| Date |
Text |
| 2014-08-25 15:11:21 | FUEL GAS PLAN REVIEW |
| | PERMIT: 14050097 |
| | ADD: 8100 IBIS BLVD |
| | CONT:THE WEITZ CO. |
| | TEL: (561)686-5511 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | |
| | 3D REVIEW |
| | DATE: MON. AUG. 25/ 2014 |
| | ACTION: DENIED |
| | |
| | SHEET P306 GAS PIPING ISOMETRIC. |
| | |
| | GAS PERMIT APPLICATION REQUIREMENTS, MISSING |
| | INFORMATION: |
| | |
| | |
| | 1. COMPLIED. |
| | |
| | 2. COMPLIED. |
| | |
| | 3.. COMPLIED. |
| | |
| | 4. 3RD REQUEST. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE OUTLET IN THE |
| | BUILDING AND/OR SYSTEM PER THE FBC-2010 FUEL GAS |
| | APPENDIX A ? USE OF CAPACITY SECTION A.3.1(4) |
| | |
| | 2010 FBC- FUEL GAS |
| | A.3.1 LONGEST LENGTH METHOD. |
| | THIS SIZING METHOD IS CONSERVATIVE IN ITS APPROACH BY |
| | APPLYING THE MAXIMUM OPERATING CONDITIONS IN THE SYSTEM |
| | AS THE NORM FOR THE SYSTEM AND BY SETTING THE LENGTH OF |
| | PIPE USED TO SIZE ANY GIVEN PART OF THE PIPING SYSTEM |
| | TO THE MAXIMUM VALUE. |
| | |
| | TO DETERMINE THE SIZE OF EACH SECTION OF GAS PIPING IN |
| | A SYSTEM WITHIN THE RANGE OF THE CAPACITY TABLES, |
| | PROCEED AS FOLLOWS (ALSO SEE SAMPLE CALCULATIONS |
| | INCLUDED IN THIS APPENDIX): |
| | |
| | (1) DIVIDE THE PIPING SYSTEM INTO APPROPRIATE SEGMENTS |
| | CONSISTENT WITH THE PRESENCE OF TEES, BRANCH LINES AND |
| | MAIN RUNS. FOR EACH SEGMENT, DETERMINE THE GAS LOAD |
| | (ASSUMING ALL APPLIANCES OPERATE SIMULTANEOUSLY) AND |
| | ITS OVERALL LENGTH. AN ALLOWANCE (IN EQUIVALENT LENGTH |
| | OF PIPE) AS DETERMINED FROM TABLE A.2.2 SHALL BE |
| | CONSIDERED FOR PIPING SEGMENTS THAT INCLUDE FOUR OR |
| | MORE FITTINGS. |
| | |
| | (2) DETERMINE THE GAS DEMAND OF EACH APPLIANCE TO BE |
| | ATTACHED TO THE PIPING SYSTEM. WHERE TABLES 402.4(1) |
| | THROUGH 402.4(22) ARE TO BE USED TO SELECT THE PIPING |
| | SIZE, CALCULATE THE GAS DEMAND IN TERMS OF CUBIC FEET |
| | PER HOUR FOR EACH PIPING SYSTEM OUTLET . WHERE TABLES |
| | 402.4(23) THROUGH 402.4(35) ARE TO BE USED TO SELECT |
| | THE PIPING SIZE, CALCULATE THE GAS DEMAND IN TERMS OF |
| | THOUSANDS OF BTU PER HOUR FOR EACH PIPING SYSTEM OUTLET |
| | . |
| | |
| | (3) WHERE THE PIPING SYSTEM IS FOR USE WITH OTHER THAN |
| | UNDILUTED LIQUEFIED PETROLEUM GASES, DETERMINE THE |
| | DESIGN SYSTEM PRESSURE, THE ALLOWABLE LOSS IN PRESSURE |
| | (PRESSURE DROP), AND SPECIFIC GRAVITY OF THE GAS TO BE |
| | USED IN THE PIPING SYSTEM. |
| | |
| | (4) DETERMINE THE LENGTH OF PIPING FROM THE POINT OF |
| | DELIVERY TO THE MOST REMOTE OUTLET IN THE |
| | BUILDING/PIPING SYSTEM. |
| | |
| | |
| | |
| | 5. COMPLIED. |
| | 6. COMPLIED. |
| | |
| | 7. COMPLIED. |
| | |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |