| 2014-07-05 12:43:32 | BUILDING PLAN REVIEW |
| | PERMIT: 14050097 |
| | ADD: 8100 IBIS BLVD |
| | CONT:THE WEITZ CO. |
| | TEL: (561)686-5511 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. JULY 12/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) NOTE SHEET G-1 101 LIFE SAFETY SHEET LOWER LEVEL |
| | UNDERTHE HEADING USE & OCCUPANCY INDICATES THE KITCHEN |
| | AS 200 GROSS, THE FIRE COMMENT STATES THAT UNDER THE |
| | FIRE CODES THEY USE 100 SF/ OCCUPANT. WHEN THERE IS A |
| | DIFFERENCE IN CODES, THE MOST RESTRICTIVE SHALL APPLY. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 102.1. |
| | |
| | 1A) THE BUILDING CODE ANALYSIS FOUND ON G-1-101 DOES |
| | NOT INDICATE IF THE OCCUPANCIES ARE DESIGNED AS |
| | SEPARATED OR NON-SEPARATED? |
| | 2010 FBC-B 508.3 OR 508.4. |
| | |
| | 1B) G1-101 DINING ROOM 131 INDICATES A OCCUPANCY LOAD |
| | OF 67 TRAVELING THROUGH THE EXTERIOR DOUBLE DOORS. WHEN |
| | FIGURING THE OCCUPANCY LOAD AT 15 SQ FT / OCC WITHOUT |
| | THE BAR THE LOAD IS APPROX. 60 OCCUPANTS WHICH WILL |
| | REQUIRE A 2ND EXIT. 2010 FBC-B 1008.1.2. |
| | PLEASE ALSO UPDATE THE AMOUNT OF OCCUPANTS THAT WILL BE |
| | TRAVELING THROUGH THE EXTERIOR DOUBLE DOORS. |
| | |
| | 1C) G1-101 CARD ROOM 185 HAS (2) EXIT DOORS THAT |
| | CONVERGE INTO A SINGLE MEANS OF EGRESS, THERE IS NO 2 |
| | SEPARATE MEANS OF EGRESS FROM THIS ROOM. A CONVERGING |
| | MENAS OF EGRESS. |
| | |
| | 1D) IN BOTH THE CULTURAL CLASS # 125 & THE TRAINING |
| | ROOM # 169 ARE BOTH TAKEN AT 20 SQ FT/ OCC. THE 20 SQ |
| | FT IS TAKEN WITH AN EDUCATIONAL SETTING KINDERGADEN |
| | -12TH GRADE. FOR ADULT EDUCATION IN COLLEGES IT IS |
| | CONSIDERED BUSINESS OCCUPANCY. THIS IS A MULTI-PURPOSE |
| | ROOM WHERE A NASSEMBLY OCCUPANCY CAN BE TAKEN AT 15 SQ |
| | FT/ OCCUPANT. 2010 FBC-B TABLE 1004.1.1. |
| | |
| | 2) SHEET AE105: |
| | |
| | 2A) MEETING ROOMS 225 A& B BOTH INDICATE THE USE OF A |
| | NANAWALL SYSTEM, PLEASE PROVIDE THE MANUFACTURERS |
| | SPECIFICATION AS TO HOW THIS SYSTEM WILL FOLD BACK AND |
| | NOT PROJECT INTO THE EXIT ACCESS CORRIDOR MORETHAN |
| | (7INCHES). 2010 FBC-B 1008.1.9.11 |
| | DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL |
| | LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF THE REQUIRED |
| | WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY, OR LANDING, |
| | NOR PROJECT MORE THAN 7 INCHES (178 MM) INTO THE |
| | REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY OR |
| | LANDING, WHEN FULLY OPEN. |
| | |
| | 2B) THE MONUMENTAL STAIR # 209 INDICATES SEE DETAIL #5/ |
| | AE.402 THIS DETAIL DIRECTS YOU TO DETAIL # 1/ A320 THIS |
| | IS A ELEVATION CUT SECTION THROUGH THE MONUMENTAL |
| | STAIR. PLEASE SEE 2010 FBC-B SECTION 708.2 EXCEPTION |
| | 2.1 THAT REQUIRES A DRAFT CURTAIN AND CLOSELY SPACED |
| | SPRINKLERS IN ACCORDANCE WITH NFPA 13. |
| | |
| | 3) AE401 PLEASE REVIEW THE 2010 FBC-ACCESSIBILITY CODE |
| | SECTION 213.3.1 TOILET COMPARTMENTS. |
| | WHERE TOILET COMPARTMENTS ARE PROVIDED, AT LEAST ONE |
| | TOILET COMPARTMENT SHALL COMPLY WITH 604.8.1. IN |
| | ADDITION TO THE COMPARTMENT REQUIRED TO COMPLY WITH |
| | 604.8.1, AT LEAST ONE COMPARTMENT SHALL COMPLY WITH |
| | 604.8.2 WHERE SIX OR MORE TOILET COMPARTMENTS ARE |
| | PROVIDED, OR WHERE THE COMBINATION OF URINALS AND WATER |
| | CLOSETS TOTALS SIX OR MORE FIXTURES. |
| | 604.8.2 AMBULATORY ACCESSIBLE COMPARTMENTS. |
| | 604.8.2.1 SIZE. |
| | AMBULATORY ACCESSIBLE COMPARTMENTS SHALL HAVE A DEPTH |
| | OF 60 INCHES (1525 MM) MINIMUM AND A WIDTH OF 35 INCHES |
| | (890 MM) MINIMUM AND 37 INCHES (940 MM) MAXIMUM. |
| | |
| | 604.8.2.2 DOORS. |
| | TOILET COMPARTMENT DOORS, INCLUDING DOOR HARDWARE, |
| | SHALL COMPLY WITH 404, EXCEPT THAT IF THE APPROACH IS |
| | TO THE LATCH SIDE OF THE COMPARTMENT DOOR, CLEARANCE |
| | BETWEEN THE DOOR SIDE OF THE COMPARTMENT AND ANY |
| | OBSTRUCTION SHALL BE 42 INCHES (1065 MM) MINIMUM. |
| | |
| | THE DOOR SHALL BE SELF-CLOSING. A DOOR PULL COMPLYING |
| | WITH 404.2.7 SHALL BE PLACED ON BOTH SIDES OF THE DOOR |
| | NEAR THE LATCH. TOILET |
| | COMPARTMENT DOORS SHALL NOT SWING INTO THE MINIMUM |
| | REQUIRED COMPARTMENT AREA. |
| | |
| | 4) SHEET AE501: |
| | 4A) DRINKING FOUNTAINS MUST COMPLY WITH 2 HEIGHTS: 2010 |
| | FL ACC CODE 211.2 MINIMUM NUMBER. |
| | NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| | 602.7. |
| | |
| | 4B) THE GRAB BAR RANGE IS THE SAME BUT THE HEIGHT OF |
| | THE GRAB BAR IS NO LONGER TO THE CENTERLINE OF THE GRAB |
| | BAR BUT TO TOP OF THE GRIPPING SURFACE SEE 2010 FL ACC |
| | CODE 609.4. |
| | |
| | 5) THE STRUCTURAL SHEETS PROVIDE THE PRESSURES FOR THE |
| | ROOF IN VULT & VASD BUT THERE ARE NO PRESSURES GIVEN |
| | FOR THE WALL OPENINGS INTERIOR WALL ZONE 4 NOR THE |
| | CORNER WALL ZONE # 5. 2010 FBC-B 1609.6 .2010 FBC-B |
| | 1609.1.1 DETERMINATION OF WIND DESIGN- CHAPTER 6 OF |
| | ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 5.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |
| | |
| | |
| | 6) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 8) THE PLANS INDICATE THIS IS A TYPE IIIA BUILDING, |
| | PLEASE PROVIDE HOW COMPLIANCE WITH 2010 FBC-B TABLE 601 |
| | FIRE RATINGS WILL BE ACHIEVED. |
| | |
| | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |