| 2014-07-05 12:43:58 | BUILDING PLAN REVIEW |
| | PERMIT: 14050097 |
| | ADD: 8100 IBIS BLVD |
| | CONT:THE WEITZ CO. |
| | TEL: (561)686-5511 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. JULY 12/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET P105 NOR 305 DOES NOT INDICATE THE SIZE OF THE |
| | VERTICAL CONDUCTORS AND LEADERS, BUILDING STORM DRAINS, |
| | BUILDING STORM SEWERS, AND ANY HORIZONTAL BRANCHES OF |
| | SUCH DRAINS OR SEWERS SHALL BE BASED ON THE 100-YEAR |
| | HOURLY RAINFALL RATE INDICATED IN FIGURE 1106.1 OR ON |
| | OTHER RAINFALL RATES DETERMINED FROM APPROVED LOCAL |
| | WEATHER DATA. 2010 FBC-P 1106.1. |
| | |
| | 2) P105 DOES NOT PROVIDE WHAT AREA THE ROOF DRAINS ARE |
| | RECEIVING, IF THIS IS JUST THE FLAT AREA OR IF THIS |
| | AREA IS ALSO THE CONTRIBUTING SLOPED ARAES, PLEASE |
| | PROVIDE A BREAK OUT FOR EACH ROOF DRAIN SERVED OF FLAT |
| | AND ADJOINING SLOPED ROOFS THAT CONTRIBUTE TO THE ROOF |
| | DRAIN LOAD. |
| | 2010 1106.4. |
| | |
| | 3) SHEET P201 VERSES P301 |
| | 3A) THE LADIES RESTROOM 222 THE 4 WATER CLOSETS IN A |
| | ROW IS MISSING THE VENT CONNECTION FOR A CIRCUIT VENT |
| | SEE SECTION 2010 FBC-P 911.2. |
| | |
| | 3B) IT APPEARS ONE OF THE WATER CLOSETS IN THE MENS |
| | RESTROOM IS NOT VENTEDAS A INDIVDUAL VENT OF THE |
| | BEGINNING OF A CIRCUIT VENT SEE 2010 FBC-P 907.1 & |
| | 911.2. T |
| | |
| | 3C) IT APPEARS ONE OF THE WATER CLOSETS IN THE MENS |
| | RESTROOM IS NOT VENTEDAS A INDIVDUAL VENT OF THE |
| | BEGINNING OF A CIRCUIT VENT SEE 2010 FBC-P 907.1 & |
| | 911.2. T |
| | |
| | 4A) 0173-P304 RISER E GREASE WASTE, THE PLANS INDICATE |
| | THE GREASE WASTE FROM KITCHENS # 135 & #245, THE PLANS |
| | DO NOT COMMENT ON THE DRAINAGE FIXTURE UNITS FOR THE |
| | GREASE WASTE NOR MENTION SIZING NOR THE LOCATION OF THE |
| | GREASE INTERCEPTOR. 2010 FBC-PLUMBING 1003.2. APPROVAL. |
| | 1003.3.3 SIZED. NOTE IF A CONCRETE VAULT TYPE OF |
| | INTERCEPTOR IS TO BE INSTALLED PLEASE NOTE THAT FBC-P |
| | TABLE 1003.5.1 IS THE SIZING TABLE TO BE USED FOR THIS |
| | TYPE OF APPLICATION. |
| | |
| | 4B) THE PLANS DO NOT INDICATE IF ANY FOOD WASSTE |
| | GRINDERS ARE GOING TO BE INSTALLED. 2010 FBC-PLUMBING |
| | 1003.3.2. |
| | |
| | 4C) THE ARCHITECTURAL SHEETS & STRURTURAL SHEETS BOTH |
| | INDICATE THE ELEVATOR PIT TO HAVE A SUMP PIT. PLANS ARE |
| | NOT CLEAR IF THIS IS TO BE A HYDROLIC ELEVATOR, IF SO |
| | PLEASE INDICATE HOW COMPLIANCE WITH 2010 FBC-PLUMBING |
| | 1003.4 OIL SPEARATOR REQUIRED WILL BE ACHIEVED. I DID |
| | NOT SEE A DETAIL FOR A SUMP IN THE ELEVATOR PIT AND |
| | WASTE CONNECTIONS.SHEET P401 DOES INDICATE THE USE OF |
| | ZOELLER SUBMERSIBLE SUMP PUMP EXCEPTION: AN OIL |
| | SEPARATOR IS NOT REQUIRED IN HYDRAULIC ELEVATOR PITS |
| | WHERE AN APPROVED ALARM SYSTEM IS INSTALLED. |
| | |
| | 1003.4.2 OIL SEPARATOR DESIGN. |
| | OIL SEPARATORS SHALL BE DESIGNED IN ACCORDANCE WITH |
| | SECTIONS 1003.4.2.1 AND 1003.4.2.2. |
| | |
| | 1003.4.2.1 GENERAL DESIGN REQUIREMENTS. |
| | OIL SEPARATORS SHALL HAVE A DEPTH OF NOT LESS THAN 2 |
| | FEET (610 MM) BELOW THE INVERT OF THE DISCHARGE DRAIN. |
| | THE OUTLET OPENING OF THE SEPARATOR SHALL HAVE NOT LESS |
| | THAN AN 18-INCH (457 MM) WATER SEAL. |
| | |
| | 5) SHEET 0176- P401 PLUMBING SCHEDULE. TTRAP PRIMERS |
| | INDICATE PRECISION PLUMBING PRODUCTS BUT THE ACTUAL |
| | TYPE OR MODEL NUMBER IS NOT INDICATED NOR IS THE |
| | CONFORMANCE FOR TRAP SEAL PRIMER VALVES TO COMPLY WITH |
| | ASSE 1018 OR ASSE 1044. 2010 FBC-P 1002.4. |
| | |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |