFFSET TO THE NORTHEAST OR TO THE EAST OF GRID LINE Y.2
 . THE PLANS SHOW THE ACCESS TO THE ACCESS CHUTE DOOR
 LOCATED WITH THE CORRADOR. PLEASE CONFORM WITH:
  
 2010 FBC-B 708.13.3 REFUSE AND LAUNDRY CHUTE ACCESS
 ROOMS.
 ACCESS OPENINGS FOR REFUSE AND LAUNDRY CHUTES SHALL BE
 LOCATED IN ROOMS OR COMPARTMENTS ENCLOSED BY NOT LESS
 THAN 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE
 WITH SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED
 IN ACCORDANCE WITH SECTION 712, OR BOTH. OPENINGS INTO
 THE ACCESS ROOMS SHALL BE PROTECTED BY OPENING
 PROTECTIVES HAVING A FIRE PROTECTION RATING OF NOT LESS
 THAN 3/4 HOUR. DOORS SHALL BE SELF- OR
 AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE IN
 ACCORDANCE WITH SECTION 715.4.8.3.
  
 27) SHEET A7.15 THE LINEN CHUTE DETAILS DO NOT MENTION
 THE REQUIREMENT OR ANY ALLOWANCES FOR FIRE SPRINKLERS
 IN THE LINEN CHUTE. THE FIRE SPRINKLER SHEETS ONLY
 PROVIDE A DEAIL ON FP0.01 INDICATING SERVICE CHUTE
 DETAIL.
 708.13.6 AUTOMATIC SPRINKLER SYSTEM.
 AN APPROVED AUTOMATIC SPRINKLER SYSTEM SHALL BE
 INSTALLED IN ACCORDANCE WITH SECTION 903.2.11.2 F]
 903.2.11.2 RUBBISH AND LINEN CHUTES.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED AT THE
 TOP OF RUBBISH AND LINEN CHUTES AND IN THEIR TERMINAL
 ROOMS. CHUTES EXTENDING THROUGH THREE OR MORE FLOORS
 SHALL HAVE ADDITIONAL SPRINKLER HEADS INSTALLED WITHIN
 SUCH CHUTES AT ALTERNATE FLOORS. CHUTE SPRINKLERS SHALL
 BE ACCESSIBLE FOR SERVICING.
  
 THE LAUNDRY CHUTE DETAIL SHEET ALSO DOESN'T MAKE
 REFERANCE TO THE REQUIREMENT FOR CHUTE SPRINKLERS SHALL
 BE ACCESSIBLE FOR SERVICING.
  
 28A) SHEET A7.03, A7.07 & A7.10 THE STAIR PLANS AND
 NOTES DO NOT INDICATE COMPLIANCE WITH 2010 FBC-B
 403.5.5 AND SECION 1024 LUMINOUS EGRESS PATH MARKINGS.
  
 28B) THESE SHEETS ALSO ARE MISSING COMPLIANCE WITH
 403.5.3.1 STAIRWAY COMMUNICATION SYSTEMS.
  
 29) SHEET A12.20 DETAILS 4A & 4B SHOW THE USE OF PIING
 PILE CAPS AND GRADE BEAMS, AREN'T THE PILES BEING
 ELIMINATED? 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 30) SHEET A12.22 DETAIL # 1 SPRAY APPLIED
 FIRE-RESISTANCE MATERIALS INDICATES SEE DETAIL ON
 A12.04 SPRAY APPLIED RESISTIVE MATERIAL. PLEASE PROVIDE
 COMPLIANCE WITH FBC-B 403.2.4 SPRAYED FIRE-RESISTANT
 MATERIALS (SFRM).
 THE BOND STRENGTH OF THE SFRM INSTALLED THROUGHOUT THE
 BUILDING SHALL BE IN ACCORDANCE WITH TABLE
 403.2.4.HEIGHT OF BUILDING (A FOOTNOTE)
 SFRM MINIMUM BOND STRENGTH UP TO 420 FEET 430 PSF (A)
 ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE
 ACCESS.
  
 31) SHEET A12.09.2 ALUMINUM FRAMED GLASS CANOPY DETAILS
 PLEASE PROVIDE COMPLIANCE WITH GLAZING REQUIREMENTS
 FOUND UNDER THE 2010 FBC-B
 2405.2 ALLOWABLE GLAZING MATERIALS AND LIMITATIONS.
 SLOPED GLAZING SHALL BE ANY OF THE FOLLOWING MATERIALS,
 SUBJECT TO THE LISTED LIMITATIONS.
 1. FOR MONOLITHIC GLAZING SYSTEMS, THE GLAZING MATERIAL
 OF THE SINGLE LIGHT OR LAYER SHALL BE LAMINATED GLASS
 WITH A MINIMUM 30-MIL (0.76 MM) POLYVINYL BUTYRAL (OR
 EQUIVALENT) INTERLAYER, WIRED GLASS, LIGHT-TRANSMITTING
 PLASTIC MATERIALS MEETING THE REQUIREMENTS OF SECTION
 2607, HEAT-STRENGTHENED GLASS OR FULLY TEMPERED GLASS.
 2. FOR MULTIPLE-LAYER GLAZING SYSTEMS, EACH LIGHT OR
 LAYER SHALL CONSIST OF ANY OF THE GLAZING MATERIALS
 SPECIFIED IN ITEM 1 ABOVE.
 ANNEALED GLASS IS PERMITTED TO BE USED AS SPECIFIED
 WITHIN EXCEPTIONS 2 AND 3 OF SECTION 2405.3.
 FOR ADDITIONAL REQUIREMENTS FOR PLASTIC SKYLIGHTS, SEE
 SECTION 2610. GLASS-BLOCK CONSTRUCTION SHALL CONFORM TO
 THE REQUIREMENTS OF SECTION 2101.2.5.
  
 32)) SHEET A5.04 PLEASE REVIEW THE HOSPITALITY SUITES
 DETAIL 1 & 2 NEITHER OF THESE SUITES SHOW UP ON THE
 FLORIDA ACCESSIBLITY ROOM MATRIX. PLEASE REVIEW 2010 FL
 ACCESSIBILITY SECTION 224.5 THESE UNITS DO HAVE
 KITCHENS IN THEM WHERE AS NONE OF THE OTHER UNITS IN
 THE MATRIX INDICATE SUITES WITH KITCHENS NOR ARE THE
 BATHROOMS ACCESSIBLE.
  
 33) SHEET S0.00 THE WIND DESIGN CRITERIA IS SHOWN IN
 VULT, PLEASE PROVIDE THE PRESSURES IN VASD SINCE ALL
 PRODUCT APPROVALS ARE PRINTED IN VASD.
 TABLE 1609.3. IS THIS PROJECT GOING TO DO WIND TUNNEL
 TESTING TO REDUCE PRESSURES?
  
 34) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 35) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 36) SHEET M5.1 SMOKE CONTROL NOTES UNDER THE HEADING
 GENERAL , SMOKE CONTROL NOTES AND SMOKE CONTROL
 SEQUENCE THE NOTES DO NOT MAKE IT CLEAR HOW THE SMOKE
 CONTROL SYSTEM IS TO OPERATE.
 2010 FBC-B 03.4.6 SMOKE REMOVAL.SMOKE CONTROL SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 909. SECTION 909
 PROVIDES VARIOUS METHODS OF COMPLYING WITH SMOKE
 CONTROL:
 909.6 PRESSURIZATION METHOD.
 909.7 AIRFLOW DESIGN METHOD.
 909.8 EXHAUST METHOD.
 909.9 DESIGN FIRE.
  
 [F] 909.2 GENERAL DESIGN REQUIREMENTS.
 BUILDINGS, STRUCTURES OR PARTS THEREOF REQUIRED BY THIS
 CODE TO HAVE A SMOKE CONTROL SYSTEM OR SYSTEMS SHALL
 HAVE SUCH SYSTEMS DESIGNED IN ACCORDANCE WITH THE
 APPLICABLE REQUIREMENTS OF SECTION 909 AND THE
 GENERALLY ACCEPTED AND WELL-ESTABLISHED PRINCIPLES OF
 ENGINEERING RELEVANT TO THE DESIGN. THE CONSTRUCTION
 DOCUMENTS SHALL INCLUDE SUFFICIENT INFORMATION AND
 DETAIL TO ADEQUATELY DESCRIBE THE ELEMENTS OF THE
 DESIGN NECESSARY FOR THE PROPER IMPLEMENTATION OF THE
 SMOKE CONTROL SYSTEMS. THESE DOCUMENTS SHALL BE
 ACCOMPANIED BY SUFFICIENT INFORMATION AND ANALYSIS TO
 DEMONSTRATE COMPLIANCE WITH THESE PROVISIONS.
  
 [F] 909.3 SPECIAL INSPECTION AND TEST REQUIREMENTS.
 IN ADDITION TO THE ORDINARY INSPECTION AND TEST
 REQUIREMENTS WHICH BUILDINGS, STRUCTURES AND PARTS
 THEREOF ARE REQUIRED TO UNDERGO, SMOKE CONTROL SYSTEMS
 SUBJECT TO THE PROVISIONS OF SECTION 909 SHALL UNDERGO
 SPECIAL INSPECTIONS AND TESTS SUFFICIENT TO VERIFY THE
 PROPER COMMISSIONING OF THE SMOKE CONTROL DESIGN IN ITS
 FINAL INSTALLED CONDITION. THE DESIGN SUBMISSION
 ACCOMPANYING THE CONSTRUCTION DOCUMENTS SHALL CLEARLY
 DETAIL PROCEDURES AND METHODS TO BE USED AND THE ITEMS
 SUBJECT TO SUCH INSPECTIONS AND TESTS. SUCH
 COMMISSIONING SHALL BE IN ACCORDANCE WITH GENERALLY
 ACCEPTED ENGINEERING PRACTICE AND, WHERE POSSIBLE,
 BASED ON PUBLISHED STANDARDS FOR THE PARTICULAR TESTING
 INVOLVED.
  
 [F] 909.4 ANALYSIS.
 A RATIONAL ANALYSIS SUPPORTING THE TYPES OF SMOKE
 CONTROL SYSTEMS TO BE EMPLOYED, THEIR METHODS OF
 OPERATION, THE SYSTEMS SUPPORTING THEM AND THE METHODS
 OF CONSTRUCTION TO BE UTILIZED SHALL ACCOMPANY THE
 SUBMITTED CONSTRUCTION DOCUMENTS AND SHALL INCLUDE, BUT
 NOT BE LIMITED TO, THE ITEMS INDICATED IN SECTIONS
 909.4.1 THROUGH 909.4.6.
  
 37) PLEASE PROVIDE CODE COMPLIANCE WITH: 2010 FBC-B [F]
 914.2 EQUIPMENT ROOM IDENTIFICATION.
 FIRE PROTECTION EQUIPMENT SHALL BE IDENTIFIED IN AN
 APPROVED MANNER. ROOMS CONTAINING CONTROLS FOR
 AIR-CONDITIONING SYSTEMS, SPRINKLER RISERS AND VALVES
 OR OTHER FIRE DETECTION, SUPPRESSION OR CONTROL
 ELEMENTS SHALL BE IDENTIFIED FOR THE USE OF THE FIRE
 DEPARTMENT. APPROVED SIGNS REQUIRED TO IDENTIFY FIRE
 PROTECTION EQUIPMENT AND EQUIPMENT LOCATION SHALL BE
 CONSTRUCTED OF DURABLE MATERIALS, PERMANENTLY INSTALLED
 AND READILY VISIBLE.
  
 38) EMERGENCY RESPONDER RADIO COVERAGE SHALL BE
 PROVIDED IN ALL NEW BUILDINGS IN ACCORDANCE THE FLORIDA
 FIRE PREVENTION CODE.
  
 39) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B [F]
 911.1.5 REQUIRED FEATURES. THE FIRE COMMAND CENTER
 SHALL COMPLY WITH NFPA 72 AND SHALL CONTAIN THE
 FOLLOWING FEATURES: 1-17.
  
 40) THE SUBMITTED DOCUMENTS FOR 1ST REVIEW DID NOT
 PROVIDE DOCUMENTS FOR THE ENERGY CODE FOR COMPLIANCE.
 SEE 2010 FBC-ENERGY 103.2.1 & 103.2.3.1.2.
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  