| 2014-06-12 16:23:14 | 8100 (8225) IBIS BOULEVARD |
| | PERMIT #14050097 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | NOTE: SEVERAL SHEETS COULD NOT BE OPENED/REVIEWED AS |
| | THEY RESULTED IN A COMPUTER CRASH. |
| | |
| | SHEET GI101 & GI102 - LIFE SAFETY PLANS: INDICATE WHAT |
| | MEASURES WILL BE IN PLACE TO ENSURE THE ASSEMBLY AREAS |
| | WITHOUT SEATING (SUCH AS BAR TERRACE #214) ARE NOT |
| | OVERCROWDED (EXCEED 15 SQ.FT. OCCUPANT LOAD FACTOR). |
| | |
| | SHEET GI101: THE OCCUPANT LOAD FACTOR FOR KITCHEN |
| | SPACES SHALL BE 100 SQ.FT. PER PERSON PER TABLE |
| | 7.3.1.2. ALSO KITCHEN #135 ONLY HAS EXIT SIGNAGE |
| | LEADING TO ONE EXIT. PROVIDE SIGNAGE FOR SECONDARY |
| | MEANS OF EGRESS. |
| | |
| | SHEET GI101: FORMAL DINING #131 IS APPROXIMATELY 800 |
| | SQ.FT. USING AN OCCUPANT LOAD FACTOR OF 15 SQ.FT. PER |
| | PERSON, THE OCCUPANT LOAD FOR THIS ROOM WOULD BE CLOSER |
| | TO 54 PERSONS. ONLY 1 MEANS OF EGRESS IS PROVIDED FOR |
| | THIS ROOM. |
| | |
| | SHEET GI101: FORMAL DINING #130 IS APPROXIMATELY 1600 |
| | SQ.FT. USING AN OCCUPANT LOAD FACTOR OF 15 SQ.FT. PER |
| | PERSON, THE OCCUPANT LOAD FOR THIS ROOM WOULD BE CLOSER |
| | TO 107 PERSONS. |
| | |
| | SHEET GI101: CULTURAL CLASS #125 AND TRAINING #169 |
| | APPEAR TO ACTUALLY BE ASSEMBLY USE (15 SQ.FT. OCCUPANT |
| | LOAD FACTOR) SPACES AND NOT EDUCATIONAL (20 SQ.FT. |
| | OCCUPANT LOAD FACTOR) USE. EDUCATIONAL USE IS DEFINED |
| | AS AN OCCUPANCY USED FOR EDUCATIONAL PURPOSES THROUGH |
| | THE 12TH GRADE BY SIX OR MORE PERSONS FOR 4 OR MORE |
| | HOURS PER DAY OR MORE THAN 12 HOURS PER WEEK. |
| | |
| | SHEET GI102: THE OCCUPANT LOAD FACTOR FOR KITCHEN |
| | SPACES SHALL BE 100 SQ.FT. PER PERSON PER TABLE |
| | 7.3.1.2. |
| | |
| | SHEET GI102: KITCHEN #245 ONLY HAS EXIT SIGNAGE LEADING |
| | TO ONE EXIT. PROVIDE SIGNAGE FOR SECONDARY MEANS OF |
| | EGRESS. |
| | |
| | SHEET GI102: GRILL DINING AREA 264A/B IS APPROXIMATELY |
| | 3,000 SQ.FT. USING AN OCCUPANT LOAD FACTOR OF 15 SQ.FT. |
| | PER PERSON, THE OCCUPANT LOAD FOR THIS ROOM WOULD BE |
| | CLOSER TO 200 PERSONS. |
| | |
| | SHEET GI102: PROVIDE EXIT SIGNAGE LEADING TO SECONDARY |
| | MEANS OF EGRESS FROM LOUNGE #258 AREA. |
| | |
| | SHEET GI102: PROVIDE A SECONDARY MEANS OF EGRESS AND |
| | SIGNAGE FOR BAR TERRACE #214. |
| | |
| | SHEET AE101: CARD ROOM #185 (71 PERSONS) HAS TWO EXIT |
| | ACCESS DOORS THAT HAVE APPROPRIATE SEPARATION; HOWEVER, |
| | BOTH DOORS LEAD TO THE SAME CORRIDOR #186 WHEREBY ONE |
| | FIRE EVENT COULD COMPROMISE BOTH DOORS. PER SECTION |
| | 12.2.5.1.2 THE COMMON PATH OF TRAVEL IS LIMITED TO 75 |
| | FEET FOR 50 OR LESS OCCUPANTS AND 20 FEET FOR 51 OR |
| | MORE OCCUPANTS. THE EXIT ACCESS DOORS SHALL BE ARRANGED |
| | FOR OCCUPANTS TO HAVE ACCESS TO AT LEAST TWO EXITS BY |
| | SEPARATE WAYS OF TRAVEL PER SECTION 7.5.1.1.1. |
| | |
| | SHEET AE101: CULTURAL CLASS #125 (71 PERSONS) HAS TWO |
| | EXIT ACCESS DOORS THAT HAVE APPROPRIATE SEPARATION; |
| | HOWEVER, BOTH DOORS LEAD TO THE SAME CORRIDOR GALLERY |
| | #102 WHEREBY ONE FIRE EVENT COULD COMPROMISE BOTH |
| | DOORS. PER SECTION 12.2.5.1.2 THE COMMON PATH OF TRAVEL |
| | IS LIMITED TO 75 FEET FOR 50 OR LESS OCCUPANTS AND 20 |
| | FEET FOR 51 OR MORE OCCUPANTS. THE EXIT ACCESS DOORS |
| | SHALL BE ARRANGED FOR OCCUPANTS TO HAVE ACCESS TO AT |
| | LEAST TWO EXITS BY SEPARATE WAYS OF TRAVEL PER SECTION |
| | 7.5.1.1.1. |
| | |
| | SHEET AE101: LOUNGE #110 THE COMMON PATH OF TRAVEL IS |
| | 135 FEET. PER SECTION 12.2.5.1.2 THE COMMON PATH OF |
| | TRAVEL IS LIMITED TO 75 FEET FOR 50 OR LESS OCCUPANTS |
| | AND 20 FEET FOR 51 OR MORE OCCUPANTS. |
| | |
| | SHEET AE104: MONUMENTAL STAIR #209 APPEARS TO BE |
| | FUNCTIONING AS A "COMMUNICATING SPACE" PER NFPA 101 |
| | SECTION 8.6.8; HOWEVER, REQUIREMENT #3 REQUIRES THAT |
| | SUCH OPENINGS SHALL BE SEPARATED FROM CORRIDORS. |
| | |
| | SHEET AE105: PROVIDE PANIC HARDWARE FOR UNMARKED |
| | SECONDARY EXIT ACCESS DOOR IN BALLROOM #248A. |
| | |
| | SHEET AE106: BAR TERRACE #214 FEATURES A FIRE PIT. |
| | INDICATE IF THE FIRE PIT FLAME WILL BE OPEN OR SCREENED |
| | FROM OCCUPANTS. |
| | |
| | SHEET FP101: RECEIVING #142, MECHANICAL #103 AND |
| | STORAGE #126 NOT INDICATED AS ORDINARY HAZARD GROUP 1 |
| | PROTECTION. |
| | |
| | SHEET FP101: WILL THE "COVERED TERRACE" CEILING |
| | ADJACENT TO STAIR #4 BE PROTECTED WITH SPRINKLERS? WHAT |
| | ABOUT THE OTHER EXTERIOR OVERHAND CEILINGS, SUCH AS BAR |
| | TERRACE #214, WILL THEY BE PROTECTED? |
| | |