| 2014-09-05 16:57:48 | DATE: 9/12/2014 |
| | PROJECT: IBIS |
| | PERMIT#: 14050097 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: PROVISO |
| | |
| | 1) SHEET EL103 |
| | TERRACE AND STAIRS. LIGHTING CONTROL REQUIRED FOR |
| | EXTERIOR LIGHTING. FBC 505.2.4 |
| | |
| | 2) SHEET EP104 |
| | 214-BAR TERRACE. FLUSH CEILING OUTLETS TO HAVE GFCI |
| | PROTECTION. |
| | 212-BAR LOUNGE. PROVIDE MANUFACTURER?S PRODUCT |
| | SPECIFICATIONS ON FLOOR BOXES. FLOOR BOXES SHALL BE |
| | APPROVED TO MAINTAIN THE FIRE RATED INTEGRITY OF THE |
| | FLOOR. |
| | |
| | 3) SHEET EP401 |
| | 207- STORAGE RM. THIS IS ELECTRICAL EQUIPMENT ROOM. |
| | THERE SHALL BE NO STORAGE ALLOWED AND SHALL BE |
| | IDENTIFIED WITH A SIGN STATING ?ELECTRIC ROOM. NO |
| | STORAGE ALLOWED? MAINTAIN WORKING CLEARANCE AND |
| | DEDICATED WORKING SPACE. NEC 110.26 |
| | |
| | 4) SHEET EP501 |
| | A) INDICATE HOW THE CLUBHOUSE GROUNDING ELECTRODE |
| | SYSTEM TIES TO MDP BARN GROUNDING ELECTRODE SYSTEM. |
| | NOTE 3 THIS SHEET STATES TO BOND PANEL IT1 GROUND TO |
| | CLUBHOUSE GROUNDING ELECTRODE SYSTEM. THIS WOULD CREATE |
| | A DIFFERENCE OF POTENTIAL BETWEEN THE BARN AND |
| | CLUBHOUSE SYSTEMS. |
| | B) PROVIDE A NOTE AND ADD A SYMBOL TO THE SYMBOLS |
| | LEGEND FOR THE REMOTE SHUNT TRIP STATIONS TO ACTIVATE |
| | SHUNT TRIP MAIN BREAKERS SD 1 OF 4 AND SD 2 OF 4. |
| | C) INDICATE THE TYPE AND LOCATIONS FOR THE REMOTE SHUNT |
| | TRIP STATIONS NEXT TO THE EXISTING CHILLER PANEL SD 3 |
| | OF 4 AND SD 4 OF 4. |
| | D) PROVIDE A NOTE ADDING A SIGN AT THE EXISTING CHILLER |
| | PANEL IDENTIFYING THE REMOTE SHUNT TRIP STATIONS AS |
| | TRIP UNITS FOR ADDITIONAL SERVICE ENTRANCE MAIN |
| | DISCONNECTS LOCATED IN ELECTRICAL ROOM 150 IN MDPA AND |
| | MDPB |
| | E) THE ATS AT THE NEW GENERATOR IS IDENTIFIED AS A |
| | 4POLE ATS. I BELIEVE THIS IS MIS-LABELED AND THE INTENT |
| | IS FOR A STANDARD 3 POSITION ATS WITH A SOLID NEUTRAL |
| | FOR STANDARD OPTIONAL STANDBY SYSTEM AS ALSO NOTED THIS |
| | SHEET. |
| | |
| | 5) SHEET ES101 |
| | SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR SITE LIGHTING, GENERATOR, FIRE ALARM, |
| | SECURITY, CCTV, NETWORK, DATA/COM, AUDIO, VIDEO, AND |
| | SIGNAGE. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |