| 2014-05-27 13:52:59 | 1ST REVIEW: |
| | |
| | 1) SURVEY PROVIDED INDICATES FLOOD ZONE IS AN A-6; FIRM |
| | MAP 120229 001 B INDICATES A5, AND DOES NOT ESTABLISH |
| | THE PROPOSED FINISH FLOOR ELEVATION. |
| | SEE 107.2.5.1 DESIGN FLOOD ELEVATIONS. WHERE DESIGN |
| | FLOOD ELEVATIONS ARE NOT SPECIFIED, THEY |
| | SHALL BE ESTABLISHED IN ACCORDANCE WITH SECTION |
| | 1612.3.1. |
| | 2) PROVIDE DETAILS FOR FLOOD RESISTANCE CONSTRUCTION |
| | TECHNIQUES TO BE INCORPORATED IN THE STEM WALL AT THE |
| | CRAWL SPACE AREA. |
| | SEE 1612.5 FLOOD HAZARD DOCUMENTATION. |
| | THE FOLLOWING DOCUMENTATION SHALL BE PREPARED AND |
| | SEALED BY A REGISTERED DESIGN PROFESSIONAL AND SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL: |
| | 1. FOR CONSTRUCTION IN FLOOD HAZARD AREAS NOT SUBJECT |
| | TO HIGH-VELOCITY WAVE ACTION: |
| | 1.1 THE ELEVATION OF THE LOWEST FLOOR, INCLUDING |
| | BASEMENT, AS REQUIRED BY THE FOUNDATION INSPECTION AND |
| | THE FINAL INSPECTION IN SECTION 110.3. |
| | 1.2. FOR FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD |
| | ELEVATION WHERE PROVISIONS TO ALLOW FOR THE AUTOMATIC |
| | ENTRY AND EXIT OF FLOODWATERS DO NOT MEET THE MINIMUM |
| | REQUIREMENTS IN SECTION 2.6.2.1, ASCE 24, CONSTRUCTION |
| | DOCUMENTS SHALL INCLUDE A STATEMENT THAT THE DESIGN |
| | WILL PROVIDE FOR EQUALIZATION OF HYDROSTATIC FLOOD |
| | FORCES IN ACCORDANCE WITH SECTION 2.6.2.2 OF ASCE 24. |
| | 1.3. FOR DRY FLOODPROOFED NONRESIDENTIAL BUILDINGS, |
| | CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT |
| | THE DRY FLOODPROOFING IS DESIGNED IN ACCORDANCE WITH |
| | ASCE 24. |
| | |
| | 3) FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY |
| | DCA RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING, |
| | WINDOW, AND DOOR SUBMITTALS |
| | |
| | STEVEN KENNEDY, CBO |
| | CHIEF PLANS EXAMINER |
| | (561) 805-6710 |
| | [email protected] |
| | |
| | |