| 2014-06-05 06:31:33 | BUILDING PLAN REVIEW |
| | PERMIT:14050111 |
| | ADD: 600 OKEECHOBEE BLVD |
| | CONT: COASTAL CONSTRUCTION |
| | TEL: (561) 630-3770 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | THE PALM BEACH CONVENTION CENTER HILTON HOTEL |
| | CONSTRUCTION OF NEW 400 ROOM HOTEL INCLUDING BALLROOMS, |
| | RESTAURANT(S), MEETING SPACE, POOL DECK AND AMENITIES |
| | |
| | 1ST REVIEW |
| | DATE: TUESDAY JUNE 17TH/ 2014 |
| | |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT DESCRIPTION LISTED ABOVE TO BUILD THE |
| | HOTEL, POOL, POOL DECK & AMENITIES IS A INCLUSIVE |
| | PACKAGE WITHIN THE SUBMITTED PLANS. THERE ARE CIVIL, |
| | SITE, LANDSCAPING, IRRIGATION, GREASE INTERCEPTORS, |
| | FUEL GAS, GENERATOR, FIRE SPRINKLER, FIRE ALARM, |
| | LOWVOLTAGE, AWNINGS AND SIGNAGE PLANS WITHIN THE |
| | SUBMITTED DOCUMENTS. |
| | THESE TYPE OF ACTIVITIES REQUIRE A SEPARATE PERMIT |
| | APPLICATION, REVIEW AND ASSOCIATED FEES. PLEASE BACK |
| | OUT THE VALUE OF WORK TO BE COMPLETED UNDER EACH OF |
| | THESE PERMITS SO THE BUILDING DEPARTMENT DOES NOT |
| | CHARGE YOU TWICE FOR THESE SERVICES. 2010 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION 105.1 PERMITS |
| | |
| | 2) THE APPLIED VALUE OF THE HOTEL IS VALUED AT |
| | $35,000,000.00. THE CALCULATED VALUE OF THE PROJECT IS |
| | $55,930,374.00 (312,216 SQ FT X $179.14 BUILDING ONLY, |
| | NO SITE DEVELOPMENT) USING THE ICC BUILDING VALUATION |
| | DATA FOR BOTH AUGUST 2013 & FEB, 2014. W P B |
| | ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. ON |
| | BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, AND |
| | PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A |
| | FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| | ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| | APPLICABLE GOVERNING AUTHORITY. |
| | IF A BUILDING BREAK OUT OF SQUARE FOOTAGE UNDER EACH |
| | OCCUPANCY CLASSIFICATION THIS NUMBER WOUD DROP SOME |
| | WHAT, THIS WAS UNOT COMPLETED UNDER THE OCCUPANCY |
| | CLASSIFICATION, PROBANLY BECAUSE OF UNLIMITED AREA FOR |
| | A TYPE 1A BUILDING TYPE. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 3) 0210-A2.00: |
| | |
| | 3A) HEADING: PROJECT NAME LIST THE ADDRESS FORTHIS |
| | PROJECT AS 901 FLORIDA AVENUE, PLEASE UPDATE THE |
| | ADDRESS FOR THIS SITE TO 600 OKEECHOBEE BLVD. WEST PALM |
| | BEACH, FL. (PALM BEACH COUNTY). |
| | |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 107.2.1. CONSTRUCTION |
| | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| | THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED |
| | AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. 2010 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW |
| | AND EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED |
| | ADDRESS NUMBERS OR LETTERS. |
| | |
| | 3B) HEADING: APPLICABLE CODES LIST THE (4) FLORIDA |
| | BUILDING CODE-TEST PROTOCOLS FOR HIGH VELOCITY |
| | HURRICANE ZONES- 2010 EDITION PLEASE NOTE THIS PORTION |
| | OF THE CODE IS FOR BROWARD AND MIAMI-DADE COUNTIES. THE |
| | ONLY REASON WE MAY LOOK AT THIS CODE IS IF A MIAMI-DADE |
| | NOA NOTICE OF ACCEPTANCE REPORT IS SUBMITTED, THE |
| | PRESCRIPTIVE REQUIREMENTS OF THIS CODE HAVE NOT AND CAN |
| | NOT BE USED IN THIS JURISDICTION. |
| | |
| | 3C) HEADING CONSTRUCTION TYPE: LIST THE CODE SECTION |
| | FOR OPEN PARIKNG GARAGES FBC 406.3.5 OPEN PARKING |
| | GARAGES, PLEASE NOTE THE OPEN PARKING GARAGE IS ON |
| | ANOTHER PROPERTY, WITH A SEPARATE ADDRESS. THIS |
| | STRUCTURE WILL REQUIRE A SEPARATE PERMIT, REVIEW AND |
| | ASSOCIATED FEES, FOR RECORD RECORDING PURPOSES. 2010 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 105.1 PERMIT REQUIRED. |
| | |
| | 3D) THE FIRE RESISTANCE REQUIREMENTS- WALLS DOES NOT |
| | PROVIDE THE RATING OF THE R-1 TENANT WALLS FOUND IN |
| | SECTION 2010 FBC-B 439.2 FIRE PARTITIONS. |
| | |
| | PLEASE PROVIDE THE ACTUAL SQUARE FOOTAGE OF THE |
| | BUILDING FOOT PRINT AS WELL AS THE SQUARE FOOTAGE FOR |
| | THE TOWER AND THE TOTAL OVER ALL SQUARE FOOTAGE UNDER |
| | ROOF, THESE ARE REQUIREMENTS FOR RECORD KEEPING AND |
| | PRINTING OF CERTIFICATE OF OCCUPANCY. 107.2.1.3. |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3E) SHEET A2.00 WHILE THIS SHEET PROVIDES TABLES FOR |
| | OCCUPANCY CLASSIFICATION & OCCUPANT LOAD FACTORS THE |
| | LIFR SAFETY SHEET DOES NOT PROVIDE OCCUPANT LOADS PER |
| | FLOOR OR FOR THE TOTAL BUILDING. 2010 FBC-B 1004.1 |
| | DESIGN OCCUPANT LOAD. |
| | |
| | 4) 0211-A2.01/ BASEMENT LEVEL: |
| | |
| | 4A) THE SERVICE COORIDOR B000 IN FRONT OF THE HOUSEMANS |
| | STORAGE AND HOUSE KEEPING LAUNDRY IT APPEARS THERE IS |
| | STORAGE CABINETS BEING STORED WITHIN THE CORRIDOR? |
| | PLEASE EXPLAIN THE USAGE OF THIS AREA? 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 4B) THE 2 ROOMS TO THE LEFT OF STORAGE ROOM B005 DO NOT |
| | PROVIDE IDENTIFICATION, OR USAGE BUT INDICATE A 2 HR |
| | FIRE RATING PLEASE IDENTIFY ROOMS AND OCCUPANCY. FBC-B |
| | TABLE 508.4. |
| | |
| | 5) 0212-A2.02/ LEVEL 0100 |
| | |
| | 5A) IN THE LAST MEETING ALOT OF DISCUSSION TOOK PLACE |
| | ABOUT THE CONNECTOR BETWEEN THE CONVENTION CENTER AND |
| | THE HOTEL PROPERTY. ONE TOPIC WAS A DELUGE SYSTEM |
| | REQUIRED FOR THE GLAZING. 3104.5 REQUIRES A 2 HR |
| | SEPARATION, WALKWAYS SHALL BE SEPARATED FROM THE |
| | INTERIOR OF THE BUILDING BY NOT LESS THAN 2 HOURS. |
| | THERE ARE 4 EXCEPTIONS TO THE CODE. THERE ARE 4 |
| | EXCEPTIONS TO THIS REQUIREMENT. |
| | WITHIN EXCEPTION # 1 THERE IS 3 COMPONENTS: |
| | 1). THE THE WALL IS CAPABLE OF RESISTING THE PASSAGE OF |
| | SMOKE OR IS CONSTRUCTED OF A TEMPERED, WIRED OR |
| | LAMINATED GLASS WALL AND DOORS SUBJECT TO THE |
| | FOLLOWING: |
| | 1.1. THE WALL OR GLASS SEPARATING THE INTERIOR OF THE |
| | BUILDING FROM THE PEDESTRIAN WALKWAY SHALL BE PROTECTED |
| | BY AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| | SECTION 903.3.1.1 AND THE SPRINKLER SYSTEM SHALL |
| | COMPLETELY WET THE ENTIRE SURFACE OF INTERIOR SIDES OF |
| | THE WALL OR GLASS WHEN ACTUATED; |
| | 1.2. THE GLASS SHALL BE IN A GASKETED FRAME AND |
| | INSTALLED IN SUCH A MANNER THAT THE FRAMING SYSTEM WILL |
| | DEFLECT WITHOUT BREAKING (LOADING) THE GLASS BEFORE THE |
| | SPRINKLER OPERATES; AND |
| | 1.3. OBSTRUCTIONS SHALL NOT BE INSTALLED BETWEEN THE |
| | SPRINKLER HEADS AND THE WALL OR GLASS. |
| | |
| | THE ISSUE WITH THIS EXCEPTION STATES THE INTERIOR SIDE |
| | OF THE GLASS SHALL BE PROTECTED WITH A SPRINKLER, WHEN |
| | THE DOORS ARE OPEN THEY WILL NOT BE PROTECTED. |
| | |
| | 5B) ON THE EMERGENCY EXITING SIDE OF THE CONNECTOR THE |
| | PLANS STATE THAT THE DOORWAY WILL ACCEPT 640 OCCUPANTS. |
| | PLEASE REVIEW THE DOORWAY LEADING FROM THE JR. |
| | BALLROOMS WITH A OCCUPANT LOAD OF 320 OCCUPANTS, THE |
| | LEFT HAND DOOR BLOCKS ONE OF THE 4 EXIT DOORWAYS |
| | REDUCING THE CLEAR WIDTH OF THE OPENING. THE OTHER |
| | ISSUE WITH THIS CONFIGURATION IS THE SAME DOUBLE DOORS |
| | LEADING FROM THE JR BALLROOMS, THE RIGHT HAND DOOR IS |
| | PARTIALLY BLOCKED BY THE LEADING EDGE OF THE INSWING |
| | DOOR, THERE IS ONLY A FOOT UNTIL THIS DOOR SWING |
| | BECOMES AN OBSTRUCTION AGAIN DECREASING THE ABILITY TO |
| | GET THE DECLARED OCCUPANT LOAD OUT THIS EXIT THE ACTUAL |
| | OCCUPANT ACCESS LOADS ARE SKEWED. 2010 FBC-B 1005.1., |
| | 1005.2 & FBC-B 1008.1.1.1. |
| | |
| | 5C) PLEASE PROVIDE IF THE LULA LIFT IS ON STANDBY |
| | POWER? IF THE 3 HOUR FIRE DOOR IS ACTIVATED BY THE FIRE |
| | ALARM AND IS CLOSED WILL A OCCUPANT IN THE LULA LIFT IF |
| | LOCATED ON THE LOWER LEVEL BE ABLE TO OPERATE THE LIFT |
| | TO THE UPPER LANDING TO BE ABLE TO ESCAPE FROM THE |
| | BUILDING? FBC-B 403.4.7.2 (3) DOES NOT SAY ANYTHING |
| | ABOUT LIFTS. |
| | [F] 403.4.7.2 STANDBY POWER LOADS. |
| | THE FOLLOWING ARE CLASSIFIED AS STANDBY POWER LOADS: 3. |
| | STANDBY POWER SHALL BE PROVIDED FOR ELEVATORS IN |
| | ACCORDANCE WITH SECTIONS 1006.2.4, 3003, 3007 AND 3008. |
| | |
| | 5D) WHAT APPEARS TO BE THE MENS RESTROOM, NOT LABELED, |
| | BY THE WOMENS RESTROOM # 116 THIS RESTROOM HAS 4 |
| | QUESTION MARKS WITHIN THE RESTROOM. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 5E) THE LAST MEETING THERE WAS DISCUSSION ABOUT THE |
| | RATING OF THE COORIDOR IN FRONT OF THE RESTARAUNT 115. |
| | THE CODE ALLOWS FOR 250 FEET (FBC-B TABLE 1016.1) |
| | BEFORE HAVING TO REACH EITHER A PROTECTED EXIT FRONT |
| | THE ENTRANCE OF THE BALL ROOM TO THE FRONT ENTRY THE |
| | TRAVEL DISTANCE IS APPROXIMATELY 237 FEET. THE OTHER |
| | ISSUE IS REQUIED EXIT ACCESS CORRIDORS, FBC-B 1018.1 |
| | FOR AN ASSEMBLY OCCUPANCY IN A FIRE SPRINKLERED |
| | BUILDING THERE IS NO FIRE RATING REQUIRED FOR THIS |
| | CORRIDOR, YOU SEE THIS IN CONFIGURATION IN MALLS & |
| | AIRPORT CONCOURSES AND TERMINAL. |
| | |
| | 5F) MEETING ROOM 2 & 3 WHEN COMBINED THE DIAGONAL |
| | DISTANCE FROM CORNER TO CORNER APPEARS TO BE 57.2 FEET |
| | ON THE DIAGONAL AND THE TO ENTRY DOORS ONLY BEING |
| | 13'-0" APART CENTERLINE TO CENTER LINE NOT THE 18'-7 " |
| | AS INDICATED ON THE PLANS. 2010 FBC-B 1015.2.1 EXCEP # |
| | 2. |
| | |
| | 5G) NOT SHOWN ON THIS SHEET BUT A4.04 DOES SHOW THE |
| | WEST PROPERTY LINE GOING THROUGH THE CABANAS AND POOL |
| | ON THE WEST OF THE PROPERTY. |
| | UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE |
| | TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS |
| | WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE' |
| | SHALL BE |
| | RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE |
| | RECORDED 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE |
| | 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| | NOT APPLICABLE. |
| | SEE WEBSITE FOR APPLICATION: |
| | HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP |
| | "APPLICATION FOR UNITY OF TITLE" |
| | HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45 |
| | -38-UNITYOFTITLE3.PDF |
| | |
| | 6) 0213-A-2.03 0200 LEVEL: |
| | |
| | 6A) SERVICE ELEVATOR LOBBY TO MAKE CHANGES AS PER THE |
| | LAST MEETING AS DISCUSSED. |
| | |
| | 6B) THE MEETING ROOM # 1, BOARDROOM & MEETING ROOM # 2 |
| | ARE TO BE REWORKED AS THE LAST MEETING ALLOWING EACH OF |
| | THE ADJACENT ROOMS TO BE CONSIDERED INTERVENING ROOMS |
| | AS PER FBC-B 1014.2 AND THE CORRIDOR DOORS THAT |
| | SEPARATE THE 2 STORY ATRIUM BE MOVED CLOSER IN TO THE |
| | ATRIUM AREA ALLOWING EGRESS FROM MEETING ROOM 1 & 2 |
| | INTO THE RATED PORTION OF THE CORRIDOR ACCHIEVING CODE |
| | COMPLIANCE WITH A HYBRID TYPE OF ATRIM WALL RATED 1 HR |
| | AND ACHIEVING EXITING WITHOUT HAVING TO TRAVEL THROUGH |
| | A UNPROTECTED ATRIUM. |
| | |
| | 7) 0214-A-2.04 / 0300 LEVEL. PLEASE REVIEW GUEST ROOM # |
| | 346 IT APPEARS TO BE MISSING A LAVATORY. SEE DEFITITION |
| | OF SLEEPING ROOM. |
| | |
| | 8)0221-A2.11 0100 LEVEL: GUEST ROOM #1046 IS A SHELL |
| | ROOM, PLEASE PROVIDE A OCCUPANCY TYPE AND OCCUPANCY |
| | LOAD FOR THIS UNIT, AS DEPICTED THIS MAY BE A ASSMBLY |
| | OCCUPANCY, PLEASE PROVIDE ADDITIONAL DETAILS THIS ROOM |
| | IS AN ADJOINING ROOM WITH SUITE # 1044 WHAT IS THE FIRE |
| | RATING OF THE 2 COMMUNICATING DOORS. FBC-B 302.1, TABLE |
| | 508.4 & TABLE 715.4. |
| | |
| | 9A) 0222-A2.12/ 1200 LEVEL ROOM 1136 THE EXECUTIVE |
| | LOUNGE HAS A OCCUPANT LOAD OF 96 THIS IS AN ASSEMBLY |
| | OCCUPANCY PLEASE PROVIDE A FURNATURE LATOUT. SHEET |
| | A3.00 DOES NOT INCLUDE THIS ROOM IN THE PLUMBING |
| | FIXTURE COUNT. DEPENDING ON THE USAGE THIS MAY BE |
| | CONSIDERED EIHER AN A2 OR A3, IF CONSIDERED MORE AS A |
| | LOUNGE A-2 THE WATER CLOSET RATIO WILL BE 1/40 |
| | REQUIRING ADDITIONAL FIXTURES. |
| | |
| | 9B) 0222-A2.12/ 1200 LEVEL ROOM 1136 THE EXECUTIVE |
| | LOUNGE, THERE IS A SMALL ROOM THAT NO INFORMATION HAS |
| | BEEN PROVIDED, IS THIS FOR STORAGE, BAR OR KITCHEN TO |
| | BE USED IN CONJUNCTION WITH THE LOUNGE? FBC-B 302.1. |
| | |
| | 10) A201 LIFE SAFETY BASEMENT PLAN VERSES A4.00 VERSES |
| | DOOR SCHEDULE. |
| | |
| | 10A) THE DOMESTIC PUMP ROOM B002 IS SHOWN TO HAVE 2 HR |
| | RATED WALLS WHERE AS THE DOOR SCHEDULE INDICATESS THE |
| | DOOR TO BE A 45 MINUTE DOOR. |
| | 2010 FBC-B TABLE 715.4/ 2HR RATED WALLS REQUIRES 1 1/2 |
| | HR PROTECTIVES. |
| | |
| | 10B) THE STORE ROOM B005 IS INDICATED TO HAVE 1 HR |
| | WALLS WHERE AS THE DOOR SCHEDULE INDICATES DOOR B005 TO |
| | BE 90 MIN. FBC-B TABLE 715.4. |
| | |
| | 10C) THE LAUNDRY ROOM WALLS ARE SHOWN AS 1 HR RATED |
| | WALLS WHEREAS THE DOOR SCHEDULE INDICATES B006 TO BE A |
| | 90 MIN. DOOR. FBC-B TABLE 715.4. |
| | |
| | 10D) ROOM B013 SOILED LINEN ROOM IS ALSO THE |
| | TERMINATION ROOM FOR THE LAUNDRY CHUTE THE WALLS ARE |
| | INDICATED TO BE ONE HOUR WHERE AS THE DOORS SHOW AS 90 |
| | MINUTE RATED. SEE 708.11 & 708.13.4. THE LAUNDRY CHUTE |
| | MUST HAVE A 2 HOUR FIRE RATING AT THE END OF THE CHUTE |
| | TO KEEP THE 1 HR FIRE RATING OF THE ROOM AND 45 MINUTE |
| | OPENING PROTECTIVES. FBC-B TABLE 715.4. |
| | |
| | 10E) STAIR # 2, DOOR # B)16A BLOCKS THE STAIRWAY, 2010 |
| | FBC-B 1008.1.1.1 PROJECTIONS INTO THE CLEAR WIDTH. |
| | 1008.1.6 LANDINGS AT DOORS & 1009.5 STAIRWELL LANDINGS |
| | BLOCKS THE REQUIRED LANDING LENGHT. |
| | |
| | 11) A2.02 VERSES A4.01 AND DOOR SCHEDULE: |
| | |
| | 11A) WALLS SHOWN ON A2.02 TO BE 1 HOUR FIRE RATED, |
| | DOORS IDENTIFIED ON A4.01 AND DOOR SCHEDULE , DOORS |
| | MISSING RATING IN THE DOOR SCHEDULE ARE |
| | DOOR 121L, DOOR 121N & DOOR 121O. FBC-B TABLE 715.4 |
| | |
| | 11B) STAIR # 6 A 2 HOUR FIRE RATING AND DOOR SCHEDULE |
| | MISSING 1 1/2 HR PROTECTIVE . FBC-B TABLE 715.4. |
| | |
| | 11C) ROOM POOL STORAGE IS A 1 HR RATING , DOOR SCHEDULE |
| | MISSING FIRE RATING. FBC-B TABLE 715.4. |
| | |
| | 12) A2.02 VERSES A4.02 AND DOOR SCHEDULE: |
| | |
| | 12A) FPL VAULT 3 HR FIRE RATING THE DOOR SCHEDULE IS |
| | MISSING THE1 1/2 HOUR FIRE RATING PER NEC 450.21. |
| | |
| | 13) SHEET A2.02 & A4.03, SHEET A4.03 COUNTING ROOM 112N |
| | TABLE IS BLOCKING THE EGRESS DOOR. 2010 FBC-B |
| | 1008.1.1.1 PROJECTIONS INTO THE CLEAR WIDTH. |
| | |
| | 14) SHEET A2.03 VS A4.07: |
| | |
| | 14A) SHEET A2.03 INDICATES A 1HR FIRE RATING BETWEEN |
| | SLEEPING ROOMS IN ACCORDANCE WITH 709.1, PLEASE NOTE |
| | 709.3 DOES NOT GIVE THE 1/2 HR REDUCTION IN WALL RATINS |
| | SINCE THIS IS A TYPE IA CONSTRUCTION. THE EXCEPTION IS |
| | FOR IIB, IIIB & VB CONSTRUCTION. THE COMMUNICATING |
| | DOORS T12 WILL REQUIRE A 3/4 HR FIRE RATED DOOR. THE |
| | DOOR SCHEDULE DOES NOT INDICATE ANY FIRE RATING. IF |
| | TRYING TO USE 2/ 20 MIN DOORS, PLEASE SHOW A TESTED |
| | ASSEMBLY MEETING THE 3/4 HR FIRE RATING. THIS COMMENT |
| | WILL STAND FOR ALL FLOORS WITH SLEEPING ROOMS WITH |
| | INTER-CONNECTING DOORS. |
| | |
| | 14B) DOOR # 219 NOTE # 20 INDICATES THE USE OF A CARD |
| | READER TO GAIN ACCESS TO THE VERTICAL EXIT STAIRWAY. |
| | SHEET A2.00 DOES NOT PROVIDE THE ACTUAL OCCUPANT LOADS |
| | FOR ANY FLOORS PLEASE PROVIDE A MATRIX WITH OCCUPANT |
| | LOADS PER FLOOR. FBC-B TABLE 1021.1 ONLY REQUIRES 2 |
| | VERTICAL EXITS IF THE OCCUPANT LOAD IS 500 OR LESS, |
| | REMOTENESS IS MET WITH STAIRWELL 1 &3 WITH THE |
| | EXCEPTION OF THE TOP 3 FLOORS THERE THE CARD READER |
| | WOULD NEED TO BE REMOVED. THE TOP FLOOR IS LESS THAN |
| | 120'-0" IN HEIGHT, A FIRE SERVICE ELEVATOR (403.6.1 |
| | REQUIRED AT 120 FT OCCUPIED FLOOR LEVEL) IS NOT |
| | REQUIRED, THIS STAIR AND ELEVATOR COULD BE FOR BACK OF |
| | HOUSE USE ONLY AND LIMITED TO EMPLOYEES ONLY. IF THE |
| | ELEVATORS ARE TO BE FOR THE FIREMEN THEN THE ACCESS |
| | CARD READERS WOULD NEED TO BE CONNECTED TO THE FIRE |
| | COMMAND ROOM FOR THIER USE IN CASE OF EMERGENCY. |
| | |
| | 14C) THE OTHER ISSUE IS THE WAY THE ATRIUM WALL RATING |
| | IS BEING CONSIDERED AS THE 1 HOUR WALL AT THE MEETING |
| | ROOMS & BOARD ROOM. THE LAST MEETING IT WAS DISCUSSED |
| | THAT THERE WOULD BE FIRE RATED DOOR OPENINGS AT EACH |
| | SIDE OF THE ATRIUM AREA AND NEW COMMUNACATING DOORS |
| | WITHIN THE BOARDROOM AND MEETING ROOMS TO CREATE |
| | INTERVENING ROOMS AND A WAY FOR THE OCCUPANTS WITH THE |
| | BOARD & MEETING ROOMS TO EXIT INTO A EXIT ACCESS |
| | CORRIDOR. |
| | TO DO THIS WILL THERE BE EXIT DIRECTIONAL SIGNS SHOWING |
| | THIS AS A PART OF THE EGRESS PATH. THE OTHER QUESTION |
| | IS THE A3 ASSEMBLY BOARD & MEETING ROOMS WILL REQUIRE A |
| | INTERIOR FINISH FOR THE ROOMS AS A C AND THE CORRIDORS |
| | AS A B, NOW WILL THE MEETING ROOMS BE CONSIDERED |
| | CORRIDORS AND A B INTERIOR JUST AS THE CORRIDOR. NOTE |
| | THE ASSEMBLY OCCUPANCY NOW WILL BE EXITING INTO THE |
| | PORTION OF THE CORRIDOR FOR THE HOTEL ROOMS BUT WILL |
| | NEED TO MAINTAIN THE FINISH FOR CORRIDORS AS FOR A3 |
| | OCCUPANCY A B FINISH. TABLE 803.9. |
| | |
| | ROOMS 201- 217 HAVE THE TWO MEANS OF EGRESS, ROOMS 235 |
| | THRU 250 WILL BE REQUIRED TO TRAVEL THRU THE MEETING |
| | ROOMS TO MEET THE REQUIRED 2 MEANS OF EGRESS. FBC-B |
| | TABLE 1018.1 FINSHES & TABLE 1021.1 MINIMUM EXITS. |
| | |
| | 14D) PLEASE SEE MEETING ROOM # 2 THE LOCAION OF THE ONE |
| | HOUR RATED WALLTHE PURPLE LINE REPRESENTING THE RATED |
| | WALL GOES AROUND THE DUCTWOK THAT COMES UP FROM THE 1ST |
| | FLOOR 48"X15", THE MECHANICAL SHEET M-1.08 DOES NOT |
| | SHOW A DAMPER IN IT. IT APPEARS THE FIRE RATING SHOULD |
| | BE ONLY BEHIND THE DUCTWORK, THEN NO DAMPER WOULD BE |
| | REQUIRED, 713.1.1 DUCTS AND AIR TRANSFER OPENINGS. |
| | |
| | 15) SHEET A2.03 VS A4.08: |
| | |
| | 15A) DETAIL 7/12.05 IS A FIRE EXTINGUISHER CABINET IN A |
| | FIRE RATED WALL, THE DETAILS ON 12.05 DO NOT INDICATE |
| | HOW THE FIRE RATINGS ARE TO BE MAINTAINED IN THE FIRE |
| | RATED WALLS. ON SOME OF THE DETAILS FEC RATING SHOULD |
| | BE SIMILAR TO WALL RATING. PLEASE PROVIDE HOW THE FIRE |
| | RATING WILL BE MAINTAINED. |
| | |
| | 15B) SUITE OF ROOMS 240 & 247 DO HAVE INTERVENING ROOMS |
| | AND DO MEET THE COMMON PATH OF TRAVEL OF 50 FT. ALL |
| | SUITES WILL NEED TO MEET THE 50' COMMON PATH OF TRAVEL |
| | FOR A R1 OCCUPANCY. FBC-B 1014.3 ECP # 6. |
| | |
| | 16) SHEET A4.20 SECTION THRU BUILDING A12.10 : |
| | |
| | 16A NOTES ON THE PLANS INDICATES THE USE OF ALUMINUM |
| | COMPOSITE WALL PANELS, PLEASE PROVIDE DOCUMENTATION FOR |
| | CODE COMPLIANCE WITH: 2010 FBC-B |
| | 1407.2 EXTERIOR WALL FINISH. |
| | MCM USED AS EXTERIOR WALL FINISH OR AS ELEMENTS OF |
| | BALCONIES AND SIMILAR PROJECTIONS AND BAY AND ORIEL |
| | WINDOWS TO PROVIDE CLADDING OR WEATHER RESISTANCE SHALL |
| | COMPLY WITH SECTIONS 1407.4 THROUGH 1407.14. |
| | |
| | 16B) A12.10 DETAILS 1 & 8 BOTH INDICATE THE PERIMETER |
| | SUN SCREEN , DETAIL 3 A12.09 ALSO A CLOSE UP OF THE |
| | PERIMETER SUNSCREEN INDICATE THE USE OF |
| | STEEL EMBEDS W/ NELSON BOLTS PER THE MANUFACTURERS |
| | REQUIREMENTS. PLEASE PROVIDE ENGINEERING FOR THIS |
| | SYSTEM THAT THE DESIGN AND ATTACHMENTS WILL MEET THE |
| | WINDLOADS AND HEIGHT ADJUSTMENT FACTORS FOR THIS |
| | ELEVATION, TO BE DESIGNED TO ASCE 7-10 .1609.1.1 |
| | DETERMINATION OF WIND LOADS. |
| | WIND LOADS ON EVERY BUILDING OR STRUCTURE SHALL BE |
| | DETERMINED IN ACCORDANCE WITH CHAPTERS 26 THROUGH 30 OF |
| | ASCE 7 OR THE PROVISIONS OF THE ALTERNATE ALL HEIGHTS |
| | METHOD IN SECTION 1609.6. L |
| | |
| | 17A) SHEET # A5.00 THIS COMMENT WILL STAND FOR ALL |
| | FLOORS. TYPICAL STANDARD KING. THE PLANS INDICATE A |
| | WALL TAG 28C WITHIN THE BATHROOM THAT BACKS UP TO |
| | ANOTHER SLEEPING UNIT. TENANT SEPARATION WALL NOT |
| | RATED. FBC-B 709.1(6). THE WALL TAG 28C USES |
| | ABBREVIATIONS GMGB AND SAFB NOT FOUND IN THE |
| | ABBRREVIATIONS FOUND ON SHEET A0.02. PLEASE PROVIDE |
| | WHAT THIS STAND FOR? ALSO SEE COMPLIANCE WITH 2010 |
| | FBC-B 2509.2 BASE FOR TILE. |
| | GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS, |
| | DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE |
| | SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENT |
| | SUBSTRATE SHEETS IN COMPLIANCE WITH ASTM C 1178, C 1288 |
| | OR C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER |
| | RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE |
| | IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN |
| | SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD |
| | SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET |
| | COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH |
| | GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS. |
| | REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR |
| | WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN |
| | INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840. |
| | 2509.3 LIMITATIONS. WATER-RESISTANT GYPSUM BACKING |
| | BOARD SHALL NOT BE USED IN THE FOLLOWING LOCATIONS: |
| | 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB |
| | COMPARTMENTS. |
| | 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN |
| | AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY. |
| | 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES |
| | (305 MM) O.C. FOR 1/2-INCH-THICK (12.7 MM) |
| | WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16 |
| | INCHES (406 MM) O.C. FOR 5/8-INCH-THICK (15.9 MM) |
| | WATER-RESISTANT GYPSUM BACKING BOARD. |
| | |
| | 17B) TYPICAL STANDARD KING TENANT SEPERATION WALL, WALL |
| | TAG 5B DETAIL SHEET 11/1200 INDICATES FIRE RATING NOT |
| | REQUIRED. FBC-B 709.1(6). |
| | |
| | 18) ) SHEET A5.11: |
| | A) SHEET A5.11 VERSES A2.02 SEE WALL RATINGS OF 1 HOUR |
| | WALL TAGS 7, 5C & 13 DO NOT SHOW THE 1 HOUR FIRE RATING |
| | THAT THE LIFE SAFETY PLANS INDICATE. |
| | |
| | B) SHEET A5.11 0100 LEVEL BOH RESTROOM PLANS DOES NOT |
| | MATCH UP WITH A2.02. WALL TYPE IDENTIFIED AS WALL TAG |
| | 10A IS INDICATED AS A 2 HR WALL THIS WALL IS A COMMON |
| | WALL TO THE FPL VAULT A 3 HR RATED WALL. WALL TAG 3B IS |
| | INDICATED AS NOT RATED BY WALL TAG, A2.02 THE LIFE |
| | SAFETY PLANS INDICATES THIS WALL TO BE A 1 HOUR FIRE |
| | RATED WALL. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED, DISCREPANCY IN PLANS. |
| | |
| | C)SHEET A5.11 0100 LEVEL BOH RESTROOM PLANS DOES NOT |
| | MATCH UP WITH A2.02. WALL TYPE IDENTIFIED AS WALL TAG |
| | 3B IS INDICATED AS A NON-RATED WALL A2.02 LIFE SAFETY |
| | SHEET A 1 HOUR RATED WALL. 107.2.1.3 DISCREPANCY IN |
| | PLANS. ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 19) SHEET A5.12 : |
| | A) WALL TAGS 5A COMMON TO RESTROOM 124 AND PRE-FUNCTION |
| | AREA ARE INDICATED NOT TO BE FIRE RATED WHERE AS A2.02 |
| | LIFE SAFETY SHEET INDICATES THEM TO BE A 1 HOUR FIRE |
| | RATING. 107.2.1.3 DISCREPANCY IN PLANS. ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | B) POOL STORAGE ROOM 126, MISSING WALL TAG FOR THE |
| | COMMON WALL WITH MENS RESTROOM 125, LIFE SAFETY SHOW |
| | THE BLOCKWALL A 2 HR FIRE RATED WALL. 107.2.1.3 |
| | DISCREPANCY IN PLANS. ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | C) ) POOL STORAGE ROOM 126, MISSING WALL TAG FOR THE |
| | COMMON WALL WITH MENS RESTROOM 125, LIFE SAFETY SHOW |
| | THE BLOCKWALL A 2 HR FIRE RATED WALL. 107.2.1.3 |
| | DISCREPANCY IN PLANS. ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 20) SHEET A5.15: |
| | A) ADMINISTRATIVE OFFICES WALL IDENTIFICATION TAGS LIFE |
| | SAFETY SHEET INDICATES THIS TO BE A 1 HOUR FIRE RATING |
| | WHERE AS THE WALL IDENTIFICATION TAGS INDICATE A 2 HR. |
| | 107.2.1.3.DISCREPANCY. ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | B) SHEET A5.15 COMMON WALL OF SERVICE CORRIDOR AND |
| | PAYMASTER AT WATER FOUNTAINS WALL IDENTIFICATION TAG |
| | 28C. THIS WALL TAG INDICATES THIS A NON-FIRE RATED WALL |
| | WHERE AS THE LIFE SAFETY PLAN SHOW THE ONE HOUR FIRE |
| | RATING GOING THROUGH BEHIND THE WATER FOUNTAINS. |
| | 107.2.1.3.DISCREPANCY. ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 21) SHEET A5.16 DOCK OFFICE WALL IDENTIFICATION TAGS 4A |
| | & 2A BOTH INDICATE A 1 HOUR FIRERATING WHERE AS THE |
| | LIFE SAFETY PLAN INDICATES THESE WALLS AS 2 HR FIRE |
| | RATING. WINDOW IN A 2 HR RATED WALL 1 1/2 HOUR |
| | PROTECTIVE. 107.2.1.3.DISCREPANCY. ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 22) SHEET A5.17: |
| | A) THE FPL VAULT SWITH ROOMS DO NOT HAVE WALL |
| | IDENTIFICATION TAGS, NOR DOES THE 2 SWITCH ROOMS HAVE |
| | ROOM IDENTIFICATION NUMBERS. |
| | 107.2.1.3.DISCREPANCY. ADDITIONAL INFORMATION IS |
| | REQUIRED. SEE LIFE SAFETY PLAN FOR WALL FIRE RATING. |
| | |
| | B) NEITHER THE LIFE SAFETY PLAN NOR A5.17 PROVIDE |
| | WHATTHE REQUIRED FIRE RATING OF THE FPL VAULT CEILING |
| | IS? SEE A2.00 FPL TRANSFORMER VAULT 2008 NEC 450.21. |
| | |
| | C) SHEET A5.17 FPL VAULT DOOR # 143 DOOR HARDWARE |
| | SCHEDULE UPDATE HARDWARE SEE SECTION FBC-B 1008.1.10 |
| | PANIC AND FIRE EXIT HARDWARE. ELECTRICAL ROOMS WITH |
| | EQUIPMENT RATED 1,200 AMPERES OR MORE AND OVER 6 FEET |
| | (1829 MM) WIDE THAT CONTAIN OVERCURRENT DEVICES, |
| | SWITCHING DEVICES OR CONTROL DEVICES WITH EXIT OR EXIT |
| | ACCESS DOORS SHALL BE EQUIPPED WITH PANIC HARDWARE OR |
| | FIRE EXIT HARDWARE. THE DOORS SHALL SWING IN THE |
| | DIRECTION OF EGRESS TRAVEL. |
| | |
| | 23) A5.18: |
| | WALL IDENTIFICATION TAGS ARE MISSING AND IDENTIFICATION |
| | OF FIRE RATED WALLS. ADDITIONAL INFORMATION IS |
| | REQUIRED. SEE LIFE SAFETY PLAN FOR WALL FIRE RATING |
| | DISCREPANCY IN PLANS. 107.2.1.3. |
| | |
| | 24) A7.03, A7.05 & A7.10 THE STAIR FLOOR PLANS DO NOT |
| | INDICATE THE REQUIRED STANDPIPES 2010 FBC-B 905.3. [F] |
| | 403.3.1.1 RISER LOCATION. |
| | SPRINKLER RISERS SHALL BE PLACED IN EXIT ENCLOSURES |
| | THAT ARE REMOTELY LOCATED IN ACCORDANCE WITH SECTION |
| | 1015.2. |
| | |
| | |
| | 25) SHEET A7.15 THE LINEN CHUTE DETAIL AT THE 12TH |
| | FLOOR THE 2 HOUR RATED SHAFT STOPS SHORT OF THE ROOF |
| | DECK, YET THE LAUNDRY CHUTE CONTINUES THROUGH THE ROOF. |
| | 708.12 ENCLOSURE AT THE TOP. A SHAFT ENCLOSURE THAT |
| | DOES NOT EXTEND TO THE UNDERSIDE OF THE ROOF SHEATHING, |
| | DECK OR SLAB OF THE BUILDING SHALL BE ENCLOSED AT THE |
| | TOP WITH CONSTRUCTION OF THE SAME FIRE-RESISTANCE |
| | RATING AS THE TOPMOST FLOOR PENETRATED BY THE SHAFT, |
| | BUT NOT LESS THAN THE FIRE-RESISTANCE RATING REQUIRED |
| | FOR THE SHAFT ENCLOSURE. |
| | |
| | 26) SHEET A2.10 SHOWS THE LAUNDRY CHUTE LOCATED ON THE |
| | GRID LINES X.1 JUST NORTH & Y.2 CENTERED ON THE GRID |
| | LINE WHICH IS LOCATED IN THE MAIDS ROOM. |
| | FLOORS 10-12 SEE SHEET A2.11 THE LAUBDRY CHUTE IS |
| | OFFSET TO THE NORTHEAST OR TO THE EAST OF GRID LINE Y.2 |
| | . THE PLANS SHOW THE ACCESS TO THE ACCESS CHUTE DOOR |
| | LOCATED WITH THE CORRADOR. PLEASE CONFORM WITH: |
| | |
| | 2010 FBC-B 708.13.3 REFUSE AND LAUNDRY CHUTE ACCESS |
| | ROOMS. |
| | ACCESS OPENINGS FOR REFUSE AND LAUNDRY CHUTES SHALL BE |
| | LOCATED IN ROOMS OR COMPARTMENTS ENCLOSED BY NOT LESS |
| | THAN 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE |
| | WITH SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED |
| | IN ACCORDANCE WITH SECTION 712, OR BOTH. OPENINGS INTO |
| | THE ACCESS ROOMS SHALL BE PROTECTED BY OPENING |
| | PROTECTIVES HAVING A FIRE PROTECTION RATING OF NOT LESS |
| | THAN 3/4 HOUR. DOORS SHALL BE SELF- OR |
| | AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE IN |
| | ACCORDANCE WITH SECTION 715.4.8.3. |
| | |
| | 27) SHEET A7.15 THE LINEN CHUTE DETAILS DO NOT MENTION |
| | THE REQUIREMENT OR ANY ALLOWANCES FOR FIRE SPRINKLERS |
| | IN THE LINEN CHUTE. THE FIRE SPRINKLER SHEETS ONLY |
| | PROVIDE A DEAIL ON FP0.01 INDICATING SERVICE CHUTE |
| | DETAIL. |
| | 708.13.6 AUTOMATIC SPRINKLER SYSTEM. |
| | AN APPROVED AUTOMATIC SPRINKLER SYSTEM SHALL BE |
| | INSTALLED IN ACCORDANCE WITH SECTION 903.2.11.2 F] |
| | 903.2.11.2 RUBBISH AND LINEN CHUTES. |
| | AN AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED AT THE |
| | TOP OF RUBBISH AND LINEN CHUTES AND IN THEIR TERMINAL |
| | ROOMS. CHUTES EXTENDING THROUGH THREE OR MORE FLOORS |
| | SHALL HAVE ADDITIONAL SPRINKLER HEADS INSTALLED WITHIN |
| | SUCH CHUTES AT ALTERNATE FLOORS. CHUTE SPRINKLERS SHALL |
| | BE ACCESSIBLE FOR SERVICING. |
| | |
| | THE LAUNDRY CHUTE DETAIL SHEET ALSO DOESN'T MAKE |
| | REFERANCE TO THE REQUIREMENT FOR CHUTE SPRINKLERS SHALL |
| | BE ACCESSIBLE FOR SERVICING. |
| | |
| | 28A) SHEET A7.03, A7.07 & A7.10 THE STAIR PLANS AND |
| | NOTES DO NOT INDICATE COMPLIANCE WITH 2010 FBC-B |
| | 403.5.5 AND SECION 1024 LUMINOUS EGRESS PATH MARKINGS. |
| | |
| | 28B) THESE SHEETS ALSO ARE MISSING COMPLIANCE WITH |
| | 403.5.3.1 STAIRWAY COMMUNICATION SYSTEMS. |
| | |
| | 29) SHEET A12.20 DETAILS 4A & 4B SHOW THE USE OF PIING |
| | PILE CAPS AND GRADE BEAMS, AREN'T THE PILES BEING |
| | ELIMINATED? 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 30) SHEET A12.22 DETAIL # 1 SPRAY APPLIED |
| | FIRE-RESISTANCE MATERIALS INDICATES SEE DETAIL ON |
| | A12.04 SPRAY APPLIED RESISTIVE MATERIAL. PLEASE PROVIDE |
| | COMPLIANCE WITH FBC-B 403.2.4 SPRAYED FIRE-RESISTANT |
| | MATERIALS (SFRM). |
| | THE BOND STRENGTH OF THE SFRM INSTALLED THROUGHOUT THE |
| | BUILDING SHALL BE IN ACCORDANCE WITH TABLE |
| | 403.2.4.HEIGHT OF BUILDING (A FOOTNOTE) |
| | SFRM MINIMUM BOND STRENGTH UP TO 420 FEET 430 PSF (A) |
| | ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE |
| | ACCESS. |
| | |
| | 31) SHEET A12.09.2 ALUMINUM FRAMED GLASS CANOPY DETAILS |
| | PLEASE PROVIDE COMPLIANCE WITH GLAZING REQUIREMENTS |
| | FOUND UNDER THE 2010 FBC-B |
| | 2405.2 ALLOWABLE GLAZING MATERIALS AND LIMITATIONS. |
| | SLOPED GLAZING SHALL BE ANY OF THE FOLLOWING MATERIALS, |
| | SUBJECT TO THE LISTED LIMITATIONS. |
| | 1. FOR MONOLITHIC GLAZING SYSTEMS, THE GLAZING MATERIAL |
| | OF THE SINGLE LIGHT OR LAYER SHALL BE LAMINATED GLASS |
| | WITH A MINIMUM 30-MIL (0.76 MM) POLYVINYL BUTYRAL (OR |
| | EQUIVALENT) INTERLAYER, WIRED GLASS, LIGHT-TRANSMITTING |
| | PLASTIC MATERIALS MEETING THE REQUIREMENTS OF SECTION |
| | 2607, HEAT-STRENGTHENED GLASS OR FULLY TEMPERED GLASS. |
| | 2. FOR MULTIPLE-LAYER GLAZING SYSTEMS, EACH LIGHT OR |
| | LAYER SHALL CONSIST OF ANY OF THE GLAZING MATERIALS |
| | SPECIFIED IN ITEM 1 ABOVE. |
| | ANNEALED GLASS IS PERMITTED TO BE USED AS SPECIFIED |
| | WITHIN EXCEPTIONS 2 AND 3 OF SECTION 2405.3. |
| | FOR ADDITIONAL REQUIREMENTS FOR PLASTIC SKYLIGHTS, SEE |
| | SECTION 2610. GLASS-BLOCK CONSTRUCTION SHALL CONFORM TO |
| | THE REQUIREMENTS OF SECTION 2101.2.5. |
| | |
| | 32)) SHEET A5.04 PLEASE REVIEW THE HOSPITALITY SUITES |
| | DETAIL 1 & 2 NEITHER OF THESE SUITES SHOW UP ON THE |
| | FLORIDA ACCESSIBLITY ROOM MATRIX. PLEASE REVIEW 2010 FL |
| | ACCESSIBILITY SECTION 224.5 THESE UNITS DO HAVE |
| | KITCHENS IN THEM WHERE AS NONE OF THE OTHER UNITS IN |
| | THE MATRIX INDICATE SUITES WITH KITCHENS NOR ARE THE |
| | BATHROOMS ACCESSIBLE. |
| | |
| | 33) SHEET S0.00 THE WIND DESIGN CRITERIA IS SHOWN IN |
| | VULT, PLEASE PROVIDE THE PRESSURES IN VASD SINCE ALL |
| | PRODUCT APPROVALS ARE PRINTED IN VASD. |
| | TABLE 1609.3. IS THIS PROJECT GOING TO DO WIND TUNNEL |
| | TESTING TO REDUCE PRESSURES? |
| | |
| | 34) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 35) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 36) SHEET M5.1 SMOKE CONTROL NOTES UNDER THE HEADING |
| | GENERAL , SMOKE CONTROL NOTES AND SMOKE CONTROL |
| | SEQUENCE THE NOTES DO NOT MAKE IT CLEAR HOW THE SMOKE |
| | CONTROL SYSTEM IS TO OPERATE. |
| | 2010 FBC-B 03.4.6 SMOKE REMOVAL.SMOKE CONTROL SHALL BE |
| | PROVIDED IN ACCORDANCE WITH SECTION 909. SECTION 909 |
| | PROVIDES VARIOUS METHODS OF COMPLYING WITH SMOKE |
| | CONTROL: |
| | 909.6 PRESSURIZATION METHOD. |
| | 909.7 AIRFLOW DESIGN METHOD. |
| | 909.8 EXHAUST METHOD. |
| | 909.9 DESIGN FIRE. |
| | |
| | [F] 909.2 GENERAL DESIGN REQUIREMENTS. |
| | BUILDINGS, STRUCTURES OR PARTS THEREOF REQUIRED BY THIS |
| | CODE TO HAVE A SMOKE CONTROL SYSTEM OR SYSTEMS SHALL |
| | HAVE SUCH SYSTEMS DESIGNED IN ACCORDANCE WITH THE |
| | APPLICABLE REQUIREMENTS OF SECTION 909 AND THE |
| | GENERALLY ACCEPTED AND WELL-ESTABLISHED PRINCIPLES OF |
| | ENGINEERING RELEVANT TO THE DESIGN. THE CONSTRUCTION |
| | DOCUMENTS SHALL INCLUDE SUFFICIENT INFORMATION AND |
| | DETAIL TO ADEQUATELY DESCRIBE THE ELEMENTS OF THE |
| | DESIGN NECESSARY FOR THE PROPER IMPLEMENTATION OF THE |
| | SMOKE CONTROL SYSTEMS. THESE DOCUMENTS SHALL BE |
| | ACCOMPANIED BY SUFFICIENT INFORMATION AND ANALYSIS TO |
| | DEMONSTRATE COMPLIANCE WITH THESE PROVISIONS. |
| | |
| | [F] 909.3 SPECIAL INSPECTION AND TEST REQUIREMENTS. |
| | IN ADDITION TO THE ORDINARY INSPECTION AND TEST |
| | REQUIREMENTS WHICH BUILDINGS, STRUCTURES AND PARTS |
| | THEREOF ARE REQUIRED TO UNDERGO, SMOKE CONTROL SYSTEMS |
| | SUBJECT TO THE PROVISIONS OF SECTION 909 SHALL UNDERGO |
| | SPECIAL INSPECTIONS AND TESTS SUFFICIENT TO VERIFY THE |
| | PROPER COMMISSIONING OF THE SMOKE CONTROL DESIGN IN ITS |
| | FINAL INSTALLED CONDITION. THE DESIGN SUBMISSION |
| | ACCOMPANYING THE CONSTRUCTION DOCUMENTS SHALL CLEARLY |
| | DETAIL PROCEDURES AND METHODS TO BE USED AND THE ITEMS |
| | SUBJECT TO SUCH INSPECTIONS AND TESTS. SUCH |
| | COMMISSIONING SHALL BE IN ACCORDANCE WITH GENERALLY |
| | ACCEPTED ENGINEERING PRACTICE AND, WHERE POSSIBLE, |
| | BASED ON PUBLISHED STANDARDS FOR THE PARTICULAR TESTING |
| | INVOLVED. |
| | |
| | [F] 909.4 ANALYSIS. |
| | A RATIONAL ANALYSIS SUPPORTING THE TYPES OF SMOKE |
| | CONTROL SYSTEMS TO BE EMPLOYED, THEIR METHODS OF |
| | OPERATION, THE SYSTEMS SUPPORTING THEM AND THE METHODS |
| | OF CONSTRUCTION TO BE UTILIZED SHALL ACCOMPANY THE |
| | SUBMITTED CONSTRUCTION DOCUMENTS AND SHALL INCLUDE, BUT |
| | NOT BE LIMITED TO, THE ITEMS INDICATED IN SECTIONS |
| | 909.4.1 THROUGH 909.4.6. |
| | |
| | 37) PLEASE PROVIDE CODE COMPLIANCE WITH: 2010 FBC-B [F] |
| | 914.2 EQUIPMENT ROOM IDENTIFICATION. |
| | FIRE PROTECTION EQUIPMENT SHALL BE IDENTIFIED IN AN |
| | APPROVED MANNER. ROOMS CONTAINING CONTROLS FOR |
| | AIR-CONDITIONING SYSTEMS, SPRINKLER RISERS AND VALVES |
| | OR OTHER FIRE DETECTION, SUPPRESSION OR CONTROL |
| | ELEMENTS SHALL BE IDENTIFIED FOR THE USE OF THE FIRE |
| | DEPARTMENT. APPROVED SIGNS REQUIRED TO IDENTIFY FIRE |
| | PROTECTION EQUIPMENT AND EQUIPMENT LOCATION SHALL BE |
| | CONSTRUCTED OF DURABLE MATERIALS, PERMANENTLY INSTALLED |
| | AND READILY VISIBLE. |
| | |
| | 38) EMERGENCY RESPONDER RADIO COVERAGE SHALL BE |
| | PROVIDED IN ALL NEW BUILDINGS IN ACCORDANCE THE FLORIDA |
| | FIRE PREVENTION CODE. |
| | |
| | 39) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B [F] |
| | 911.1.5 REQUIRED FEATURES. THE FIRE COMMAND CENTER |
| | SHALL COMPLY WITH NFPA 72 AND SHALL CONTAIN THE |
| | FOLLOWING FEATURES: 1-17. |
| | |
| | 40) THE SUBMITTED DOCUMENTS FOR 1ST REVIEW DID NOT |
| | PROVIDE DOCUMENTS FOR THE ENERGY CODE FOR COMPLIANCE. |
| | SEE 2010 FBC-ENERGY 103.2.1 & 103.2.3.1.2. |
| | |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |