| Plan Review Notes For Permit 14050102 |
| Permit Number |
14050102 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-07-14 10:58:17 | DATE: 7/14/2014 | | | PROJECT: SEABOARD TRAIN STATION IMPROVEMENTS. | | | PERMIT#: 14050102 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: PROVISO | | | | | | 1) THE "WP" RECEPTACLE ADJACENT TO THE FOUNTAIN SHALL | | | BE LISTED "WR" WEATHER-RESISTANT TYPE IN ADDITION TO | | | THE WEATHER-PROOF COVERS. NEC 406.8(B) | | | | | | 2) ALL 125-VOLT, SINGLEPHASE, 15- AND 20-AMPERE | | | RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1) | | | THROUGH (5) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER | | | PROTECTION FOR PERSONNEL: NEC 210.8(B)(4) OUTDOORS. | | | | | | 3) EACH MOTOR USED IN A CONTINUOUS DUTY APPLICATION AND | | | RATED MORE THAN 1 HP SHALL BE PROTECTED AGAINST | | | OVERLOAD BY ONE OF THE MEANS IN 430.32(A)(1) THROUGH | | | (A)(4). | | | | | | 4) THE PROVISIONS OF PART I AND PART V OF THE NEC | | | ARTICLE 680 SHALL APPLY TO ALL PERMANENTLY INSTALLED | | | FOUNTAINS AS DEFINED IN THE NEC 680.2 AND 680.50 | | | | | | 5) WIND LOADS SHALL BE DETERMINED IN ACCORDANCE WITH | | | CHAPTERS 26 THROUGH 30 OF ASCE 7 OR THE PROVISIONS OF | | | THE ALTERNATE ALL HEIGHTS METHOD IN SECTION 1609.6. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|