2014-08-13 10:47:47DATE: 7/14/2014
 PROJECT: SEABOARD TRAIN STATION IMPROVEMENTS.
 PERMIT#: 14050101 SEE ALSO PERMIT 14050102, 14040876
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1
 SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT
 OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR &
 TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING
 DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E
 505.2.4
  
 2) THE "WP" RECEPTACLE ADJACENT TO THE FOUNTAIN SHALL
 BE LISTED "WR" WEATHER-RESISTANT TYPE IN ADDITION TO
 THE WEATHER-PROOF COVERS. NEC 406.8(B)
 ALL 125-VOLT, SINGLEPHASE, 15- AND 20-AMPERE
 RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1)
 THROUGH (5) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL: NEC 210.8(B)(4) OUTDOORS.
  
 3) THE INTERIOR OF AN UNDERGROUND RACEWAY SHALL BE
 CONSIDERED A WET LOCATION. ALL CONDUCTORS WITHIN THE
 RACEWAY SHALL BE LISTED ACCORDINGLY.
 SUITABILITY FOR INSTALLATION AND USE SHALL BE IN
 CONFORMITY WITH THE PROVISIONS OF
 THIS CODE. NEC 110.3(A)(1 THRU 8)
  
 4)THE PROVISIONS OF PART I AND PART V OF THE NEC
 ARTICLE 680 SHALL APPLY TO ALL PERMANENTLY INSTALLED
 FOUNTAINS AS DEFINED IN 680.2. NEC 680.50
 THE LIGHTING AND SUBMERSIBLE PUMP CIRCUITS SHALL BE
 GFCI PROTECTED UNLESS THEY OPERATE AT UNDER 15 VAC. NEC
 680.51
  
 5) THE "WP" RECEPTACLE ADJACENT TO THE FOUNTAIN SHALL
 BE LISTED "WR" WEATHER-RESISTANT TYPE IN ADDITION TO
 THE WEATHER-PROOF COVERS. NEC 406.8(B)
  
 6) ALL 125-VOLT, SINGLEPHASE, 15- AND 20-AMPERE
 RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1)
 THROUGH (5) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL: NEC 210.8(B)(4) OUTDOORS.
  
 7) EACH MOTOR USED IN A CONTINUOUS DUTY APPLICATION AND
 RATED MORE THAN 1 HP SHALL BE PROTECTED AGAINST
 OVERLOAD BY ONE OF THE MEANS IN 430.32(A)(1) THROUGH
 (A)(4).
  
 8) THE PROVISIONS OF PART I AND PART V OF THE NEC
 ARTICLE 680 SHALL APPLY TO ALL PERMANENTLY INSTALLED
 FOUNTAINS AS DEFINED IN THE NEC 680.2 AND 680.50
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,