| 2014-07-11 12:15:06 | BUILDING PLAN REVIEW |
| | PERMIT: 14050102 |
| | ADD: 205 TAMARIND AVE |
| | CONT: TBD |
| | TEL: (561)494-1061 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JULY 11/2014 |
| | FOUNTAIN & CLOCK TOWER REVIEW |
| | |
| | ACTION: BUILDING PROVISO |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) SHEET A-3.01: |
| | 1A) THE PLANS INDICATE A PREMANUFACTURED VERTICAL WATER |
| | FOUNTAIN FEATURE & TROUGH. THERE IS NO DETAIL |
| | INFORMATION AT THIS TIME. NOTED THAT SHOP DRAWINGS ARE |
| | TO BE SUBMITTED AND REVIEWED BY THE DESIGNER OF RECORD |
| | BEFORE SUBMITTAL TO THE BUILDING DEPARTMENT. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 1B) THE PLANS INDICATE THE VERTICAL FOUNTAIN FEATURE |
| | WALL TO HAVE STAINLESS STEEL CABLES IN A DIAMOND SHAPE |
| | PATTERN, THERE IS NO DETAIL INFORMATION AT THIS TIME. |
| | NOTED THAT SHOP DRAWINGS ARE TO BE SUBMITTED AND |
| | REVIEWED BY THE DESIGNER OF RECORD BEFORE SUBMITTAL TO |
| | THE BUILDING DEPARTMENT. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 1C) THE PLANS INDICATE THE EXISTING FOUNTAIN EQUIPMENT |
| | IS TO BE REUSED/ REPAIRED AND COORDINATION WITH THE |
| | FOUNTAIN MANUFACTURER. |
| | THERE IS NO DETAIL INFORMATION AT THIS TIME. NOTED THAT |
| | SHOP DRAWINGS ARE TO BE SUBMITTED AND REVIEWED BY THE |
| | DESIGNER OF RECORD BEFORE SUBMITTAL TO THE BUILDING |
| | DEPARTMENT. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 1D) PLEASE PROVIDE DIMENSIONS TO THE ACCESS PANEL THAT |
| | IS PART OF THE CLOCK TOWER, AND PROVIDES ACCESS TO THE |
| | FOUNTAIN PUMPS. PLEASE PROVIDE ADDITIONAL INFORMATION |
| | HOW COMPLIANCE WITH 2010 FBC-PUMBING 202- READY ACCESS. |
| | THAT WHICH ENABLES A FIXTURE, APPLIANCE OR EQUIPMENT TO |
| | BE DIRECTLY REACHED WITHOUT REQUIRING THE REMOVAL OR |
| | MOVEMENT OF ANY PANEL, DOOR OR SIMILAR OBSTRUCTION AND |
| | WITHOUT THE USE OF A PORTABLE LADDER, STEP STOOL OR |
| | SIMILAR DEVICE. |
| | |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |