Plan Review Notes
Plan Review Notes For Permit 14050102
Permit Number 14050102
Review Stop E
Sequence Number 1
Notes
Date Text
2014-07-14 10:58:17DATE: 7/14/2014
 PROJECT: SEABOARD TRAIN STATION IMPROVEMENTS.
 PERMIT#: 14050102
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) THE "WP" RECEPTACLE ADJACENT TO THE FOUNTAIN SHALL
 BE LISTED "WR" WEATHER-RESISTANT TYPE IN ADDITION TO
 THE WEATHER-PROOF COVERS. NEC 406.8(B)
  
 2) ALL 125-VOLT, SINGLEPHASE, 15- AND 20-AMPERE
 RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1)
 THROUGH (5) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL: NEC 210.8(B)(4) OUTDOORS.
  
 3) EACH MOTOR USED IN A CONTINUOUS DUTY APPLICATION AND
 RATED MORE THAN 1 HP SHALL BE PROTECTED AGAINST
 OVERLOAD BY ONE OF THE MEANS IN 430.32(A)(1) THROUGH
 (A)(4).
  
 4) THE PROVISIONS OF PART I AND PART V OF THE NEC
 ARTICLE 680 SHALL APPLY TO ALL PERMANENTLY INSTALLED
 FOUNTAINS AS DEFINED IN THE NEC 680.2 AND 680.50
  
 5) WIND LOADS SHALL BE DETERMINED IN ACCORDANCE WITH
 CHAPTERS 26 THROUGH 30 OF ASCE 7 OR THE PROVISIONS OF
 THE ALTERNATE ALL HEIGHTS METHOD IN SECTION 1609.6.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]