| 2014-08-01 06:49:02 | BUILDING PLAN REVIEW |
| | PERMIT: 14050097 |
| | ADD: 8100 IBIS BLVD |
| | CONT:THE WEITZ CO. |
| | TEL: (561)686-5511 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | NOTICE TO DESIGNER OF RECORD. THERE WERE NO CHANGES |
| | MADE TO THE PLANS. THERE ARE NO REVISION NUMBERS ON ANY |
| | OF THE SHEETS INDICATING WHERE CORRCTIONS WERE MADE TO |
| | THE PLANS NOR THROUGH PROJECT DOX DOES VERSION 2 EXIT |
| | SHOWING CORRECTIONS WERE MADE. |
| | |
| | IGNORED!!! . A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | NOTICE TO THE DESIGNER OF RECORD!!!! CHAPTER |
| | 553.80(2)(B) FLORIDA STATUTES STATES THAT A LOCAL |
| | GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE FEE FOR |
| | PLAN REVIEW, IF PLANS ARE REJECTED THREE OR MORE TIMES |
| | FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION. |
| | |
| | |
| | 2ND REVIEW |
| | DATE:FRI. AUG. 01/ 2014 |
| | ACTION: DENIED |
| | |
| | NOTICE TO DESIGNER OF RECORD. THERE WERE NO CHANGES |
| | MADE TO THE PLANS. THERE ARE NO REVISION NUMBERS ON ANY |
| | OF THE SHEETS INDICATING WHERE CORRCTIONS WERE MADE TO |
| | THE PLANS NOR THROUGH PROJECT DOX DOES VERSION 2 EXIT |
| | SHOWING CORRECTIONS WERE MADE. |
| | |
| | IGNORED!!! WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | NOTICE TO THE DESIGNER OF RECORD!!!! CHAPTER |
| | 553.80(2)(B) FLORIDA STATUTES STATES THAT A LOCAL |
| | GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE FEE FOR |
| | PLAN REVIEW, IF PLANS ARE REJECTED THREE OR MORE TIMES |
| | FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION. |
| | |
| | 1) 2ND REQUEST. SHEET P105 NOR 305 DOES NOT INDICATE |
| | THE SIZE OF THE VERTICAL CONDUCTORS AND LEADERS, |
| | BUILDING STORM DRAINS, BUILDING STORM SEWERS, AND ANY |
| | HORIZONTAL BRANCHES OF SUCH DRAINS OR SEWERS SHALL BE |
| | BASED ON THE 100-YEAR HOURLY RAINFALL RATE INDICATED IN |
| | FIGURE 1106.1 OR ON OTHER RAINFALL RATES DETERMINED |
| | FROM APPROVED LOCAL WEATHER DATA. 2010 FBC-P 1106.1. |
| | |
| | 2) 2ND REQUEST. P105 DOES NOT PROVIDE WHAT AREA THE |
| | ROOF DRAINS ARE RECEIVING, IF THIS IS JUST THE FLAT |
| | AREA OR IF THIS AREA IS ALSO THE CONTRIBUTING SLOPED |
| | ARAES, PLEASE PROVIDE A BREAK OUT FOR EACH ROOF DRAIN |
| | SERVED OF FLAT AND ADJOINING SLOPED ROOFS THAT |
| | CONTRIBUTE TO THE ROOF DRAIN LOAD. |
| | 2010 1106.4. |
| | |
| | 3) 2ND REQUEST. SHEET P201 VERSES P301 |
| | 3A) THE LADIES RESTROOM 222 THE 4 WATER CLOSETS IN A |
| | ROW IS MISSING THE VENT CONNECTION FOR A CIRCUIT VENT |
| | SEE SECTION 2010 FBC-P 911.2. |
| | |
| | 3B) 2ND REQUEST. IT APPEARS ONE OF THE WATER CLOSETS IN |
| | THE MENS RESTROOM IS NOT VENTEDAS A INDIVDUAL VENT OF |
| | THE BEGINNING OF A CIRCUIT VENT SEE 2010 FBC-P 907.1 & |
| | 911.2. T |
| | |
| | 3C) 2ND REQUEST. IT APPEARS ONE OF THE WATER CLOSETS IN |
| | THE MENS RESTROOM IS NOT VENTED AS A INDIVDUAL VENT OF |
| | THE BEGINNING OF A CIRCUIT VENT SEE 2010 FBC-P 907.1 & |
| | 911.2. T |
| | |
| | 4A) 2ND REQUEST. 0173-P304 RISER E GREASE WASTE, THE |
| | PLANS INDICATE THE GREASE WASTE FROM KITCHENS # 135 & |
| | #245, THE PLANS DO NOT COMMENT ON THE DRAINAGE FIXTURE |
| | UNITS FOR THE GREASE WASTE NOR MENTION SIZING NOR THE |
| | LOCATION OF THE GREASE INTERCEPTOR. 2010 FBC-PLUMBING |
| | 1003.2. APPROVAL. 1003.3.3 SIZED. NOTE IF A CONCRETE |
| | VAULT TYPE OF INTERCEPTOR IS TO BE INSTALLED PLEASE |
| | NOTE THAT FBC-P TABLE 1003.5.1 IS THE SIZING TABLE TO |
| | BE USED FOR THIS TYPE OF APPLICATION. |
| | |
| | 4B) 2ND REQUEST. THE PLANS DO NOT INDICATE IF ANY FOOD |
| | WASTE GRINDERS ARE GOING TO BE INSTALLED. 2010 |
| | FBC-PLUMBING 1003.3.2. |
| | |
| | 4C) 2ND REQUEST. THE ARCHITECTURAL SHEETS & STRURTURAL |
| | SHEETS BOTH INDICATE THE ELEVATOR PIT TO HAVE A SUMP |
| | PIT. PLANS ARE NOT CLEAR IF THIS IS TO BE A HYDROLIC |
| | ELEVATOR, IF SO PLEASE INDICATE HOW COMPLIANCE WITH |
| | 2010 FBC-PLUMBING 1003.4 OIL SPEARATOR REQUIRED WILL BE |
| | ACHIEVED. I DID NOT SEE A DETAIL FOR A SUMP IN THE |
| | ELEVATOR PIT AND WASTE CONNECTIONS.SHEET P401 DOES |
| | INDICATE THE USE OF ZOELLER SUBMERSIBLE SUMP PUMP |
| | EXCEPTION: AN OIL SEPARATOR IS NOT REQUIRED IN |
| | HYDRAULIC ELEVATOR PITS WHERE AN APPROVED ALARM SYSTEM |
| | IS INSTALLED. |
| | |
| | 1003.4.2 OIL SEPARATOR DESIGN. |
| | OIL SEPARATORS SHALL BE DESIGNED IN ACCORDANCE WITH |
| | SECTIONS 1003.4.2.1 AND 1003.4.2.2. |
| | |
| | 1003.4.2.1 GENERAL DESIGN REQUIREMENTS. |
| | OIL SEPARATORS SHALL HAVE A DEPTH OF NOT LESS THAN 2 |
| | FEET (610 MM) BELOW THE INVERT OF THE DISCHARGE DRAIN. |
| | THE OUTLET OPENING OF THE SEPARATOR SHALL HAVE NOT LESS |
| | THAN AN 18-INCH (457 MM) WATER SEAL. |
| | |
| | 5) 2ND REQUEST. SHEET 0176- P401 PLUMBING SCHEDULE. |
| | TTRAP PRIMERS INDICATE PRECISION PLUMBING PRODUCTS BUT |
| | THE ACTUAL TYPE OR MODEL NUMBER IS NOT INDICATED NOR IS |
| | THE CONFORMANCE FOR TRAP SEAL PRIMER VALVES TO COMPLY |
| | WITH ASSE 1018 OR ASSE 1044. 2010 FBC-P 1002.4. |
| | |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |